Introduction

The Nuaire SVT2 impulse unit comprises a high temperature

axial fan with specially designed inlet and outlet attenuators

which, along with the fan unit, are encased in a Galvanised

steel acoustic enclosure.

Fan Coding Descriptions

SVT2 - 1

(A-E)

1

2

3

1. AXUS Impulse fan

2. Case size

3. Impeller blade angle

The Nuaire SVT2 unit comprising fan/motor assembly, and 

inlet & outlet silencers shall be certified for high temperature

operation at 300

O

C for 2 hours, the range shall have been type

tested to EN12101-3.

The units shall be either 2 speed or inverter driven providing,

low speed for day to day environmental ventilation and one off

operation for emergency ventilation (S1 duty). They shall also 

be suitable for reversible operation.

Fully reversible options (i.e similar duty in both airflow 

directions) are available, please contact Nuaire for details.

The unit shall have a unique mounting bracket, which shall

enable the bracket to be positioned as a “first fix” component

with the unit being fitted as a “second fix” component, avoiding

possible mechanical damage.

The Nuaire SVT2 unit shall have inlet guards for safety purposes

and also to prevent debris being sucked through the fan. 

It also has a specially designed airflow deflector to 

direct the jet stream from the fan at the required 

angle sufficient to overcome the natural buoyancy 

effect of the smoke. (see page 2 for adjusting).

EN12101-3 compliant, refer to EC certificate of 

conformity, 0086-CPD-467873. 

Handling

Always handle the units carefully 

to avoid damage and distortion.

If mechanical aids are used to 

lift the unit, spreaders should 

be employed and positioned 

so as to prevent the slings. 

webbing etc. making 

contact with the 

the casing.  

Installation

Installation must be carried out by competent personnel in

accordance with the appropriate authority and conforming 

to all statutory governing regulations.

1) Fixing the support bracket to the ceiling

The support bracket is included with the unit. Using the four

slots in the top side of the bracket attach to the ceiling ensuring

that it is firmly fixed and able to take the weight (100kg) of the

SVT2 unit.

Figure 2. 

2) Fitting the SVT2 unit to the support bracket

Having fixed the support bracket the SVT2 unit can now be

raised up into position between the support bracket on the 

ceiling and attached when required using the holes through the

sides of the bracket and the unit. 