This leaflet is intended to support the main Installation and

Maintenance Instructions supplied with the fan unit. (Leaflet

Number 671142) available on request from the Nuaire Technical

Library. Telephone: 02920 885911.

Note: These units feature a commissioning box mounted on

the case exterior for your convenience. 

The main connections etc are located in the module inside

the fan casing.

1. Getting started

The Ecosmart Twinfan is designed for maximum control 

flexibility. Apart from the power supply, an enabling signal is

always

required to set the fan running. This enabling signal

can be a switched live signal (connected to the SL terminal of

each fan) or an enabling device plugged in the NET connection

(see table ‘Ecosmart compatible devices’)

.

If an enabling signal is not available, connect a link wire

between ‘L’ & ‘SL’.

Additional sensor and manual control may be added. For 

example: to run the fan with a temperature sensor, connect a

link across L to SL (enabling signal) and connect a temperature

sensor in one of the sockets labelled ‘NET’ 

The fan will now adjust it’s speed according to temperature.

To obtain manual control, connect a link across L to SL

(enabling signal) and connect a user control in one of the 

sockets labelled ‘NET’.

Ecosmart compatible devices

Enabling Devices

ES-PIR:

PIR Sensor

ES-TC:

7 day Timeclock

Sensors

ES-TEMP:

Temperature Sensor

ES-RH:

Humidity Sensor

User Controls

ES-UCF:

Fan only control

ES-UCFH:

Fan and Heating Control

(heating will only operate within relevant units)

Others

ES-JB:

Junction Box (to add extra sensors etc)

ES-AVI:

Audio Visual Fault Indication

Note that these Ecosmart devices will affect all the fans linked

using the SELV data cable. 

The switched live signal will only affect the fan to which it is

connected.

New devices are constantly in development, please contact us

for latest range details.

1

10. 05. 17. Leaflet Number 671154

COMMISSIONING

ECOSMART TWINFANS

(EST-X/R/B)

1 phase, Direct Drive, 

Run & Standby for roof/external use

The EMC Directive 
2

01

4/

30

/E

U

  

The Low Voltage 
directive 
20

14

/

3

5/E

U

INDOOR USE ONL

Y

Connection 
to Damper

N

L

SL

OP

CL

N

RET

RUN

RUN

FAULT

FAULT

240V 1ph 
50Hz mains 
supply

NOTE: Remove the link wire if a switched live 
signal is present or an enabling device or BMS 
is connected to the'NET'

Switch live signal
(if required)

F3

FUSES
F1 & F2 = 20mm *   type T fuse for fan 1 and fan 2
F3 

  = 20mm 1A type T fuse for dampers

F4 

  = 20mm 1A type T fuse for control circuit

* rated to fan size

NET connections for ECOSMART devices
eg sensors and inter-connections of fans

F4

NET

N

L

Volt Free Contact  
RUN signal

Volt Free Contact  
FAULT signal

5A resistive
0.5A inductive

Link
wire

Fan 2      Fan 1

      OV
0-10V 

0-10V 
signal
from 
BMS

Figure 1.  Fan Control module connection details.

Figure 2  External Commissioning 

Box details.

Switched Live Run-On 
Timer adjustment

0 = off. 1 = selected