background image

3

3

Leaflet Number 671409 February 2009

Installation and Maintenance

AXUS SVT2 High Temperature Impulse Axial Fans

Specific Commissioning and 
Servicing Requirements

Motors for Smoke Extract Fans

Exposure temperature/time: 300

o

C for 120 minutes. 

These motors are used to provide a SAFETY FUNCTION for

people in the event of fire in public premises or in the home: 

they are therefore subject to strict constraints concerning 

their operating and maintenance.

Operating constraints

i.  Check on the nameplate that the selected motor corresponds

to the maximum exposure temperature and duration.

ii.  Non ventilated motors MUST be placed in the airflow from 

the driven fan. Ventilated motors can be placed outside the 

flow.

iii. 

AFTER THE MOTOR HAS BEEN SUBJECTED TO ONE 

EMERGENCY DUTY OPERATION, IT MUST BE REPLACED.

iv.  With variable speed control. Ensure that the maximum speed

never exceeds the speed of the motor supplied by the mains 

and that the delivered power corresponds to the previous 

definitions.

These qualifications ensure the qualification of the driven

fan by the manufacturer.

Maintenance Constraints

Regular service visits must be performed on the
installation at least every 6 months, incorporating
the following checks:

i. Checking the insulation resistance 
(R>100MOhms, 500V DC)

a)  If the drain holes are blocked, open them to eliminate any 

accumulated condensation.

b)   If R<100MOhms, dry the stator in an oven and check 

the insulation 

resistance. If the fault persists, replace the stator.

c)  The stator must be replaced 5 years after installation or 

after 20,000 hours of operation.

ii. Cooling check

a)  Ensure there is no dust or grease in the entire ventilation 

circuit  (housing fins, motor cover/fan if fitted driven fan).

b) Ensure the motor runs normally when switched on for a 

few minutes.

iii. Bearing check (C3 or C4 play)

Run the motor during each maintenance visit. When the 

motor is cold, a high level of noise is caused by the texture  

of the grease. This does not indicate a bearing fault.

S2 duty only: 

The bearings must be replaced by an identical type every 

5 years. Ensure the motor runs normally when switched on 

for a few minutes.

S1 duty and Emergency in S2 duty:

a)  Permanently greased bearings. 

300

o

C range; replace on 2 pole motors after 10,000 hours  

of operation and on motors with 4 poles or more after 

20,000hours.

b) Re-greaseable bearings

The information on the motor nameplates must be strictly 

respected

(grease quantity, grease quality and re-greasing frequency). 

The bearings must be replaced after 20,000 hours of 

operation.

Replacement of parts

When ordering spares it is important to state the unit serial

number to ensure that the correct spares will be supplied.

Notes - Fixing bolts, nuts, studs, screws, spacers or washers

are not included with these parts and if required, should be

clearly specified on the order in addition to the part description

number. 

Warranty

The three year warranty starts from the day of delivery and

includes parts and labour for the first year. The labour element

is subject to full, free and safe access to the equipment as 

recommended by the CDM regulations. 

The remaining two years covers replacement parts only.

Note: Installation and maintenance of the equipment must be

undertaken as directed in the instructions provided with the

unit.

Enquiries

Please contact Nuaire Limited for information on any aspects

of the motor performance that may need clarification. Contact

must be made prior to any remedial action being taken under

the warranty. 

Please quote the motor serial number in all such cases with

detailed description of the problem.

Service Enquiries

Our service department will be happy to provide any assistance

or further information required. If you have any comments or

queries on any of our products or services please write to the

Product Information Manager at the main address on page one

of this document.

Customer Services Department 

Tel: 02920 858 585

Fax: 02920 858 586

Technical or commercial considerations may, from time to time, make it necessary to alter the design, performance and 

dimensions of equipment and the right is reserved to make such changes without prior notice.