NATURAL GAS TO PROPANE GAS 

CONVERSION INSTRUCTIONS

service agency in accordance with the manufacturer’s 

instructions and all applicable codes and requirements 

of the authority having jurisdiction. If the information 

an  explosion  or  production  of  carbon  monoxide 

may  result  causing  property  damage,  personal 

responsible for the proper installation of this kit. THE 

INSTALLATION IS NOT PROPER AND COMPLETE UNTIL 

THE  OPERATION  OF THE  CONVERTED  APPLIANCE  IS 

CHECKED  AS  SPECIFIED  IN  THE  MANUFACTURER’S 

INSTRUCTIONS  SUPPLIED  WITH  THE  KIT,  WHICH 

NECESSITATES  THE  USE  OF  A  CALIBRATED  CO2/O2 

AND CO COMBUSTION ANALYZER.

WARNING

Applicable Models: 

TFTN

TFTN085, TFTN110, TFTN150, and TFTN199

Содержание TFTN

Страница 1: ...on of carbon monoxide may result causing property damage personal responsible for the proper installation of this kit THE INSTALLATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CONVERTED A...

Страница 2: ...150 and 199 Kit Contents Natural to LP Conversion Instructions nr 1 LP Conversion Label nr 1 LP Mixer w Diaphragm Table 1 nr 1 Gasket for gas pipe nr 2 Model Polidoro code MIXER data plate LP diaphrag...

Страница 3: ...result in dangerous explosion leading to property damage personal injury or death ATTENTION LIQUEFIED PETROLEUM LP PROPANE propane gas is heavier than air therefore it is imperative that your boiler i...

Страница 4: ...e g Remove the three bolts securing the NG mixer to the blower and remove the NG Mixer i Reassemble the gas pipe to the gas valve and mixer ATTENTION Use the new rubber gaskets provided with the kit j...

Страница 5: ...r clockwise 2 turns c Turn the gas supply on and test for gas leaks in all piping d Perform gas line pressure test and combustion calibration in accordance with Parts 2 and 3 NOTICE 199 Model ONLY Fig...

Страница 6: ...setting and continue with the Gas Valve and Burner Setup procedure outlined below Failure to perform the Gas Valve and Burner Setup correctly may result in incorrect operation component failure prope...

Страница 7: ...ilure to do so could result in serious personal injury or death Figure 6 Combustion Test Port Adjustments to the Gas valve may technician while using a calibrated combustion analyzer capable of measur...

Страница 8: ...valve by turning setting screw 4 clockwise to increase the CO2 level counterclockwise to reduce the CO2 level 1 turn adjusts the CO2 level by approximately 0 3 Wait 1 minute after each change in setti...

Страница 9: ...corresponds to the value given in Table 3 Min Power adjustment is complete Otherwise continue with the procedure Attention If Screw 2 has been adjusted it is necessary to repeat the Ajusting the CO2...

Страница 10: ...essure Pression d admission Natural Naturel Propane 10 5 wc 2 6 kPa 3 5 wc 1 kPa 0 wc 0 kPa 0 wc 0 kPa 8 wc 2 kPa 13 wc 3 2 kPa October 22 2018 b Conversion Decal Fill out the required information on...

Страница 11: ...11...

Страница 12: ...NTI Boilers Inc 30 Stonegate Drive Saint John NB E2H 0A4 Canada Technical Assistance 1 800 688 2575 Website www ntiboilers com Fax 1 506 432 1135 Visit us online 86662 Rev 22 7 13...