Combustion Calibration Procedure

 

To calibrate burner combustion, perform the following procedure using a calibrated combustion analyzer capable of 
measuring CO

2

 and CO from a Natural Gas or Propane burning appliance: 

1.

 

Set analyzer

 to the appropriate fuel (Propane). 

2.

 

Gas Line Pressure Test

 – monitor gas line pressure throughout all combustion tests and verify it is maintained 

within tolerance.  See 

Gas Line Pressure Test

 below. 

3.

 

Set Throttle Screw

 – operate burner to the maximum modulation rate (see Table 2-2); set combustion according 

to Table  2-1 using the Throttle Screw; allow time for the analyzer readings to stabilize between adjustments  – 
record CO

2

 value.  See 

Throttle Screw Adjustment

 below. 

4.

 

Set Offset Screw

 – operate burner to the minimum modulation rate (see Table 2-2); using the Offset Screw, set 

the CO

2

 to 0.5-1.0% lower than the value obtained during the maximum modulation rate test (e.g. if CO

2

 at Max 

= 10%, then CO

2

 at Min must = 9.0-9.5%).  See 

Offset Screw Adjustment

 below. 

 

Combustion  Calibration  is  mandatory

  upon  installation  and  during  each  annual  service.  

Failure  to  perform  the  Combustion  Calibration  in  accordance  with  these  instructions  may 
result  in  incorrect  combustion  leading  to  burner  damage  or  excessive  Carbon  Monoxide 
concentrations causing property damage, personal injury or death. 

 

Carbon Monoxide

 - Never leave the unit operating while producing Carbon Monoxide (CO) 

concentrations  in  excess  of  175  ppm.  Failure  to  follow  this  warning  may  result  in  serious 
injury or death.

 

 

 

Throttle Screw Adjustment 

The gas valve Throttle Screw (see Figure 1-1) is used to calibrate the CO

2

 concentration with the burner operating at 

or near the maximum modulation rate (see Table 2-2).  Turning the Throttle Screw in (clockwise) decreases the CO

concentration.  Turning  the  Throttle  Screw  out  (counterclockwise)  increases  the  CO

concentration.

   

Typical 

adjustment required is 0 - 

1

/

8

th

 of a turn in or out from the position established in Section 1.0 above.  

 NOTE: 

 

Calibration  of  the  Throttle  Screw  should  only  be  performed  with  the  burner  operating  at  or  near  the 
maximum modulation rate (see Table 2-2). 

 

Adjustments to the 

Throttle Screw

 may only be made by a qualified gas technician using a 

calibrated combustion analyzer capable of measuring CO

2

 and CO. Adjustments may only be 

performed  if  the  gas  line  pressure  is  maintained  above  minimum  levels  throughout  the 
duration of the test (see Table 2-1).  Failure to follow these instructions may result in serious 
injury or death. 

 

Offset Screw Adjustment 

The gas valve Offset Screw (see Figure 1-1) is used to calibrate the CO

2

 offset at minimum modulation vs. maximum 

modulation.  Turning the Offset Screw in (clockwise) increases the CO

concentration at minimum modulation rate.  

Turning  the  Offset  Screw  out  (counterclockwise)  decreases  the  CO

concentration  at  minimum  modulation  rate.

  

Typical adjustment required is 0 - 

1

/

8

th

 of a turn in or out from the factory setting. 

 NOTE: 

  

Calibration  of  the  Offset  Screw  must  only  be  performed  with  the  burner  operating  at  the  minimum 
modulation rate (see Table 2-2). 

 

Adjustments  to  the 

Offset  Screw

  may  only  be  made  by  a  qualified  gas  technician  using  a 

calibrated combustion analyzer capable of measuring CO

2

 and CO, and only with the burner 

at the minimum modulation rate (see Table 2-2).  Attempting to set the Offset Screw while the 
burner  is  operating  at  a  modulation  rate  other  than  the  minimum  will  result  in  incorrect 
combustion and may lead to burner damage or excessive CO. 

 

 

 

 

 

 

 

 