It is very important that the
combustion system be set
within the recommended CO2/
CO measurements listed in
Table 3. Visually looking at the
burner does not determine
combustion quality. Failure to
measure combustion with a
calibrated combustion analyzer
and set the throttle within
the
recommended
CO2/CO
measurements could result
in property damage, severe
personal injury, or death.
1. Preparing the measuring equipment
Remove the Combustion Test Port plug,
as
illustrated
(Figure 6)
, and insert a
calibrated combustion analyzer.
Make sure the analyzer is set to the
appropriate fuel.
It is required to use a calibrated
combustion analyzer to verify
the combustion chart (Table 3).
Failure to do so could result in
serious personal injury or death.
Figure 6
–
Combustion Test Port
Adjustments to the Gas valve may
technician, while using a calibrated
combustion analyzer capable of
measuring
CO
2
and CO. Adjustments
may only be performed if the gas
line pressure is maintained above
minimum levels throughout the
duration of the test. See Table 3.
Failure to follow these instructions
may result in serious injury or death.
FAILURE TO PERFORM THE FLUE
GAS ANALYSIS AND ADJUSTMENT
AS DETAILED IN THIS SECTION
MAY RESULT IN ERRATIC AND
UNRELIABLE BURNER OPERATION,
LEADING TO REDUCED EFFICIENCY,
INCREASED FUEL CONSUMPTION,
REDUCED
COMPONENT
LIFE,
HEAT EXCHANGER COMBUSTION
DEPOSITS, AND GENERAL UNSAFE
OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT
IN SERIOUS INJURY OR DEATH.
WARNING
WARNING
WARNING
WARNING
NOTICE
Pa
rt
3.
Checking/Adjusting the
CO
2
at Max
and Min Power