The unit must remain switched on at all times to maintain

ventilation within the dwelling. Turning the unit off will

cause long term damage to the unit and building fabric.

This appliance is not intended for use by persons 

(including children) with reduced physical, sensory or

mental capabilities, or lack of experience and knowledge,

unless they have been given supervision or instruction

concerning the use of the appliance by a person for their

safety. Children should be supervised so that they do not

play with the appliance.

MRXBOX95B-LP1 (Standard Unit)

MRXBOX95B-LP1-OH (Opposite Hand Unit)

Mechanical Ventilation Unit with Heat Recovery 

& Summer Bypass for Ceiling Void Mounting

Installation and Maintenance

1.0 Introduction

The LP1 ceiling void mounted unit is designed to provide

mechanical supply and extract ventilation with heat recovery

and incorporates summer bypass.

The unit is fitted with two independent fans. Each fan has full

speed control for background and boost ventilation rates. 

To recover heat from the extract air the heat exchanger block 

is utilised. The heat exchanger can recover up to 80% of the 

normally wasted heat.

The bypass damper shall open automatically via a wax 

actuator allowing the air to bypass the heat exchanger to 

deliver fresh filtered air during the warmer months.

The unit is fitted with a frost protection mode, in the event of

the fresh air temperature dropping below -5 Deg C the supply

fan will switch off. The unit will then automatically switch back

on when the temperature raises back above -5 Deg C.

2.0 Installation

Installation must be carried out by competent personnel in

accordance with the appropriate authority and conforming 

to all statutory governing regulations. All mains wiring must 

be in accordance with the current I.E.E. Regulations, or the

appropriate standards. Ensure that the mains supply (Voltage,

Frequency and Phase) complies with the rating label. 

Please note a clear working space is required around the

installed unit to allow the cover to be removed and provide 

sufficient access for maintenance such as filter change.

The fan must be installed indoors, in a suitable ceiling void

away from direct sources of frost, heat, water spray or 

moisture generation. For a vibration-free result the unit must

be mounted to a solid surface in the void.

The unit is designed for ceiling mounting only (Horizontal 

surface).

1. The unit is supplied with a steel mounting bracket.

2. Position & secure the steel bracket to the ceiling using

appropriate fixings (supplied by others), ensuring that the

two outer fixing holes on the unit are accessible (see fig 2).

Note: The mounting bracket should be on the same side as the

condensate take off.

3. The unit can now be offered into position & located into the

mounting bracket.

4. Using appropriate fixings (supplied by others), fix the unit to

the ceiling. It is recommended that the unit is fixed through

three holes on the non-bracket side and the two outer holes on

the bracket side.

Note: The unit must be installed in an upright position as 

shown for the condensate drain and for compliance with safety

regulations relating to IP protection for water drip ingress.

1

27. 11. 17. Leaflet Number 671582

Spigot 1.

Spigot 4.

Spigot 3. 

Spigot 2.

Figure 1a. Airflow through unit (Standard unit).

Spigots 1 to 4

1. Intake air (Fresh Air from outside).
2. Supply Air (Supply in to house).
3. Extract Air (Warm air from house).
4. Exhaust Air (Waste air to outside). 

Figure 1b. Airflow through OH unit (Opposite hand unit).

Spigots 1 to 4

1. Intake air (Fresh Air from outside).
2. Supply Air (Supply in to house).
3. Extract Air (Warm air from house).
4. Exhaust Air (Waste air to outside). 

Spigot 3.

Spigot 2.

Spigot 1. 

Spigot 4.

The EMC Directive 

2014/30/EU  

The Low Voltage 

Directive 

2014/35/EU

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA  

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk

Содержание Ecosmart MRXBOX95B-LP1

Страница 1: ...Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for ma...

Страница 2: ...ad Hand tight should be adequate to form a proper seal 2 2 Extract input areas The unit is designed to extract air from all wet rooms e g bathroom kitchen en suite utility room with sink WC s do not n...

Страница 3: ...step 2 calculation Step 3 The required airflow rates are as follows n the maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the ma...

Страница 4: ...oom to outside via air brick Supply and extract ducts from external air bricks to the unit needs to be insulated Minimum distance as specified in Building Regulations Top of ceiling void Intake air fr...

Страница 5: ...ir Spigot 4 Air Exhaust Spigot 1 Air 250 Intake Heat exchanger Bypass chamber Supply fan Extract fan 21 5mm condensate pipe Drip tray Wire frame lter Wire frame lter Bypass 4 damper 1 2 3 735 Filter a...

Страница 6: ...al cable tray as other cables Figure 9 7 0 Electrical Connection Please note the electrical connection of the unit must be be carried out by a qualified electrician The unit is supplied with a flexibl...

Страница 7: ...al gov uk building regulations approved documents partf associated A calibrated moving vane anemometer and hood will be required to carry out commissioning 5 Adjustment valves should be locked in plac...

Страница 8: ...ty is conditional on planned maintenance being undertaken This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissi...

Отзывы: