For good EMC engineering practice, any sensor cables 

or switched live cables should not be 

placed within 50mm of other cables or on the same 

metal cable tray as other cables.

3

d) Data Cable installation

A 4-core SELV data cable is used to connect devices such as

sensors to the fan and for interconnecting multiple fan units. 

Do not run data cable in the same conduit as the mains

cables 

and ensure there is a 50mm separation between the

data cable and other cables. 

The maximum cable run between any two devices is 300m

when it is installed in accordance with the instructions. 

Please note that the total data cable length used in any system

must be less than 1000m. Keep the number of cable joints to a

minimum to ensure the best data transmission efficiency 

between devices.

e) Maximum number of devices

The maximum number of devices (including fans) that can be

connected together via the data cable is 32, irrespective of 

their functions.

NOTE: A Commissioning Procedure document (leaflet No.

671154) is available on request from the Nuaire Technical

Library Tel: 02920 885911.

2.0 Using the Test button 

(see fig. 5).

The test button allows the individual blowers within the unit to

be checked for its operation. If the fan is running already, press

the button once to stop the fan, press again to switch on the

standby fan, press again to stop and so on.

Note that the fan will return to normal operation after 

30 seconds.

3.0 LED Indication 

(see fig. 5).

PWR

GREEN: Power on & OK. RED:Too much power 

is taken by peripherals or there is a short circuit in 

the net cable. Check the cable and use a junction 

box (ES-JB) to connect some of the peripherals.

Standby

LED on when fan is not running.

Fan 1

GREEN: Fan 1 is running, RED: Fan 1 faulty.

Fan 2

GREEN: Fan 2 is running, RED: Fan 2 faulty.

Heating*

Not applicable. See note.

Cooling*

Not applicable. See note.

Fault

LED on when a fault is present on unit.

Frost*

Not applicable. See note.

Tx

LED on when the controller is transmitting data.

Rx

LED on when the controller is receiving data.

* Note that the control panel is common to all the Ecosmart

products and will have indicators for functions that are not

available in this particular fan. However these indicators

will not be illuminated.

4.0 BMS input signals

The systems response to a 0-10V dc BMS signal is given in the 

following table. Note the BMS signal will override any sensors

and user control connected in the system. 

The voltage tolerance is +/_ 125mV and is measured at the

fans terminal.

Ventilation mode

Cooling mode*

Heating mode*

Local control

0.00

-

-

OFF/trickle

0.25

-

-

Speed 1

0.50

0.75

1.00

Speed 2

1.50

1.75

2.00

Speed 3

2.50

2.75

3.00

Speed 4

3.50

3.75

4.00

Speed 5

4.50

4.75

5.00

Speed 6

5.50

5.75

6.00

Speed 7

6.50

6.75

7.00

Speed 8

7.50

7.75

8.00

Speed 9

8.50

8.75

9.00

Speed 10

9.50

9.75

10.00

* Only available on relevant unit

5.0 Setting the airflow

Setting the maximum air flow

i) Ensure the power supply is switched off and that a link wire

is connected from the supply L to the SL terminal. Unplug all

items connected to the ‘Net‘ connectors.

ii) Switch on the power supply.

Note: Ensure unit cover is securely attached. 

iii) Wait for the fan to complete its self-test operation.

iv) Remove the cover of the units external commissioning box.

Measure the airflow using standard commissioning instruments

at a suitable point in the ductwork. If adjustment is required,

rotate the pot marked ‘MAX’ to obtain the desired airflow.

Setting the minimum trickle airflow (nominally 40%)

i) Repeat the same procedure as for maximum airflow above

but without the link wire between supply L and SL terminal.

Ensure the trickle switch is in the ‘ON’ position. The adjustment

must be made on the pot marked ‘Min’.

ii) Note that the minimum setting (nominally 40%) must be

below the maximum setting, otherwise minimum setting will 

be automatically set to be the same as the maximum.

After setting the airflows, re-connect all the items disconnected

previously. Ensure that the cover over the mains terminals is

replaced and that the cover of the controls enclosure is 

securely fastened.

Installation and Maintenance

ECOSMART Direct Drive Indoor Twinfans

21. 10. 16. Leaflet Number 671114

MIN 

 

=    

 

 

MAX 

 

SL Run on  =  

TRICKLE 

TEST 

 

 

LED indicators

Min        Max   SL run on

Trickle                       Test

0  

1

Pwr

Standby

Fan 1

Fan 2

Heating

Cooling

Fault

Frost

Tx

Rx

Minimum speed 

adjustment

Maximum speed   

adjustment

Switched Live Run-On 

 

Timer adjustment

Selects trickle running:  

 

0 = off,  1 = selected

Test button

Fig. 5  Commissioning panel details.

Содержание ECOSMART TWINFANS Series

Страница 1: ...ys be positioned with sufficient space to allow removal of the access covers and subsequent removal of fan and motor assemblies etc Ductwork connections must be airtight to prevent loss of performance The method of mounting used is the total responsibility of the installer The unit has an external case side mounted control module terminal box and is supplied ready for connection into the electrica...

Страница 2: ...no power supply at the unit N N NET Fan 2 Fan 1 0V 0 10V Run Run Fault Fault Net connections for Ecosmart devices Link wire Fuses F1 F2 20mm type T fuse for fan 1 2 F3 20mm 1A type T fuse for dampers F4 20mm 1A type T fuse for control circuit Rated to fan size L L SL OP CL N RET 240V 1 ph 50Hz Switch live signal Connection to damper 5A resistive 0 5A inductive F3 F4 Volt Free Contact RUN Signal Vo...

Страница 3: ...ot available in this particular fan However these indicators will not be illuminated 4 0 BMS input signals The systems response to a 0 10V dc BMS signal is given in the following table Note the BMS signal will override any sensors and user control connected in the system The voltage tolerance is _ 125mV and is measured at the fans terminal Ventilation mode Cooling mode Heating mode Local control 0...

Страница 4: ...f Nuaire controls and or remote indicators are fitted remove the covers and carefully clean out the interiors as necessary Check for damage Check security of components Refit the access covers Replacement of Parts The only item of the fan units unit likely to require replacement are the fan motor assemblies due to a failed motor or damaged impeller In either eventuality the complete fan motor asse...

Страница 5: ...must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations 5 3 For EMC all control and sensor cables should not be placed within 50mm or on the same metal cable tray as 230V switched live lighting or power cables and any cables not intended for use with this product 6 0 COMMISSIONING REQUIREMENTS 6 1 General...

Страница 6: ...6 21 10 16 Leaflet Number 671114 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E ahu nuaire co uk W www nuaire co uk ...

Отзывы: