Nu-Air Ventilation Systems Inc. - HRV Operating &Installation Manual
Revised April 27, 2012
Page 6 of 17
5
ANNUAL SERVICING
Your HRV/ERV should undergo annual general servicing by an accredited contractor. This
servicing should include the following:
The eight maintenance items above (3.1 - 3.8).
1.
A general check for proper operation. Controls and electrical connections should be
inspected.
2.
Verification that intake and exhaust airflows are properly balanced.
3.
Re-balancing as necessary.
6
INSTALLATION INSTRUCTIONS
6.1
Installer’s Responsibilities
Installers are responsible for the performance of the ventilation system and for ensuring that all
codes and standards are met.
Do not locate the fresh air supply near a source of contaminated air such as automotive
exhaust, gas or propane exhaust or oil tanks.
Combustion appliances such as furnaces and hot water heaters must not draw combustion
air directly from an H/ERV.
6.2
Installation Basics
Before installing a Nu-Air Commercial H/ERV for the first time, please read these instructions.
Standard Issue Items
The H/ERV comes equipped with:
Filters
Core
Drain kit
Controls (if ordered)