Installation and Maintenance

AXUS Circular Long Cased Axial Flow Fans

Sections 4.3, 4.4 & 5

 

are applicable to  

Ecosmart Control option only. 

4.3 Electrical Wiring - Ecosmart Control

The mains power supply to the controller must be appropriately sized 
and installed via a local isolation switch (by others). The isolator must 
also accommodate the 230V switched live (if used).

The mains supply from the Ecosmart controller to the fan must be 
appropriately sized, not exceeding 30 metres and must be a screened 
power cable, earthed at both ends. A four point gland plate is formed 
from the base of the control and in order to maintain EMC compliance, 
an EMC glanding kit is supplied.

Ecosmart controls and sensors are supplied with 10 metres of data 
cable plugged at both ends, if used these can now be fitted and plugged 
in to the low voltage sockets on the Ecosmart control board.

 All other 

low voltage connections i.e. BMS can also be completed.

N

L

SL

Remove this link wire if:
1. a switched live signal is connected.
2. A ES-PIR, ES-TC or BMS signal
is connected. 

Max     SL run on

Min         

Trickle  

  Test

1

0  

Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx

Ecosmart

Earth

DAMPER

FAULT     RUN

         

E  

L3

  N  

L2   

  L1    

E      N     L1    L2   L3

Mains supply connections
400V 50Hz 3ph + Neutral
via local isolator

1     3  

  5

  2  

  4  

  6

(U)

(V)     (W)

CONTACTER

A1

A2

0V

0-10V

BMS signal

'NET' connection

U     V  W     E  

DP

CL

Connections to fan via screened
power cable. Purpose made glands
are provided to earth the screening

N

RET

Note: Internal connections
between the supply
terminals, output
contactors the PCB and
inverter are made at
the factory 

IMPORTANT

Motors of 4kW and  

above must be  

connected to Delta 

IMPORTANT

The screening of the power cable must be continuous. Bridge any breaks (e.g. at local isolators) 

using braided earthing cable. Ensure the screening is earthed at both ends.

IMPORTANT

To minimise the possibility of Electro Magnetic 

Interference:

•  Always install screened cable between the control 

and the fan, maximum length 30 metres. Please consult 

Nuaire if a longer cable run is needed. 

•  This product must be earthed and always ‘earth’ the 

screened cable at both ends. Ensure that ALL earth 

connections are the same potential. Cable glands are 

provided.

•  Always keep mains supply cables and motor supply 

cables separate and DO NOT install any data cable or 

low voltage cable in the same containment as mains 

carrying cables.

Figure 5. Resilient Mounting ‘Suspended’ fixing.

Содержание Ecosmart

Страница 1: ...referred to before handling and installation Any damages or deviations should be immediately reported to the seller supplier agent quoting the order and product details from the product rating plate 2 0 Handling The fan impeller is carefully balanced and centralised in the fan case it is therefore essential that great care is exercised when handling the unit Check the weight on the rating plate de...

Страница 2: ...ppropriate fasteners and for ease of installation the cover should be removed and the casing separated from the base If cooling fans are fitted they should be disconnected while installation takes place The cable connecting the Ecosmart control and the fan must be a screened power cable not exceeding 30 metres The screening must be earthed at both ends using the special cable glands supplied Bridg...

Страница 3: ...ELTA 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply 1U 1V 1W 2U 2V 2W Motor terminal box NOTE HIGH SPEED Supply 2U 2V 2W LINK 1U 1V 1W LOW SPEED Supply 1U 1V 1W Note individual wiring instructions are included with each unit 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply L1 L2 Low Speed High Speed L3 L1 L2 L3 460V 3 phase 60Hz supply 380V 3 p...

Страница 4: ...e Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Ecosmart Earth DAMPER FAULT RUN E L3 N L2 L1 E N L1 L2 L3 Mains supply connections 400V 50Hz 3ph Neutral via local isolator 1 3 5 2 4 6 U V W CONTACTER A1 A2 0V 0 10V BMS signal NET connection U V W E DP CL Connections to fan via screened power cable Purpose made glands are provided to earth the screening N RET Note Internal conn...

Страница 5: ...eened cable with the screening grounded at one end only preferably at the inverter end 4 4 10 BMS Input Signals The BMS connection is made with a plug in connector via the socket see fig 11 To ensure the connection is made only by suitably qualified and authorised personnel the plug is not supplied It is available from R S Components Part No 403 875 or Farnell Part No 963 021 The system s response...

Страница 6: ...red airflow Remove the link wire if not required fig 7 5 3 2 Setting The Minimum Trickle Airflow Rate Nomial 20 Repeat the same procedure as for maximum airflow above but without the link wire between supply L and SL terminal Ensure the trickle switch is in the ON position Adjustment must be made on the pot marked Min Note that the minimum setting nominally 20 must be below the maximum setting oth...

Страница 7: ...K mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details 9 0 After Sales For technical assistance or further product information including spare parts and replacement components please contact the After Sales Department 6 1 Maintenance Intervals Maintenance should be carrie...

Страница 8: ...ne contaminants and unit orientation 4 2 Where installation accessories are supplied with the specified equipment eg wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4...

Отзывы: