2.7 ADF 2010 Ventilation Calculations
Design of MVHR Systems

The MVHR system has been sized for the winter period. Additional
ventilation may be required during the warmer months and it has
been assumed that the provisions for purge ventilation (e.g. openable
windows) could be used.

Step 1:

For any design air permeability, determine the whole dwelling

ventilation supply rate 

from Table 2.

As an alternative where the design air permeability is intended to be
leakier than (>) 5m

3

/(h.m

2

) 50 Pa, allow for infiltration for all

dwelling types by subtracting from the whole dwelling ventilation
supply rate 

from Table 2

; 0.04 x gross internal volume of the dwelling

heated space (m

3

).

Step 2:

Calculate the whole dwelling extract ventilation rate by 

summing the individual room rates for ‘minimum high rate’ 

from

Table 1.

(For sanitary accommmodation only, as an alternative, the purge 
ventilation provisions given in ADF 2010 can be used where security
is not an issue. In this case ‘minimum high extract rate’ for the 
sanitary accommodation should be omitted from the step 2 
calculation).

Step 3: 

The required airflow rates are as follows:

n

the maximum whole dwelling extract ventilation rate (e.g. boost) 
should be at least the greater of step 1 and step 2. 
Note that the maximum individual room extract rate should be 
at least those given

in table 1.

for minimum high rate.

n

the minimum air supply rate should be at least the whole building
ventilation rate found in step 1.

For Scotland refer to BRE Digest 398.

For further information refer to “Domestic Ventilation Compliance
Guide” www.planningportal.gov.uk/buildingregulations/approved
documents/partl/compliance

4

27. 11. 17. Leaflet Number 671722

Installation and Maintenance

The WM2 Wall Mounted Range of Units

10

53

706

448

55

172    

 CR S

144

417 CRS

=

=

142

UNI T WEI GHT =  58Kg

CONDENSATE DRAIN CONNECTION
(OPPOSITE HAND CONFIGURATION)

142

125.0

Ø

Condensate drain
connection
(standard
configuration)

Condensate drain
connection
on centre line
of unit

if ancillary distribution box (DB-WH1) is to be used refer to documentation
supplied with DB-WH1 for additional infomation as requirements will differ.

Condensate drain connection
(opposite hand configuration)

3.0 Dimensions 

Figure 9. 

Содержание Ecosmart MRXBOX95-WM2-1Z

Страница 1: ...all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase com...

Страница 2: ...d the cover plate slid along the length to bond against the base panel of the enclosure preventing noise breakout fig 7 Figure 7 1 The condensate must be discharged under a water level in a U trap dra...

Страница 3: ...t duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum...

Страница 4: ...sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows n the maximum whole dwelling extract ventilation rate e g boost should be at least...

Страница 5: ...ply duct Air supply to lounge via Air Valve in ceilings Extract air from kitchen bathroom via Air Valve in ceilings Air supply to bedrooms via Air Valve in ceilings Top of ceiling void Top of ceiling...

Страница 6: ...on to Remote Fail Indicator Ref MRXBOX95 RFI Optional 3 2 Figure 11a Note Wiring is for reference purposes only as the connections in fig 11a are factory fitted The unit is pre wired with a 2 metre fl...

Страница 7: ...st to that set by the commissioned boost speed The set point can be found on the front of the unit see Fig 14 and is at its least sensitive when turned fully clockwise Note that the sensor is measurin...

Страница 8: ...rranty The 5 year warranty starts from the day of delivery and includes parts and labour for the first year and parts only for the remaining 4 years This warranty is void if the equipment is modified...

Отзывы: