Warning - Isolate the mains power before carrying 

out any electrical wiring.

The unit must be supplied via an all-pole isolator with 

at least 3mm gap as illustrated in the figure 7.

The recommended fuse rating is 1A.

This unit must be earthed.

A permanent mains supply must be connected 

for normal operation.

4

10. 05. 17. Leaflet Number 671638

6.0 Electrical Wiring

Remove the three screws holding the top cover to gain access to

wiring terminals.

Feed the cable through the grommetted hole and wire into the 

terminals as shown in figure 7. 

Secure the cable using the cable clamp supplied.

Electrical rating: 230V~50Hz 3W.

It is recommended that the power is isolated from the damper

until the system is ready to be commissioned.

Installation and Maintenance

CVD Constant Volume Dampers

7.0 Operation

The trickle and boost flowrate together with the run-on time are

adjustable via relevant potentiometers. These are accessible through

the top cover without removing the lid.

Use a screwdriver to make the adjustment. Take care not to rotate

the potentiometer beyond its limits of travel.

When power is connected; the damper will enter a test mode which

takes approximately 2 minutes. 

The damper will start operating normally after this period.

Figure 9a. Dial calibration for CVD125 (see Note 1)

Figure 9b. Dial calibration for CVD150

Figure 9c. Dial calibration for CVD200

Note 1: These calibrated settings were obtained under laboratory

conditions. Actual site conditions may cause these calibrations

to drift. The markings are therefore for guidance only.

Figure 7. General wiring viewed with cover removed. 

Trickle

Boost 

    Run-on

10

15

20

5

25

10

15

20

5

25

15

30

45

1

60

L

SL

N

Socket for 

CVD-PIR

L

N

230V-50Hz 
supply via
fused spur or
isolator

230V-50Hz 
control signal
to select boost
setting

Trickle

Boost 

    Run-on

10

15

20

5

25

10

15

20

5

25

15

30

45

1

60

L

SL

N

Isolator     

(by others) 

1A Fuse

L

N

230V-50Hz 
supply via
fused spur or
isolator

Light

Isolator     

(by others)  1A Fuse

Figure 8. Typical wiring with boost setting triggered by light switch.