It  is  very  important  that  the 

combustion  system  be  set 

within  the  recommended  CO2/

CO  measurements  listed  in 

Table  3. Visually  looking  at  the 

burner  does  not  determine 

combustion  quality.  Failure  to 

measure  combustion  with  a 

calibrated  combustion  analyzer 

and  set  the  throttle  within 

the 

recommended 

CO2/CO 

measurements  could  result 

in  property  damage,  severe 

personal injury, or death.

1. Preparing the measuring equipment

Remove the Combustion Test Port plug, 
as 

illustrated

 (Figure 6)

, and insert a 

calibrated combustion analyzer.

Make sure the analyzer is set to the 

appropriate fuel.

It is required to use a calibrated 

combustion  analyzer  to  verify 

the  combustion  chart  (Table  3). 

Failure  to  do  so  could  result  in 

serious personal injury or death.

Figure 6 

– 

Combustion Test Port

Adjustments  to  the  Gas  valve  may 

technician, while using a calibrated 

combustion  analyzer  capable  of 

measuring 

CO

2

 and CO. Adjustments 

may  only  be  performed  if  the  gas 

line  pressure  is  maintained  above 

minimum  levels  throughout  the 

duration  of  the  test.  See  Table  3. 

Failure to follow these instructions 

may result in serious injury or death.

FAILURE  TO  PERFORM  THE  FLUE 

GAS  ANALYSIS  AND  ADJUSTMENT 

AS  DETAILED  IN  THIS  SECTION 

MAY  RESULT  IN  ERRATIC  AND 

UNRELIABLE  BURNER  OPERATION, 

LEADING TO REDUCED EFFICIENCY, 

INCREASED  FUEL  CONSUMPTION, 

REDUCED 

COMPONENT 

LIFE, 

HEAT  EXCHANGER  COMBUSTION 

DEPOSITS,  AND  GENERAL  UNSAFE 

OPERATION.  FAILURE  TO  FOLLOW 

THESE INSTRUCTIONS MAY RESULT 

IN SERIOUS INJURY OR DEATH.

WARNING

WARNING

WARNING

WARNING

   NOTICE

Pa

rt

 3.  

Checking/Adjusting the 

CO

2

 at Max

 

and Min Power

Содержание TFTN

Страница 1: ...on of carbon monoxide may result causing property damage personal responsible for the proper installation of this kit THE INSTALLATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CONVERTED A...

Страница 2: ...150 and 199 Kit Contents Natural to LP Conversion Instructions nr 1 LP Conversion Label nr 1 LP Mixer w Diaphragm Table 1 nr 1 Gasket for gas pipe nr 2 Model Polidoro code MIXER data plate LP diaphrag...

Страница 3: ...result in dangerous explosion leading to property damage personal injury or death ATTENTION LIQUEFIED PETROLEUM LP PROPANE propane gas is heavier than air therefore it is imperative that your boiler i...

Страница 4: ...e g Remove the three bolts securing the NG mixer to the blower and remove the NG Mixer i Reassemble the gas pipe to the gas valve and mixer ATTENTION Use the new rubber gaskets provided with the kit j...

Страница 5: ...r clockwise 2 turns c Turn the gas supply on and test for gas leaks in all piping d Perform gas line pressure test and combustion calibration in accordance with Parts 2 and 3 NOTICE 199 Model ONLY Fig...

Страница 6: ...setting and continue with the Gas Valve and Burner Setup procedure outlined below Failure to perform the Gas Valve and Burner Setup correctly may result in incorrect operation component failure prope...

Страница 7: ...ilure to do so could result in serious personal injury or death Figure 6 Combustion Test Port Adjustments to the Gas valve may technician while using a calibrated combustion analyzer capable of measur...

Страница 8: ...valve by turning setting screw 4 clockwise to increase the CO2 level counterclockwise to reduce the CO2 level 1 turn adjusts the CO2 level by approximately 0 3 Wait 1 minute after each change in setti...

Страница 9: ...corresponds to the value given in Table 3 Min Power adjustment is complete Otherwise continue with the procedure Attention If Screw 2 has been adjusted it is necessary to repeat the Ajusting the CO2...

Страница 10: ...essure Pression d admission Natural Naturel Propane 10 5 wc 2 6 kPa 3 5 wc 1 kPa 0 wc 0 kPa 0 wc 0 kPa 8 wc 2 kPa 13 wc 3 2 kPa October 22 2018 b Conversion Decal Fill out the required information on...

Страница 11: ...11...

Страница 12: ...NTI Boilers Inc 30 Stonegate Drive Saint John NB E2H 0A4 Canada Technical Assistance 1 800 688 2575 Website www ntiboilers com Fax 1 506 432 1135 Visit us online 86662 Rev 22 7 13...

Отзывы: