Isolation - Before commencing work make sure

that the unit, and Nuaire control are 

electrically isolated from the mains supply.

3.0 Wiring

The electrical wiring must be carried out by competent persons, in 

accordance with good industry practice and should conform to all

governing and statutory bodies i.e. IEE, CIBSE, COHSE etc.

Connections 

a) Control Connections

Net

- the 4 IDC plug-in connectors are provided for the connection

of compatible sensors, manual controls and for linking the fans

together under a common control. If more than 4 connections are

required, the junction box (product code ES-JB) should be used

(see data cable installation)

.

Switch Live (SL) terminal

A signal of 100-230V a.c. will activate

the fan. 

Note that a signal from an isolating transformer will produce

an unpredictable result and is not recommended.

b) Damper Connections

OP

230V 50Hz 1A max supply to open the damper

CL

230V 50Hz 1A max supply to close the damper

N

Neutral supply to damper

RET 

-

230V ac return signal from the damper limit switch indicates

the damper has reached its operating position. If the return signal

is not present, the fan will wait for 1 minute before starting. 

Note: If a damper is not fitted, connect a link wire from OP to

RET. This will cancel the delay.

c) Volt Free Relay Contacts

Note that the volt free contacts are not fused.  If these are used to

power any external equipment, the installer must provide adequate

fusing or other protections. 

These contacts are rated at 5A resistive, 0.5A inductive.

Run connections

- These contacts are closed when the fan is 

running.

Fault connections

- No fault = the contacts are closed.

Fault

= the contacts are opened.

Heat demand - 

contacts closed when heating is selected.

d) Data Cable Installation

A 4-core SELV data cable is used to connect devices. 

Do not run data cable in the same conduit as the mains cables and

ensure there is a 50mm separation between the data cable and

other cables. The maximum cable run between any two devices is

300m when it is installed in accordance with the instructions.

Please note that the total data cable length used in any system

must be less than 1000m. Keep the number of cable joints to a

minimum to ensure the best data transmission efficiency

between devices.

e) Maximum Number of Devices

The maximum number of devices (including fans) that can be 

connected together via the cable is 32, irrespective of their functions.

f) Other Low Voltage Cables

Follow the basic principle (as d). Keep the cable run as short as 

possible, less than 50 metres.

Electrical Details

2

21. 10. 16. Leaflet Number 671169

Installation and Maintenance

ECOSMART Squrbo Fans

Fans without 

Fans with 

Electric Heater

Electric Heater

Unit

flc 

Unit

flc 

Code

(amps)

Code

(amps)

ESS1/ESSE1

0.32

ESS1-E

4.7

ESS2/ESSE2

0.34

ESS-2E

7.0

ESS3/ESSE3

0.72

ESS-3E

9.5

ESS4/ESSE4

0.92

ESS-4E

14.0

ESS5/ESSE5

0.92

ESS-5E

20.5

ESS6/ESSE6

2.95

ESS6-E

20.0

ESS6-2L

2.95

LPHW Coil

15mm  dia. 

copper pipes 

4 port valve

Strainer

Isolating valves

Return

Flow

Installer connections

Installer connections

Figure 3.

Installing the 

Water Circuit

It is recommended that all joints are

checked for leaks when commissioning

and a strainer and isolating valves

are fitted (by others) for ease of 

maintenance.  

(See figure 3).

Содержание Ecosmart Squrbo Series

Страница 1: ...125 150 150 330 140 115 7 4 ESS2 ESSE2 185 302 630 150 150 150 330 140 150 8 1 ESS3 ESSE3 235 350 700 200 150 150 330 140 170 13 0 ESS4 ESSE4 285 350 672 250 150 150 330 140 170 13 8 ESS5 ESSE5 350 40...

Страница 2: ...ions These contacts are closed when the fan is running Fault connections No fault the contacts are closed Fault the contacts are opened Heat demand contacts closed when heating is selected d Data Cabl...

Страница 3: ...rost Tx Rx Ecosmart Heat demand signal L N E 230V 50Hz 1ph mains Earth Run signal Fault signal HEAT DAMPER DEMAND 0V 0 10V BMS signal Speed Controller Connections to Damper FAULT RUN N L SL DP CL N RE...

Страница 4: ...evant unit Settings Setting the maximum air flow ii Ensure the power supply is switched off and that a link wire is connected from the supply L to the SL terminal Unplug all items connected to the Net...

Страница 5: ...end on the site conditions Note It is important to allow sufficient time for the heater battery to cool down before beginning work Cleaning Control Box and Sensors if fitted Remove covers and carefull...

Страница 6: ...product the following general requirements should be noted 5 1 Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed...

Страница 7: ...7 21 10 16 Leaflet Number 671169 Notes...

Страница 8: ...8 21 10 16 Leaflet Number 671169 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E info nuaire co uk W www nuaire co uk...

Отзывы: