05. 04. 22. Document Number  671590

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

AVT-NC-(R/X)

Installation Manual

5.2.3 AVT9-(R/X)

 

 

Supply Fan Power

Supply Fan E

Neutral

Live 1

Live 2

Live 3

Supply &

Twin Fan

Control

Supply Fan

Alarm.

(Open = Fault.)

A1

Main Supply

Connection

A6

A3

Supply Fan Control

Supply Fan L1

Twin Fan L1

Actuator N

IO Damper N

IO Damper Close

IO Damper Open

Twin Fan Power

W1

Twin Fan Alarm

Twin Fan

Alarm.

(Open = Fault.)

08

09

10

11

IO Damper

Earth Block

W2

Key:

Pre-Wired Connection

Factory Connection

Optional External Connection

Mandatory External Connection

A1 : Rotary Isolating Switch (Supplied by Customer.)

A3 : Close to Open IO Damper (Supplied by Customer.)

W1 : Supply Fan Alarm (Open = Alarm)

W2 : Twin Fan Alarm (Open = Alarm)

Twin Fan E

Supply Fan COM

Supply Fan NC

Supply & Twin Fan 0-10v

Supply & Twin Fan 0v

Twin Fan COM

Twin Fan NC

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

A1

A*

B1

C/D2 C/D1 A5

A4

B5

B4

Supply Fan L2

A2

Supply Fan L3

A3

Twin Fan L2

B2

Twin Fan L3

B3

B6

14 

Wiring - AVT9-(R/X)

6.0 CONTROLS

The No Control (NC) units described in this manual are supplied 
without any controls. It is the installer’s responsibility to select 
and install suitable controller(s) and circuit(s) to produce the 
desired output from the units while remaining within the units safe 
performance envelope.

7.0 MAINTENANCE

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

7.1 Routine Maintenance

Clean all areas of unit and treat any areas of corrosion.

Check all access doors for leakage and if necessary locks should be 
adjusted and any replacement gasket materials should be replaced 
as required. 

7.2 Annually 

Thoroughly inspect the unit and its components for corrosion, 
acting immediately to treat/restore any damaged areas. 

All electrical terminals within the unit should be tightened. 

Check all earth connections. 

Check control dampers blades. 

Check operation of damper actuators and linkages and adjust as 
necessary. 

8.0 WARRANTY

The 2 year warranty starts from the day of delivery and includes parts 
and labour for the first year. The remaining period covers replacement 
parts only.

This warranty is void if the equipment is modified without 
authorisation, is incorrectly applied, misused, disassembled, or not 
installed, commissioned and maintained in accordance with the details 
contained in this manual and general good practice.

The product warranty applies to the UK mainland and in accordance 
with Clause 14 of our Conditions of Sale. Customers purchasing from 
outside of the UK should contact Nuaire International Sales office for 
further details.

Failure to maintain the unit as recommended will invalidate the 
warranty.

9.0 END-OF-LIFE AND RECYCLING

Where possible Nuaire use components which can be largely recycled 
when the product reaches its end-of-life:

Fans, motors, controls, actuators, cabling and other electrical 
components can be segregated into WEEE recycling streams.

Sheet metal parts, aluminium extrusion, heating/cooling coils and 
other metallic items can be segregated and fully recycled.

EPP, plastic ducting, nylon corner pieces, plastic heat exchangers, 
packaging material and other plastic components can be 
segregated into mixed plastic and widely recycled.

Cardboard packaging, wood, used filters and other paper 
components can be largely recycled or fully processed in energy 
from waste centres.

Remaining Items can be further segregated and processed in 
accordance with the zero waste hierarchy. Please call After Sales 
Support for further information on items not listed above.

Ensure that Nuaire product is made safe from any electrical / water 
/ refrigerant supplies before dismantling commences. This work 
should only be undertaken by a qualified person in accordance with 
local authority regulations and guidelines, taking into account all 
site based risks.

Содержание AVT-NC-R Series

Страница 1: ...nce by a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Symbols GENERAL WARNING Signifies a gener...

Страница 2: ...e unit case or control pack Correctly position slings to avoid twisting of the unit case and observe the centre of gravity before the final lift is made The weight of the unit is available on the unit...

Страница 3: ...Terminal Dimensions Unit Code Terminal Module Code A B C Weight kg AVT1 R AVT1 R MOD 500 716 393 8 AVT2 R AVT2 R MOD 500 716 393 8 AVT3 R AVT3 R MOD 500 716 393 8 AVT4 R AVT4 R MOD 600 857 502 11 AVT4...

Страница 4: ...i 500 827 401 34 AVT4L MSS Standard 1000 827 401 42 AVT4L MSL Large 1500 827 401 61 AVT5 AVT5 MSM Mini 500 827 781 43 AVT5 MSS Standard 1000 827 781 44 AVT5 MSL Large 1500 827 781 65 AVT6 AVT6 MSM Min...

Страница 5: ...ical Side Section View Of Outlet Silencer Floor Mounted Unit And Inlet Silencer 4 4 Unit Access To gain access to blowers for annual maintenance and connections to control board release tool operated...

Страница 6: ...r N IO Damper Close IO Damper Open Twin Fan Power Twin Fan Air Flow Alarm 08 09 10 11 IO Damper Earth Block Twin Fan E Supply Fan AFS 0v COM Supply Fan AFS Signal Supply Twin Fan 0 10v Supply Twin Fan...

Страница 7: ...ll electrical terminals within the unit should be tightened Check all earth connections Check control dampers blades Check operation of damper actuators and linkages and adjust as necessary 8 0 WARRAN...

Страница 8: ...n motor assemblies due to a failed motor or damaged impeller or damper actuator Remove the access cover Disconnect the incoming wiring from the connection box located on the fan scroll on the particul...

Отзывы: