Part 1 - General Safety Information 

Part 6 - Installing the Condensate Drain

This  condensing  high  efficiency  boiler  has  a  condensate  removal 

system. Condensate is water vapor derived from combustion 

products, similar to that produced by an automobile when it is initially 

started. It is very important that the condensate line is sloped down 

away from the boiler and to a suitable drain. 

The condensate line must remain unobstructed. If allowed to freeze in 

the line or obstructed in any other manner, condensate can exit from 

the boiler tee, resulting in potential water damage to property.

When installing a condensate pump, select one approved for use with 

condensing boilers and furnaces. The condensate pump should have 

an overflow switch to prevent property damage from spillage.

Condensate from the boiler will be slightly acidic (pH from 2 to 4.5). 

Check with your local gas company to determine if combustion 

condensate disposal is permitted in your area. Install a neutralizing 

filter if required by local codes.

  

CAUTION

NOTES:

1. Due to its efficient design, the boiler produces condensate (water) 

as a normal by-product. This condensate is acidic, with a pH level 

between 2 and 4.5. This condensate must be drained away from the 

boiler and disposed in accordance with all local regulations.

2. The condensate line should be as short as possible and must be 

pitched at least ¼” per foot to properly drain. If this cannot be done, 

increase the condensate line to a minimum of 1” ID and place a tee in 

the line to properly reduce vacuum lock in the drain line. Tees should 

be placed after the condensate neutralizer (if used).

3. Use corrosion-resistant materials to drain condensate. Use the 

included flexible plastic hose and flexible tube, PVC, or CPVC pipe. PVC 

or CPVC pipe must comply with ASTM D1785, F441, or D2665. Cement 

must comply with ASTM D2564 for PVC pipe or F493 for CPVC pipe. For 

Canadian applications, use CSA or ULC certified flexible tube, PVC or 

CPVC pipe, fittings, and cement.

4. If using flexible tube, place an overflow tee in the tube line to prevent 

condensate backing up into the boiler if the tube should kink. Ensure 

the overflow tee is positioned near a drain or in a location that will not 

damage the surrounding area.

5. Do not reduce the size of the condensate line. The line must at 

minimum equal the diameter of the line included with the appliance.

6. A frozen condensate line could result in a blocked vent condition.  

It is very important to protect the condensate line from freezing 

temperatures or any type of blockage. In installations that may 

encounter sustained freezing conditions, the use of heat tape is 

recommended to avoid freezing of the condensate line. Longer 

condensate runs are more prone to freezing. 

7. Support of the condensate line may be necessary to avoid blockage 

of the condensate flow.

8. Local building codes may require an in-line neutralizer to be 

installed (not included) to treat the condensate.  See Figure 45. If 

required by local authorities, a condensate filter of lime crystals, 

marble, or phosphate chips will neutralize slightly acidic condensate. 

Follow all the installation instructions included with the neutralizer. 

If a neutralizer is installed, periodic replacement of the limestone 

(or neutralizing agent) will be required. The rate of depletion of the 

limestone varies with usage of the boiler. During the first year of boiler 

operation, check the neutralizer every few months for depletion.

9. Route the drain line to a nearby floor drain, laundry tub, or condensate 

pump. If the boiler condensate outlet is lower than the drain, you must 

use a condensate removal pump.

NOTE:

 If a nearby laundry tub is used as a disposal for waste water from 

the washing machine, draining the condensate into this tub allows the 

soapy water discharge to neutralize the acidic condensate.

10. An error will appear on the boiler display if condensate line is 

blocked. The boiler will not operate with a blocked condensate line. 

It is extremely important to have this condition repaired by a qualified 

service technician.

11. Damages due to frozen or blocked condensate lines or leaks ARE 

NOT covered by warranty.

NOTE: 

To clean out condensate trap, see Maintenance section.

Figure 44 - Condensate Piping Suggestions

REMOVAL TO OUTSIDE SOURCE)

NEUTRALIZER

1" x 3/4" PVC PIPE

OF 1/4" PER FOOT

CONNECTIONS

HORIZONTAL LINES MUST

RECOMMENDED: 

TO OUTSIDE

CONDENSATE PIPING WITH PUMP

RECOMMENDED:

EXAMPLE: LOOSE FITING

PIPING SUPPORTS

RECOMMENDED:

BE INSTALLED WITH A PITCH

554200 LITTLE GIANT

CONDENSATE PUMP

OR DRAIN

CONDENSATE

REDUCER - SWEAT

BREAK AND OVERFLOW 

(SUGGESTED SETUP FOR CONDENSATE

 THROUGHOUT

RECOMMENDED:

CONNECTION FOR VACUUM 

RECOMMENDED:

3/4" PVC PIPE SWEAT

PROVIDED FLEXIBLE
CONDENSATE HOSE

06/24/20

LP-723-B

BOILER

CONDENSATE REMOVAL

TO FLOOR DRAIN)

CONDENSATE PIPING

(SUGGESTED SETUP FOR 

LP-723-A

06/24/20

BOILER

EXISTING DRAIN

RECOMMENDED

CONDENSATE NEUTRALIZER

BE INSTALLED WITH A PITCH

RECOMMENDED

HORIZONTAL LINES RECOMMENDED

HORIZONTAL

PIPING VERTICAL OR

PIPE REDUCER - SWEAT

3/4" PVC PIPE

OF 1/4" PER FOOT

LOOSE FITTING 1" X 3/4" PVC 

PIPE HANGERS RECOMMENDED

BE USED TO SUPPORT

CONNECTION FOR VACUUM

BREAK AND OVERFLOW EXAMPLE:

PROVIDED FLEXIBLE 
CONDENSATE HOSE

Содержание TRX150

Страница 1: ...cause property damage severe personal injury or death California Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer birth defects or other reprodu...

Страница 2: ...trical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fir...

Страница 3: ...ng and other performance criteria when undergoing tests specified in ANSI Z21 13 latest edition Installation should be made in accordance with the regulations of the Authority Having Jurisdiction loca...

Страница 4: ...r systems with total input of 300 000 BTU hr or greater See statement below for an important notice on the use of the override IMPORTANT In accordance with Section 325 f 3 of the Energy Policy and Con...

Страница 5: ...CH Circulators 48 2 Low Voltage Wiring Connections 48 3 Room Thermostat Wiring Connections 49 4 Outdoor Sensor Connections 49 5 Aquastat Default and Tank Sensor Optional Connections non Combi Models...

Страница 6: ...a fully functional and calibrated combustion analyzer Failure to follow these instructions will result in property damage severe personal injury or death WARNING WARNING DANGER NOTE If the boiler is e...

Страница 7: ...rors can cause improper or dangerous operation Failure to do so could result in electrical shock improper boiler or system operation property damage serious personal injury or death Due to the low wat...

Страница 8: ...gaskets and seals in water systems are poisonous if consumed and can cause personal injury or death Consider piping and installation when determining boiler location Damages resulting from incorrect...

Страница 9: ...ions On TRX150 TRX199 Models ONLY If the boiler is to be used only in Heating Mode not connected to an indirect water heater the electrical connection of the 3 way valve motor MUST BE DISCONNECTED whi...

Страница 10: ...ATESTHE USE OF A CALIBRATED CO2 O2 AND CO COMBUSTION ANALYZER WARNING Gas Gas 14a 15a 14f 14e 14h 15g 14b 14c 14d 14g 15b 15c 15d 15e 15f ACCESSORIES BOX BOITE ACCESSOIRES For Qualified Technician Ins...

Страница 11: ...Mode Allows manual operation of pumps to commission system and check pump operation Internal By Pass Valve Protects the boiler from damage in low flow conditions Internal ECM Pump The internal ECM Pum...

Страница 12: ...his manual Avoid continuously high levels of humidity Never close existing ventilation openings Ensure a minimum 1 clearance around hot water and exhaust vent pipes NOTE To prevent condensing in the f...

Страница 13: ...m clearance must be provided from the appliance front cover to the removable panel or combustible door Minimum Clearances from Combustible Materials Hot water pipes at least 1 from combustible materia...

Страница 14: ...er bracket drilling holes 4 Drill and plug the wall and secure the lower mounting bracket using field provided screws Then adjust the lower mounting bracket on the boiler Ensure the boiler is installe...

Страница 15: ...this manual When installing a combustion air intake from outdoors care must be taken to utilize uncontaminated combustion air To prevent combustion air contamination see Table 7 This boiler requires f...

Страница 16: ...if there is blockage leakage corrosion or other deficiencies that could cause an unsafe condition 3 If practical close all building doors windows and doors between the space in which the boiler remai...

Страница 17: ...Approved Exhaust Vent Materials3 PVC CPVC PP Stainless Steel Shipping Weight lbs 115 125 130 Gas Supply Pressure NG 3 5 to 10 5 WC LP 8 to 13 WC Power Supply 120V 60 Hz less than 12A General Operatin...

Страница 18: ...ral Heating Supply 1 1 4 NPT A Central Heating Supply 1 1 4 NPT B Supply to Indirect Water Heater 3 4 NPT B Domestic Hot Water Outlet 3 4 NPT C Gas Inlet 3 4 NPT C Gas Inlet 3 4 NPT D N A D Domestic H...

Страница 19: ...7 Flame detection electrode 8 Silencer 9 Junction box 10 DHW Heat Exchanger Combi Models Only 11 Condensate trap 12 Gas valve 13 Control panel TRX Components 15 Circulation Pump 16 DHW Flow Sensor Co...

Страница 20: ...Models Only 11 Condensate trap 12 Gas valve 15 Circulation Pump 16 DHW Flow Sensor Combi Models Only 17 Water pressure switch 18 Modulating Fan 19 Boiler inlet temperature sensor 21 Ignition electrode...

Страница 21: ...ansion tanks must be sized according to total system volume This includes all length of pipe all fixtures boilers etc Failure to properly size for system expansion could result in wasted time money po...

Страница 22: ...et 3 4 C Gas Inlet 3 4 D DHW Inlet 3 4 E CH Return 1 1 4 F Condensate discharge A CH Supply 1 1 4 B Supply to Indirect Water Heater 3 4 Cap if not in use C Gas Inlet 3 4 D N A E CH Return 1 1 4 F Cond...

Страница 23: ...irculation Pump To calculate the size of the heating installation refer to the graph below Table 11 Internal Circulation Head Curve Graph Representing the Available Circulation Pump Head 0 5 10 15 20...

Страница 24: ...event possibility of severe burns or property damage should the relief valve discharge Discharge line must be as short as possible and the same size as the valve discharge connection throughout its en...

Страница 25: ...afactoryinstalledWaterPressureSwitch Inthe event water pressure drops below 7 PSI the control will go to a blocking error FILL 108 inhibiting burner operation However a low water cut off may be requir...

Страница 26: ...thermostat is wired to its corresponding zone valve Contacts in the zone valves provide a signal to the boiler to operate when there is a call for heat 10 Unit is equipped with built in primary pump T...

Страница 27: ...the return side of the boiler as illustrated The piping will not support the weight of the circulators Refer to the circulator manufacturer s instructions to properly support the circulator Failure to...

Страница 28: ...the zone valves provide a signal to the boiler to operate when there is a call for heat 10 Unit is equipped with built in primary pump This pump is sized to ensure proper flow rate through the boiler...

Страница 29: ...TANT Minimum flow rates outlined in this manual 2 gpm must be maintained through the heat exchanger to minimize short cycling 8 In a valve based system each heating zone has a zone valve which opens w...

Страница 30: ...p for the heating loop This pump is sized to ensure proper flow rate through the boiler heat exchanger and related piping 8 For direct not primary secondary piping applications it is required to insta...

Страница 31: ...ive 6 Install a minimum of 12 diameters of straight pipe upstream of all circulators 7 VERY IMPORTANT Minimum flow rates outlined in this manual 2 gpm must be maintained through the heat exchanger to...

Страница 32: ...of days to 18 Example 1 Parameter 2 7 5 131 F increasing phase from 77 F to 131 F 6 days stays at 131 F for 6 days decreasing phase from 131 F to 77 F 6 days Example 2 Parameter 2 7 5 140 F increasin...

Страница 33: ...esponsibility to understand the hazards associated with explosive solvents and take the necessary precautions to avoid these risks Improper seating of vent pipe gaskets can cause eventual gasket failu...

Страница 34: ...about the applicability of the proposed venting material Failure to follow these directions will result in substantial property damage severe personal injury or death DANGER DANGER B Approved Materia...

Страница 35: ...ppliance Direct Vent 1 foot 3 feet 91 cm Power Vent 4 ft below or to side of opening 1 ft above opening K Clearance to mechanical air supply inlet 3 feet above if within 10 feet horizontally 6 feet 1...

Страница 36: ...otal length of the exhaust vent pipe run must not be less than six 6 feet 4 The total length of the exhaust vent pipe run must not exceed one hundred 100 feet in 2 pipe or one hundred fifty 150 feet i...

Страница 37: ...t location or b In the absence of specific ordinances snow levels shall be calculated from the average monthly maximum depth of snow accumulation as indicated by the National Weather Service s 10 year...

Страница 38: ...Polypropylene No Yes Z DENS Concentric Roof 2 3 2ZDVK2 DZDVK3 Not Shown Yes No NOTES 1 Instructions included with termination kits contain detailed assembly and installation instructions 2 Clearance...

Страница 39: ...ngths routing and termination methods must all comply with the methods and limits given in the Venting section of this manual When installing a combustion air intake from outdoors care must be taken t...

Страница 40: ...ing only The installer is responsible for all equipment and detailing required by local codes Sidewall Venting Options Direct Vent Installation Two Pipe Termination Low Profile Termination Concentric...

Страница 41: ...ow Keep Free of Obstructions GasVent Directly Below Keep Free of Obstructions 4 in min Refer to documentation included with termination kit for complete installation instructions Refer to documentatio...

Страница 42: ...ackets Figure 31 Venting Below Grade For installations that exit the wall below grade 1 Excavate the site to a point where the pipes are to exit as shown in Figure 31 2 Ensure the wall is fully sealed...

Страница 43: ...haust must terminate a minimum of 18 above the air intake termination See Figure 37 for more details 3 Polypro Innoflue Concentric Termination illustrated See Figure 40 for more details 3 IPEX Concent...

Страница 44: ...rates two options for exhaust termination only Neither vent pipe illustrated is intended for combustion air intake Refer to documentation included with termination kit for complete installation instru...

Страница 45: ...the system All instructions listed in this Venting section apply See Figures 41 1 and 41 2 for venting demonstrations Chase Venting Through an Existing System When venting as a chase follow all instr...

Страница 46: ...directly from the outdoors into the boiler intake connection Unconfined space is space with volume greater than 50 cubic feet per 1 000 Btu hour 4 8 cubic meters per kW of the total input rating of al...

Страница 47: ...om freezing temperatures or any type of blockage In installations that may encounter sustained freezing conditions the use of heat tape is recommended to avoid freezing of the condensate line Longer c...

Страница 48: ...nection Electrical power must only be turned on when the boiler is completely filled with cold water Failure to follow these instructions could result in component or product failure serious injury or...

Страница 49: ...OTE WHEN CONNECTING THE BOILER TO EXTERNAL CONTROLS DO NOT RUN 120V CABLES AND CABLES FOR CONTROL CIRCUITS WHICH ARE LOWVOLTAGE TOGETHER USE SEPARATE CABLESTO PREVENT INDUCED VOLTAGE ON THE LOW VOLTAG...

Страница 50: ...120V N G L 120 V AC GATEWAY WIFI Bk Bl Bl Rd Wh Bl Bl Rd Rd Br Br Bl Gry Bl Bk Bk Bk Rd Rd Wh Br Br Br Bk Bk Br Wh Br Bl Br Detection electrode EBUS 2 TT2 TT1 System sensor Tank sensor Outdoor sensor...

Страница 51: ...5 Vdc for SAFETY MCU H B RETURN 5 Vdc A NEUTRAL filtered FAN CIRCUIT SMPS Nf HOT filterd Hf Safety Ground NEUTRAL FLAME CIRCUIT Hf Hf 3 WAY VALVE RELAYS CIRCUIT SENSORS CIRCUIT HMI B Nf Nf C D Nf A G...

Страница 52: ...AS VALVE 5 120 VRAC NO 6 120 VRAC NO CN8 POWER SUPPLY OUT 1 120 VAC LINE HT 120V AC 2 120 VAC NEUTRAL CN4 PROTECTIVE EARTH 1 CN7 PROTECTIVE EARTH 1 CN9 PROTECTIVE EARTH 1 CN26 NTC HEAT RETURN 1 5V SEL...

Страница 53: ...SIGNAL EBUS2 11 EBUS2 SIGNAL SELV 24V 12 GROUND CN16 FAN MANAGEMENT 1 GROUND SELV 24V 2 PWM FAN DRIVER 3 HALL_EFFECT SENSOR 4 24V CN19 EXTERNAL CLIP IN 1 24V SELV 24V 5V 2 GROUND 3 CLIP IN SERIAL TX...

Страница 54: ...ding to the COMBINED total maximum BTUH draw for the appliances as if they were operating at the same time 3 Measure the length of the gas supply line from the gas meter to the boiler The boiler must...

Страница 55: ...Screw Figure 54 Excess Flow Valve EFV Figure 55 Remove Yellow Cap When performing a pressure test on the gas line pipng be sure the boiler is disconnected or isolated if the test pressure is expected...

Страница 56: ...of a lockout error After pressing the Reset button to clear an error condition the button will flash for five 5 seconds Display Icon Description Digits Indicating Boiler Status Temperature oF with ba...

Страница 57: ...the central heating CH temperature setpoint fromthehomescreenbypressingtheCH buttons SeeFigure59 The allowable operating range is limited by the Max and Min Temperature Settings e g Parameters 4 2 5 a...

Страница 58: ...Menu Figure 61 Access user menu Press button for setting hours Press button for setting the minutes Press OK to confirm the entered data Activate change by pressing the OK button buttons scroll throu...

Страница 59: ...to the Wifi application the Internet time is automatically taken into account Manual entry Day 1 31 Months 1 12 Year 2019 Time 00 00 item 2 Figure 57 for the hour setting item 8 Figure 57 for setting...

Страница 60: ...tlet Temperature Automatic Temperature Control AUTO OFF 1 Basic Temp Control without Optional Room Sensor or Outdoor Sensor 2 Indoor Temp Reset With Optional Room Sensor 3 Outdoor Temp Reset With Incl...

Страница 61: ...t The boiler target temperature automatically adjusts between the Min and Max Temperature Settings 4 2 6 and 4 2 5 based on the input temperature provided by the included Outdoor Sensor or Internet We...

Страница 62: ...ing system The function boosts the boiler target temperature by increasing the Slope 10 every 10 minutes a call for heat is continuously active to a maximum of 2X the nominal Slope setting 4 2 2 While...

Страница 63: ...r When this function is activated the boiler automatically switches from winter mode to summer mode based on outdoor temperature conditions This means that the appliance can independently activate or...

Страница 64: ...TECHNICIANS MAY ONLY BE ACCESSED AFTER ENTERING THE ACCESS CODE To access the Menus open the cover and proceed as follows in this example Parameter 2 3 1 1 Simultaneously press the OK and ESC buttons...

Страница 65: ...parameters 8 Service Parameters 0 Boiler Statistics 1 1 Boiler Statistics 2 2 Boiler 3 Boiler Temperature 4 Storage 5 Service 6 Error History 7 Free parameters 8 Reset Factory Settings 9 Other 1 10 Ot...

Страница 66: ...ERS 2 0 GENERAL 2 0 0 DHW Setpoint Temperature TRX COMBI 97 140 F 125 Also settable via the home screen see item 2 Figure 57 not applicable when 2 2 8 2 DHW Setpoint Temperature TRX non COMBI 104 149...

Страница 67: ...2 Boiler TRX Non Combi models set to 2 Always On This is not changeable TRX Combi models set to 0 Deactivated COMFORT function is not active TRX Combi models set to 1 or 2 On activates conditionally o...

Страница 68: ...TORY SETTINGS 2 8 0 Automatically resets all parameters to the factory defaults WARNING Always check PCB settings if restoring factory default settings on a replacement controller Replacement controll...

Страница 69: ...6 F 68 4 1 2 S W delay time 0 300 minutes 60 4 2 ZONE 1 SETTINGS 4 2 0 Temperature Range 0 68 122 F low temperature 1 86 179 F high temperature 1 4 2 1 Type of Temperature Control 0 Fixed Outlet Tempe...

Страница 70: ...icable when using an optional NTI Room Sensor and when 4 2 1 2 or 4 4 2 5 MAXIMUM Temperature Setting 86 179 F 179 if Parameter 4 2 0 1 68 122 F 120 if Parameter 4 2 0 0 4 2 5 sets the allowable boile...

Страница 71: ...UM temperature setting 86 179 F 120 if parameter 5 2 0 1 68 122 F 80 if parameter 5 2 0 0 5 2 6 sets the allowable boiler operating temperature range for Zone 2 heating limiting Automatic Temperature...

Страница 72: ...ure Control and manual adjustments from the User Menu 6 3 DIAGNOSTICS 6 3 0 S W function activation 0 OFF 1 ON 0 Only applicable when using an NTI room sensor 6 3 1 S W temperature threshold 50 86 F 6...

Страница 73: ...1 Enable Maintenance advice 0 OFF 1 ON 0 8 5 2 Maintenance Warning Reset Reset OK Yes Esc No Resets Maintenance Advice and clears the Warning 8 5 4 SW Version Display Interface 8 5 5 SW Version Main C...

Страница 74: ...r meter to monitor water makeup Freeze protection fluid may leak before the water begins to leak causing concentration to drop reducing the freeze protection level 4 Glycol in hydronic applications sh...

Страница 75: ...egisters on the pressure gauge F Check Thermostat Circuit s 1 Disconnect the two external wires connected to the boiler thermostat terminals TT1 TT2 low voltage terminal strip 2 Connect a voltmeter ac...

Страница 76: ...un is used it may be necessary to create a vent in the horizontal run to prevent a vacuum lock in the condensate line 4 Do not expose the condensate to freezing temperatures 5 It is very important you...

Страница 77: ...ting the igniter After the boiler displays Error 501 set the room thermostat to the normal setting to start the boiler 8 Open the gas valve and check the connection seals including the boiler connecti...

Страница 78: ...are it with the values given in the table below Natural Gas LP Gas Fan Speed Low High Low High CO PPM 175 175 CO2 8 5 9 7 9 5 10 7 The CO2 at minimum gas flow rate Low Fan Speed must be set lower than...

Страница 79: ...ng counter clockwise to reduce the CO2 level clockwise to increase the CO2 level Wait 1 minute after each adjustment for the CO2 value to stabilize WARNING Minimum Gas Flow Adjustment is very sensitiv...

Страница 80: ...shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction If the information i...

Страница 81: ...iping properly supported Has vent piping been checked for leaks Has the exhaust vent line been pitched back to the boiler at a rate of 1 4 per foot Have the exhaust vent and intake pipes been properly...

Страница 82: ...en started If necessary has the boiler gas valve been adjusted Has the installation been customized per installation location requirements Have all customized system parameters been tested Has proper...

Страница 83: ...to operation after the error condition goes away The button must be pressed on the control panel to restore boiler operation Iftheerrorconditionoccursoftencontactaqualifiedservicetechnician 3 Malfunct...

Страница 84: ...again 1 Check the water pressure on the pressure gauge 2 Purge the air from the central heating circuit 3 Check for the correct functioning and positioning of the supply and return temperature probes...

Страница 85: ...main PCB 3 04 Too many 5 resets in 15 minutes Switch the boiler OFF and ON at the main electrical power supply Blocking Auto Reset 1 1 Turn Off the Power to the Boiler 3 05 PCB internal error Switch...

Страница 86: ...essure is between 3 5 and 10 5 WC Natural Gas or between 8 and 13 WC for boilers converted to Propane LP operation 2 Check gas valve wire Ensure connection is secure 3 Check flame detection sensor Ens...

Страница 87: ...r short circuit This Error Code will go away when the condition is remedied 1 Check exhaust temperature sensor Ensure connections are dry and secure 2 If flue is very cold 14 F 10 C remove sensor and...

Страница 88: ...avoiding any possibility of scalding from hot water 2 Shut power off to the boiler To avoid scalding wait for boiler to cool before operating the relief valve 3 Lift the relief valve lever If water fl...

Страница 89: ...he main water inlet valve 2 Open all the hot and cold water taps 3 Drain the water from the lowest points of the system Before Starting Maintenance 1 Ensure the power and gas remain off 2 Close the va...

Страница 90: ...ers can be converted to cristobalite in very high temperature applications The International Agency for Research on Cancer IARC has concluded Crystalline silica inhaled in the form of quartz or cristo...

Страница 91: ...clean any of the boiler components The components could be damaged resulting in unreliable or unsafe boiler operation substantial property damage severe personal injury or death Figure 85 Remove the...

Страница 92: ...densate can exit from the tee resulting in potential water damage to property D Replacing Components At any point in time over the boiler s service life it may be necessary to replace boiler component...

Страница 93: ...onents 5 Reinstall the fan and combustion assembly components as described in Cleaning the Heat Exchanger Combustion Chamber Ensure the gasket 6 is assembled between the fan and air inlet channel Fail...

Страница 94: ...CH circuit is filled and purged with a pressure of 12 psi Ensure the DHW circuit is filled and purged 1 Power the boiler on 2 If necessary purge air again from the CH and DHW circuits 3 Check the boil...

Страница 95: ...e personal injury or death Such product failures ARE NOT covered under warranty The combustion chamber insulation in this product contains ceramic fiber material Ceramic fibers can be converted to cri...

Страница 96: ...de Clean Set gap at 1 8 CONDENSATE Condensate Trap Clean debris from the condensate trap Fill with clean water Neutralizer Check condensate neutralizer Replace if necessary Condensate hose Disconnect...

Страница 97: ...d correct the problem If a technician is not available press a button on the display to wake it Then press the RESET button to remove the lockout state so additional trials for ignition can be perform...

Страница 98: ...98 Maintenance Notes...

Страница 99: ...ion Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Please only sign after the...

Страница 100: ...NTI Boilers Inc 30 Stonegate Drive Saint John NB E2H 0A4 Canada Technical Assistance 1 800 688 2575 Website www ntiboilers com Fax 1 506 432 1135 Visit us online 86661 Revision Date 2 25 21...

Отзывы: