6

08. 05. 17. Leaflet Number 671063

Installation and Maintenance

AXUS AXR High Temperature Axial Fans

Maintenance 

Nuaire recommends all products maintained in accordance with

the HVCA “Standard Maintenance Specification for Mechanical

Services in Buildings” - Volume II Ventilating and Air

Conditioning and BS5588 Pt. 12.

Motor Maintenance

On going maintenance

Induction motors, by their very nature require minimal

maintenance. However, a regular regime of inspection is

recommended to ensure minor problems do not escalate into

breakdowns. Typical intervals would be 1000 hours of

operation or 3 months, whichever is the sooner. 

Maintenance Checklist 

Item 

Tick

No visible damage i.e.  impeller cracked, fan cowl 

bent, foot cracked etc.

No accumulation of dust or fibres on the frame 

or around the fan inlet.

No significant corrosion of the lifting lugs/

eyebolts.

No excessive vibration.

No loose fasteners.

Cables and earths are sound.

Sealing of the motor and gland plate in 

good condition.

Insulation resistance adequate, imperative this 

is checked after prolonged shutdown.

Regreasing of bearings required, 160 frames 

and above.

Bearing condition. 

Motor must be returned to manufacturer for repair.

Because the unit is certified to EN12101-3 and complying with

the construction products directive, the motor must be

returned to the motor manufacturer for replacement.

Enquiries

Please contact Nuaire Limited for information on any aspects

of the motor performance that may need clarification.

Tel: 02920

 

858

 

400

 

Contact must be made prior to any remedial action being taken

 

under guarantee.

Please quote the motor serial number in all such cases with

 

detailed description of the problem.

Policy

Our policy is one of continuous technical improvement and we

 

reserve the right to alter any detail of our product at any time

 

without prior notice.

Warranty

The 3 year warranty starts from the day of delivery and

 

includes parts and labour for the first year. The remaining 

2 years covers replacement parts only.

This warranty is void if the equipment is modified without 
authorisation, is incorrectly applied, misused, disassembled, or 
not installed, commissioned and maintained in accordance with 
the details contained in this manual and general good practice. 

Specific Commissioning and 

Service Requirements

Motors for Smoke Extract Fans

These motors are used to provide a SAFETY FUNCTION for

people in the event of fire in public premises, they are therefore

subject to strict constraints concerning their operating and

maintenance.

Operating Constraints

i.

Check on the nameplate that the selected motor

corresponds to the maximum exposure temperature and

duration.

ii.

AFTER THE MOTOR HAS BEEN SUBJECTED TO ONE

EMERGENCY DUTY OPERATION, IT MUST BE REPLACED.

iii.

With variable speed control. Ensure that the maximum

speed never exceeds the speed of the motor supplied by

the mains and that the delivered power corresponds to the

previous definitions. The motor should be equipped with

PTC thermistors connected to the protection system

during day to day (S1 duty) and switched off during S2

duty (operation during an emergency).

Maintenance Constraints

Regular service visits must be performed on the installation

and EVERY 6 MONTHS, completing the following checks:

i. Checking the insulation resistance

a) If the drain holes are blocked, open them to eliminate

any accumulated condensation.

ii. Condition of motor

a) Ensure there is no dust and grease e.g. motor, housing

fins, motor cover/fan if fitted driven fan.

b) Ensure the motor runs normally when switched on for

a few minutes.

iii. Bearing check

Run the motor during each maintenance visit. When the

motor is cold, a high level of noise is caused by the texture

of the grease. This does not indicate a bearing fault.

a) Permanently greased bearings.

Replace on 2 pole motors after 10,000 hours of operation

and on motors with 4 poles or more after 20,000hours.

b) Re-greaseable bearings

The information on the motor nameplates must be strictly

respected (grease quantity, grease quality and re-greasing

frequency). The bearings must be replaced after 20,000

hours of operation.

Note: Any maintenance, repair or bearing replacement on the

motor must only be undertaken by the motor manufacturer in

accordance with the requirements of the construction products

directive of Ref. 89/106/EEC.

The product warranty applies to the UK mainland and in 
accordance with Clause 14 of our Conditions of Sale. 
Customers purchasing from outside of the UK should contact 
Nuaire International Sales office for further details.

Содержание AXUS AXR

Страница 1: ...ames In addition to making the fans easier to handle during transit the frames also afford protection for the motor section We advise that the wooden frames should remain on the fans until the moment of actual installation and fixing Handling the unit is best carried out wth the unit fixed to the transit frame When lifting use spreader beams through the transit frame ensuring the unit is evenly ba...

Страница 2: ...t Number 671063 Danger This equipment incorporates rotating and moving parts as well as electrical components and conductors It is the responsibility of the installer to ensure that any such items that remain externally accessible once the equipment is installed are adequately guarded This precaution is necessary to avoid the possibility of accidental injury or death Particular attention must be p...

Страница 3: ...den cappings set to the maximum overhang position of 15mm The roof flashing can be run up the sides of the curb to finish just beneath the top Alternatively if adequate clearance is available the flashing could be run over the top of the capping prior to lowering the unit onto the curb When installed the curb must be bolted securely to the roof trimmer angles Soaker sheet Soaker sheets are manufac...

Страница 4: ...tors Fans with motors of 4 0kW and above will have all six ends of the motor windings brought out to the terminal box on all but the EEXD motors These motors should be connected in the DELTA mesh for connection to a DOL starter 4 0kW motors and above are also suitable for connection to a STAR DELTA controller but as smoke fans are required to start with the minimum of delay in an emergency this me...

Страница 5: ... on a three phase unit simply reverse any two of the supply connections in the isolator box Wiring Diagrams S L1 L2 L3 Single Speed 3 phase below 4kW 400V 3 phase 50Hz supply Fan unit L 4 1U 1V 1W L U1 L V1 L W1 L U1 W2 L V1 U2 L W1 V2 L W V U 4 Notes T S L N S L2 N L1 L L N L2 N N L1 L L L3 N N L2 U V W THREE PHASE UNITS For specialist connections not shown always refer to the wiring diagram supp...

Страница 6: ...ordance with the details contained in this manual and general good practice Specific Commissioning and Service Requirements Motors for Smoke Extract Fans These motors are used to provide a SAFETY FUNCTION for people in the event of fire in public premises they are therefore subject to strict constraints concerning their operating and maintenance Operating Constraints i Check on the nameplate that ...

Страница 7: ... general requirements should be noted 5 1 Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations...

Отзывы: