2

Installation and Maintenance

ECOSMART Direct Drive Indoor Twinfans

21. 10. 16. Leaflet Number 671114

Wiring Connections 

Fig. 4  Control module connection details.

1.0 Connections 

a) Control Connections 

(see fig. 4).

Net

- the 4 IDC plug-in connectors are provided for the 

connection of compatible sensors, manual controls and for 

linking the fans together under a common control. If more than

4 connections are required,  junction box (product code ES-JB)

should be used. 

See ‘d’ Data Cable Installation. 

Switch Live (SL) terminal 

- A signal of 100-230V a.c. will 

activate the fan.

Note that a signal from an isolating transformer will produce

an unpredictable result and is not recommended.

b) Damper connections

OP

-  230V 50Hz 1A max supply to open the damper

CL

-  230V 50Hz 1A max supply to close the damper

N

-  Neutral supply to damper

RET

-  230V ac return signal from the damper limit switch to

indicate the damper has reached its operating position. 

If the return signal is not present, the fan will wait for 1 minute

before starting.

Note: If a damper is not fitted, connect a link wire from OP 

to RET. This will cancel the delay.

c) Volt Free Relay Contacts

Note that the volt free contacts are not fused.  If these are used

to power any external equipment, the installer must provide

adequate fusing or other protections. 

These contacts are rated at 5A resistive, 0.5A inductive.

Run connections

-  These  contacts are  closed when the fan 

is running.

Fault connections

- No fault = the contacts are closed.

Fault = the contacts are opened (this includes no power supply

at the unit).

N

N

NET

Fan 2

Fan 1

0V

0-10V

Run

Run

Fault

Fault

Net connections for Ecosmart devices

Link wire

Fuses

F1 & F2 = 20mm* type T fuse for fan 1 & 2

F3 = 20mm 1A type T fuse for dampers

F4 = 20mm 1A type T fuse for control circuit

*Rated to fan size.

L

L

SL

OP

CL

N

RET

240V 1 ph 50Hz

Switch live signal

Connection to 

damper

5A resistive

0.5A inductive

F3

F4

Volt Free Contact

RUN Signal

Volt Free Contact

FAULT Signal

Note:

Remove the link wire if a 

switched live signal is 

present or a enabling device 

is connected to the NET

Isolation - Before commencing work make sure

that the unit, switched live and Nuaire control are 

electrically isolated from the mains supply. 

Motor Electrical Information 

Table 3.

230V single phase 50Hz only

Unit

Fuse

Code

rating 

EST 1

2A

EST 2

2A

EST 3

3.15A

EST 4

3.15A

EST 5

6A

EST 6

8A

EST 8

10A

EST 9

10A

Electrical Detail

Because the run and start currents depend upon the duty and

associated ductwork of an individual unit, run currents will be

exceeded if the unit is operated with its cover removed. It is

therefore recommended that the unit is not run for prolonged

periods in this condition.

Testing after installation

Ensure that the Fan unit and any specified controls are fitted

securely according to the instructions.

Switch on the mains supply. push the test button to run each

fan and check that they run satisfactorily.

If a switched live signal is used, activate this signal and check

that the fan runs. De-activate the switched live signal and check

the run-on-time; adjust if necessary.

Adjust the set point of any sensors and PIR; check that they

function correctly.

Adjust the maximum and minimum airflow (if required) by 

following the commissioning procedures.

Содержание ECOSMART TWINFANS Series

Страница 1: ...ys be positioned with sufficient space to allow removal of the access covers and subsequent removal of fan and motor assemblies etc Ductwork connections must be airtight to prevent loss of performance The method of mounting used is the total responsibility of the installer The unit has an external case side mounted control module terminal box and is supplied ready for connection into the electrica...

Страница 2: ...no power supply at the unit N N NET Fan 2 Fan 1 0V 0 10V Run Run Fault Fault Net connections for Ecosmart devices Link wire Fuses F1 F2 20mm type T fuse for fan 1 2 F3 20mm 1A type T fuse for dampers F4 20mm 1A type T fuse for control circuit Rated to fan size L L SL OP CL N RET 240V 1 ph 50Hz Switch live signal Connection to damper 5A resistive 0 5A inductive F3 F4 Volt Free Contact RUN Signal Vo...

Страница 3: ...ot available in this particular fan However these indicators will not be illuminated 4 0 BMS input signals The systems response to a 0 10V dc BMS signal is given in the following table Note the BMS signal will override any sensors and user control connected in the system The voltage tolerance is _ 125mV and is measured at the fans terminal Ventilation mode Cooling mode Heating mode Local control 0...

Страница 4: ...f Nuaire controls and or remote indicators are fitted remove the covers and carefully clean out the interiors as necessary Check for damage Check security of components Refit the access covers Replacement of Parts The only item of the fan units unit likely to require replacement are the fan motor assemblies due to a failed motor or damaged impeller In either eventuality the complete fan motor asse...

Страница 5: ...must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations 5 3 For EMC all control and sensor cables should not be placed within 50mm or on the same metal cable tray as 230V switched live lighting or power cables and any cables not intended for use with this product 6 0 COMMISSIONING REQUIREMENTS 6 1 General...

Страница 6: ...6 21 10 16 Leaflet Number 671114 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E ahu nuaire co uk W www nuaire co uk ...

Отзывы: