Nuaire Limited
Western Industrial Estate Caerphilly United Kingdom CF83 1NA
T: 029 2088 5911 F: 029 2088 7033 E: [email protected] W: www.nuaire.co.uk
Introduction
The Nuaire SVT2 impulse unit comprises a high temperature
axial fan with specially designed inlet and outlet attenuators
which, along with the fan unit, are encased in a Galvanised
steel acoustic enclosure.
Fan Coding Descriptions
SVT2 - 1
(A-E)
1
2
3
1. AXUS Impulse fan
2. Case size
3. Impeller blade angle
The Nuaire SVT2 unit comprising fan/motor assembly, and
inlet & outlet silencers shall be certified for high temperature
operation at 300
O
C for 2 hours, the range shall have been type
tested to EN12101-3.
The units shall be either 2 speed or inverter driven providing,
low speed for day to day environmental ventilation and one off
operation for emergency ventilation (S1 duty). They shall also
be suitable for reversible operation.
Fully reversible options (i.e similar duty in both airflow
directions) are available, please contact Nuaire for details.
The unit shall have a unique mounting bracket, which shall
enable the bracket to be positioned as a “first fix” component
with the unit being fitted as a “second fix” component, avoiding
possible mechanical damage.
The Nuaire SVT2 unit shall have inlet guards for safety purposes
and also to prevent debris being sucked through the fan.
It also has a specially designed airflow deflector to
direct the jet stream from the fan at the required
angle sufficient to overcome the natural buoyancy
effect of the smoke. (see page 2 for adjusting).
EN12101-3 compliant, refer to EC certificate of
conformity, 0086-CPD-467873.
Handling
Always handle the units carefully
to avoid damage and distortion.
If mechanical aids are used to
lift the unit, spreaders should
be employed and positioned
so as to prevent the slings.
webbing etc. making
contact with the
the casing.
Installation
Installation must be carried out by competent personnel in
accordance with the appropriate authority and conforming
to all statutory governing regulations.
1) Fixing the support bracket to the ceiling
The support bracket is included with the unit. Using the four
slots in the top side of the bracket attach to the ceiling ensuring
that it is firmly fixed and able to take the weight (100kg) of the
SVT2 unit.
Figure 2.
2) Fitting the SVT2 unit to the support bracket
Having fixed the support bracket the SVT2 unit can now be
raised up into position between the support bracket on the
ceiling and attached when required using the holes through the
sides of the bracket and the unit.
1
Leaflet Number 671409 February 2009
Figure 3.
AXUS SVT2
300
o
C for 2hr
High Temperature Impulse Axial Fans
Installation and Maintenance
Figure 1.
The EMC Directive
2004/108/EC
The Low Voltage
directive