background image

  

Gas Line Pressure Test 

The  boiler  gas  valve  is  equipped  with  a  line  pressure  test  port;  see  Figure  1-1.  Use  the  following  procedure  to 
measure the gas line pressure to the boiler to ensure if falls within the range given in Table 2-1: 

 

1.

 

Turn the supply of gas to the boiler off. 

2.

 

Using a 3/16 in. hex wrench, remove the plug from the flange located at the inlet of the gas valve, identified as 

Line Pressure Test Port

 in Figure 1-1.  In place of the plug, install a 

1/8 NPT x hose barb adapter

, suitable for 

connecting the tubing of the gas pressure manometer being used to measure gas line pressure. 

3.

 

Slide the gas pressure manometer tubing over the 

hose

 

barb adapter

 installed in step 2; connect the other end of 

the tubing to gas pressure manometer.  Ensure both ends of the tubing make a tight connection. 

4.

 

Open the supply of gas to the boiler and check for gas leaks. 

5.

 

Observe the line pressure under static conditions and compare it to Table 2-1. The pressure will be greatest under 

static conditions. 

6.

 

With all other gas appliances in the application running, operate the burner to the maximum firing rate (see Table 

2-2) and compare the observed line pressure with  Table 2-1. The pressure will be lowest during the maximum 
flow of gas. 

7.

 

Adjust the gas line pressure to ensure the parameters in Table 2-1 are attained under all conditions (see NOTICE 

below). If possible adjust the line pressure to the "Nominal/Desired" value listed in  Table 2-1, while the unit is 
operating at the maximum modulation rate, see Table 2-2. 

8.

 

Continue  observing  the  gas  line  pressure until  the  completion of the  combustion  analyses, in case  adjustments 

need to be made. 

9.

 

Complete pressure testing, turn the gas supply off, and then reinstall the Line Pressure Test Port plug, applying 

appropriate thread sealant to the threads prior to installing. Turn gas on and check for leaks.  

 

The  line  pressure  is  a  function  of  the  gas  supply  and  is  affected  solely  by  field  provided 
parameters such as line size and regulator settings. Under no circumstances can the boiler gas 
valve influence or be used to adjust the gas line pressure. 

 

Failure to properly install the Line Pressure Test Port plug will cause a severe leakage of gas, 
resulting in a fire or explosion causing property damage, serious injury or death.     

 

Table 2-1 Line Pressure and Combustion Parameters

 

Gas 

Line Pressure (inches w.c.) 

CO

2

 (%) 

1

 

CO (ppm) 

Max. 

1

 

Nominal/Desired 

Min. 

Max. 

Min. 

Max. 

Natural 

10.5 

8.3 

9.3 

175 

Propane 

11 

13 

9.6 

10.6 

175 

Notes: 

1

 

Combustion values listed are for burner operation at maximum modulation rate; when tested at minimum modulation 
rate the CO

2

 must be 0.5-1.0% lower than CO

2

 at maximum modulation rate.  

 

 

Table 2-2 Minimum and Maximum Modulation and Input Rates

 

Model 

Min. Modulation Rate (RPM) 

Max. Modulation Rate (RPM) 

Input Rate (MBH) 

Min 

Max 

1

 

FTG 600 

1150 

5600 

80 

600 

FTG 800 

1150 

7450 

80 

800 

FTG 1200 

1050 

8100 

120 

1200 

FTG 1400 

1050 

7800 

140 

1400 

Notes: 

1

 

Canada: Altitudes between 2000-4500 ft, de-rate by 10%. Consult local authorities for de-rating for altitudes above 4500ft. 

2

 

Use 

Diagnostic Test

, accessed from the 

Diagnostic 

menu of the display, to force max. and min. modulation rates; see 

Appendix A – Controller and Touchscreen Display Instructions, Section 5 DIAGNOSTICS PAGE. 

 

 
 
 
 
 

Отзывы: