NuAire ECOSMART TWINFANS EST-X Скачать руководство пользователя страница 2

2

Commissioning

ECOSMART Direct Drive roof/external Twinfans

2. BMS Signal

The systems response to a 0-10V dc BMS signal is given in the 

following table. Note the BMS signal will override any sensors

and user control connected in the system. 

The voltage tolerance is +/_ 125mV and is measured at the fans

terminal.

Ventilation mode

Cooling mode*

Heating mode*

Local control

0.00

-

-

OFF/trickle

0.25

-

-

Speed 1

0.50

0.75

1.00

Speed 2

1.50

1.75

2.00

Speed 3

2.50

2.75

3.00

Speed 4

3.50

3.75

4.00

Speed 5

4.50

4.75

5.00

Speed 6

5.50

5.75

6.00

Speed 7

6.50

6.75

7.00

Speed 8

7.50

7.75

8.00

Speed 9

8.50

8.75

9.00

Speed 10

9.50

9.75

10.00

* Only available on relevant un

3. Commissioning Procedure

Setting the Maximum air flow

i) Ensure the power supply is switched off and that a link wire

is connected from the supply L to the SL terminal.

Unplug all items connected to the ‘Net‘ connectors.

ii) Switch on the power supply whilst still maintaining access to

the adjustment pots.

NOTE care must be taken as live parts are accessible.

iii) Wait for the fan to complete its self-test  operation.

iv) Connect a manometer across the tappings provided on

the outside of the casing. Adjust the pot marked ‘Max’ to its

maximum position. Read the manometer, transfer the pressure

value to the relevant curve and read the volume flow.

Mark the operating point on the curve and draw a parabolic

system line between the origin and this operating point (point A

on fig. 3). Adjust the ‘Max’ pot so that the pressure reading

corresponds with the required airflow (point B of fig. 3).

Setting the Minimum/trickle airflow 
(nominally 40%)

i) Repeat the same procedure as for maximum airflow above

but without the link wire between supply L and SL terminal.

Ensure the trickle switch is in the ‘ON’ position.

The adjustment must be made on the pot marked ‘Min’

ii) Note that the minimum setting (nominally 40%) must be

below the maximum setting, otherwise minimum setting will be

automatically set to be the same as the maximum.

After setting the airflows, reconnect all the items disconnected

previously.

Ensure that the cover over the mains terminals is replaced and

that the cover of the controls enclosure is securely fastened.

3. Using the graphs

The graphs are designed to assist in the establishment of the

desired air volume flow rate for the installation.

After the fan is installed in the ventilation system and connected

to the power supply, connect a manometer across the pressure

tappings on the outside of the fan casing. Note that negative

pressure is present at the fan inlet and positive at the fan 

outlet; the combined value is required. 

Set the fan to run at maximum speed as per commissioning 

procedure and take the pressure reading (in Pa) across the fan.

Use the relevant graph for the fan, plot the pressure point and

read the volume flowrate.

For example; if the pressure is 100Pa, draw a horizontal line

from 100Pa until it touches the curve (see fig. 3 point A). 

Drop the line vertically down to give the volume flow of the fan.

If it is necessary to adjust the flowrate, draw a parabolic 

system line between the origin and the operating point.

Alternatively draw a straight line; this should give a reasonable

estimate in most installations. Draw a straight line from the

required airflow (point C) up to meet the system line (point B)

and read the corresponding pressure value (point D). 

Adjust the pot so that the manometer gives the same pressure

reading as point D to obtain the required airflow.

Note that the typical minimum volume achievable with this

fan range is approximately 40%.

10. 05. 17. Leaflet Number 671154

Figure 3. Typical EST graph (size 1 unit shown).

150

50

100

250

200

Pressure across manometer tapping & atmosphere (Pa)

Volume flow (l/s)

0

5

0

4

0

0

6

0

3

0

2

0

1

Pressure 
Reading

Volume 
Flow Rate

A

C

D

B

0

Отзывы: