background image

38

30. 07. 20. Document Number  671760

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

BPS V-CO

Installation Manual

 
 
 
 
 
 
 
 
 
 
 
 

29 

Setting Favourites

Enable  

On

Fan Boost   

Off

Heat Boost 

 

Off

Trickle Mode 

Off

Name

Write

ID

Description

Status

Function

9.7 Security

If the target page or favourite page is selected as the home page 
and a security password is set, the home page will be locked. 
The only way to exit the target screen in this case is to press the 
Nuaire logo to the top right of the screen for 5 seconds. A security 
password will then be requested to access the main menu. The 
security password timeout is the same as the standby timer and set 
via the display settings.

9.7.1 Setting User Password

Navigate to the settings page.

Select the right arrow twice to reach the display settings screen.

Change the user password a 4 digit number.

The user password will now be requested each time a locked 
object is written.

The user password is also needed to exit the target page (when the  
homepage is set to target).

9.7.2 Setting Service Password

Navigate to the settings page.

Select the right arrow twice to reach the display settings screen.

Change the service password a 4 digit number.

The service password will now be requested each time the settings 
page is accessed.

9.7.3 Disable Writing Values

Navigate to the settings page.

Select the right arrow six times to reach the View Config screen.

De-select the write tickbox, all controller points are now read only.

A service password will need to be set to stop users re-enabling the 
write function.

9.7.4 Allow Writing Of Basic User Values

Navigate to the settings page.

Select the right arrow six times to reach the View Config screen.

Select the function tick box and lock.

Select the home icon.

Navigate to the network page.

Select the appropriate controller.

Navigate to the required object, see “Exposed BACnet Object List” 
for a full list.

Select any values that need password protection. A black lock 
indicates a locked value.

When finished, navigate back to the View Config screen in the settings 
section. Remove the Function tick and enable writing of values.

30 

Allowing Writing of Values

NS Zone Temp 

0°C

NS Zone 1 Temp 

0°C

NS Zone 2 Temp 

0°C

NS Zone 3 Temp 

0°C

 A user password will need to be set to stop writing of locked values. It 
is recommended that all values are locked except the following:

Enable

Time Schedule

Fan Boost

Heat Boost

Software Setpoint

9.7.5 Setting Schedule

Standard BACnet schedule objects can be adjusted in the same way 
as any other BACnet object.

The BACnet schedule function consists of an array of singular time 
values with a corresponding ON/OFF state. In order to end an ‘ON’ 
period, a new value must be created with a value of ‘OFF’. This new 
value’s time can be adjusted to the desired end time.

Select a schedule object via object browser or the favourites menu to 
access the following screens.

Time Schedule

**-**-**

**-**-**

Effective Period 

** Denotes All

Weekly 

Schedule

31 

Scheduling Page

 

Содержание B 07T/CO Series

Страница 1: ...be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue...

Страница 2: ...l heating LPHW Electric or Reverse Cycle DX and cooling Chilled Water or Reverse Cycle DX model variants are available The Reverse Cycle coils are supplied as standard with inbuilt PAC Control and opt...

Страница 3: ...shorter modules the fork lifting points will be along the length of the section without a covered channel Figure 2 Palletised Forklift Assembly with base frame Slings via spreaders fitted to unit wit...

Страница 4: ...s or exhaust ventilators Once assembled and in position sufficient free space must be available adjacent to the unit for future inspection maintenance component service repair and replacement and conn...

Страница 5: ...r to operating the unit by moving the belt drive motor from its transport to operating position 4 7 Weather Resistant Units The units are supplied in multiple sections and have weather resistant roof...

Страница 6: ...that may be attached to the fan or motor base frame and that all traps are primed Close all access door seals for damage and replace any panels that have been removed IMPORTANT If a frost coil is not...

Страница 7: ...ts B AT FE R BPS size Frost Coil Electric 36kW Right Handed for Thermal Wheel Units B AT FE L BPS size Frost Coil Electric 36kW Left Handed for Thermal Wheel Units Frost Coil LPHW 3 B AV FL R BPS size...

Страница 8: ...ndensate tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possib...

Страница 9: ...Unit Right Hand Unit Open Exhaust Open Exhaust Open Extract Open Exhaust Open Exhaust 48 49 53 50 51 52 54 55 Access For Left Hand Plate Heat Exchanger Units Top View of Access For Left Hand Plate Hea...

Страница 10: ...supply contactor 7 3 Unit Power Supply Details FLC Denotes any Character These heater models require a separate power supply for the electric heater section with an appropriate over current protection...

Страница 11: ...are located on the sides of the units Description iQ4E Terminal No 8DO Terminal No Di AI DO AO Fresh Air Sensor 1 4 5 1 Supply Air Sensor 2 6 7 1 Return Room Air Sensor 3 8 9 1 Input 4 4 10 11 1 Inpu...

Страница 12: ...jumpers In these cases the terminals are treated as one conductor 7 8 5 Jumper Removal Insert the operating tool blade between the jumper and the partition wall of the dual jumper slots then lift up t...

Страница 13: ...230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection...

Страница 14: ...Customer Connection Mandatory Customer Connection Optional FC BUS 100 240V RELAY RELAY RELAY RELAY RELAY CONFIGURABLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO OCOM7 OCOM6 OUT6 NC OUT5 NC OU...

Страница 15: ...RELAY RELAY RELAY RELAY RELAY CONFIGURABLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO OCOM7 OCOM6 OUT6 NC OUT5 NC OUT6 NO OUT5 NO OCOM5 OUT4 OCOM4 OUT3 OCOM3 OUT2 OCOM2 OUT1 OCOM1 COM POWER I...

Страница 16: ...for clarity 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Con...

Страница 17: ...0V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection Mandato...

Страница 18: ...Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection Mandatory Customer Connection Optional FC...

Страница 19: ...2 3 4 Key Factory Connection Customer Connection Mandatory Customer Connection Optional FC BUS 100 240V RELAY RELAY RELAY RELAY RELAY CONFIGURABLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO...

Страница 20: ...0 240V RELAY RELAY RELAY RELAY RELAY CONFIGURABLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO OCOM7 OCOM6 OUT6 NC OUT5 NC OUT6 NO OUT5 NO OCOM5 OUT4 OCOM4 OUT3 OCOM3 OUT2 OCOM2 OUT1 OCOM1 COM...

Страница 21: ...BLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO OCOM7 OCOM6 OUT6 NC OUT5 NC OUT6 NO OUT5 NO OCOM5 OUT4 OCOM4 OUT3 OCOM3 OUT2 OCOM2 OUT1 OCOM1 COM POWER IN8 ICOM8 IN9 ICOM9 IN6 ICOM6 IN7 ICOM7...

Страница 22: ...15mins for Room Module PIR s This is in addition to any software run on times 8 3 2 RM 3 Speed Fan Override ESCO TDFS Only When a RM fan speed override is available it will override fan speed function...

Страница 23: ...to reduce CO2 concentration The target CO2 sensor setpoint can be changed as one of the commissioning setpoints Room Module CO2 sensors are detected automatically 0 10V CO2 sensors need to be assigne...

Страница 24: ...exchanging or bypassing will achieve the same supply temperature 8 14 2 Room Temperature Control While an enable signal is present this mode modulates heating cooling heat exchanger bypass dampers wit...

Страница 25: ...r unit The enable run on time must be set to 3 minutes for reverse cycle units This is required in order to keep the compressor running for at least 3 minutes for each period 8 18 Night Cooling Summer...

Страница 26: ...X bypass damper is driven to bypass while fans are enabled the indicator will signal open windows HX Bypass due to Condensate pump failure will not affect windows status The Window Mode Status will in...

Страница 27: ...utput from a device BV Binary Variable A true false object which exists within a device MSV Multi State Variable This is an enumerated object which can have a number of states each represented by a nu...

Страница 28: ...the physical medium BACnet messages are always the same A router can be fitted to the network to translate BACnet between different physical media 8 37 1 Example BACnet Network 21 Example BACnet Netwo...

Страница 29: ...of the UI4 input MSV 10209 None 1 None 2 N A 3 N A 4 0 10V CO2 Sensor 5 0 10V Temperature Sensor 6 0 10V Humidity Sensor 7 0 10V Pressure Sensor 2 IN5 The 0 10 voltage at input 5 AI 10035 N A volts 3...

Страница 30: ...t Schedule object AV 18215 22 Degrees Celsius 33 T Sens Op Temperature sensor operation MSV 10215 NS Average 1 NS Average 2 Return Air Only 3 NS Return Average 33 0 10v Temp Range Temperature sensor r...

Страница 31: ...CO2 Value AV 10265 650 Parts per million 29 0 10 v CO2 Range CO2 sensor output range MSV 10200 N A 1 0 2 000ppm 2 0 4 000ppm 3 0 5 000ppm 4 0 10 000ppm 5 0 20 000ppm 29 CO2 Sensor Op CO2 sensor opera...

Страница 32: ...egrees Celsius 4 RM203 Humidity The Humidity at RM address 203 AI 10107 N A Percent Relative Humidity 8 RM203 Setpoint The setpoint at RM address 203 AV 10113 N A Degrees Celsius 5 RM212 CO2 The CO2 a...

Страница 33: ...m Unit is latched in critical alarm MSV 15309 N A 1 Normal 2 Alarm 38 Maint Alarm Maintenance Alarm MSV 15310 N A 1 Normal 2 Alarm 38 Sensor Alarm Sensor Out of Range MSV 17009 N A 1 Normal 2 Alarm 39...

Страница 34: ...s Ignore all MSTP network PIR sensors MSV 10208 No 1 No 2 Yes 17 EF Max Volt The upper voltage for the extract fan AV 17273 10 Volts 17 EF Start Volt The voltage required to start the extract fan AV 1...

Страница 35: ...ade continuous along the bus length Room Modules must not be fitted more than 150metres cable length from the controller 9 5 Touch Screen ESCO LCD Field Advanced Display FAD The ESCO LCD is a user fri...

Страница 36: ...y the strategy at priority level 16 By default the ESCO LCD will override these values at priority level 8 Overriding these values is not recommended and may cause undesirable operation Be sure to rel...

Страница 37: ...e home page and a security password is set the home page will be locked The only way to exit the target screen in this case is to press the Nuaire logo to the top right of the screen for 5 seconds 28...

Страница 38: ...the View Config screen De select the write tickbox all controller points are now read only A service password will need to be set to stop users re enabling the write function 9 7 4 Allow Writing Of Ba...

Страница 39: ...he LCD The screen will automatically change to a download screen Select the item required and choose upload To download data to the LCD select the data type and choose download If a user or service pa...

Страница 40: ...e Max_Master property of the node s Device object 127 APDU Time The APDU Timeout property defines the amount of time in seconds the FAD waits for responses from other devices 3 9 10 2 Display Settings...

Страница 41: ...es are automatically detected and require no set up The majority of RM modules monitor room temperature however options are available to also monitor zone humidity carbon dioxide CO2 local temperature...

Страница 42: ...annot change via RM sensors This must be changed through a commissioning tool 10 3 Installation 10 3 1 Removing Rear Cover Use a pozi screwdriver to loosen the screw on the top of the unit Insert a co...

Страница 43: ...S 80x80 YES YES YES YES 199 fixed Max of 1 per controller Group 2 Max of 4 Per Controller ESCO TS 80x80 YES 200 203 ESCO THS 80x80 YES YES 200 203 ESCO TDS 80x80 YES YES 200 203 ESCO TDHS 80x80 YES YE...

Страница 44: ...nce of 15 ft 4 6m Based on a clear line of sight Ambient Operating Conditions 10 to 30 C 10 to 90 RH Temp Probe 10 to 60 C Ambient Storage Conditions 20 to 60 C t to 95 RH CO2 Sensor Warmup Time Less...

Страница 45: ...twisted pair with RJ12 Plugs 26AWG Room Module Room Module RJ12 Plug RJ12 Plug Room Module Sensor SA Bus RJ 12 Modular Jack 6 5 4 3 2 1 Power 15 VDC Power 15 VDC Bus and Power Common Bus and Power Com...

Страница 46: ...ve will open whether the fans are running or not This is for pipe freeze protection The LPHW section requires its own supply in order to power the valve actuator 12 2 Wiring LPHW Frost Coil Unit Sizes...

Страница 47: ...exact position prior to being removed Disposable filters should be checked and changed when they become fully laden with dust Washable filters should be removed and washed in a mild detergent flushed...

Страница 48: ...ge clean if required failure to do so may impair the performance and energy efficiency of this unit Ensure condensate drains are cleaned clear and that water can flow freely from unit Check fin coil b...

Страница 49: ...nformation including spare parts and replacement components please contact the After Sales Department If ordering spares please quote the serial number of the unit together with the part number if the...

Страница 50: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Страница 51: ...51 30 07 20 Document Number 671760 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS V CO Installation Manual NOTES...

Страница 52: ...52 30 07 20 Document Number 671760 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS V CO Installation Manual NOTES...

Отзывы: