background image

NTI 

INFRARED MOTION DETECTOR

 

 

5

 

 

OPERATION 

 

Alarm Delay 

 

The E-IMD-LCV2(P) is equipped with three jumper positions to choose from.   Place the provided jumper in one of the following 
positions: 

 

15 MIN

-  After an initial alert is sent from the first motion sensed, there will be a 15 minute delay before the sensor will react to any 

additional motion and send another alert.  The sensor will send an alert every 15 minutes if it continues to sense motion.  All 
motion sensed between the 15 minute intervals will be ignored.  

10 SEC

-  After an initial alert is sent from the first motion sensed, there will be a 10 second delay before the sensor will react to 

any additional motion and send another alert.  The sensor will send an alert every 10 seconds if it continues to sense motion.  All 
motion sensed between the 10 second intervals will be ignored. 

Nor

-  There will be no delay.  When the sensor senses movement, an alert will be immediately sent.  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test 

 

When performing a product test, make sure the delay jumper is on the "Nor" pins for an immediate alert to be sent. 

 

With the E-IMD-LCV2(P) connected to the ENVIROMUX  (and power supply connected as applicable), the detector should be 
ready to sense.  Walking within the sensed range of the detector should provide an alert message to any user configured to 
receive it.  When sensed, the Red LED on the detector should illuminate for at least 2 seconds.  

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание ENVIROMUX E-IMD-LCV2

Страница 1: ...MAN238 Rev Date 9 9 2022 E IMD LCV2 P Low Cost Infrared Motion Sensor Installation and Operation Manual ENVIROMUX Series...

Страница 2: ...part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying recording or otherwise without the prior written c...

Страница 3: ...TABLE OF CONTENTS Introduction 1 Materials 1 Features 2 Installation 3 Operation 5 Alarm Delay 5 Test 5 Technical Specifications 6 Warranty Information 7...

Страница 4: ...ligent logic control prevents false alarms Wall mount or hang in a corner Good RFI protection Screw terminal To connect to the digital inputs use a 22 AWG 2 wire cable Connect the other end to the sen...

Страница 5: ...d Motion Sensor 2 Switch Tamper switch NC 3 Jumper blocks For placement of delay jumper 4 LED Illuminates Red to indicate when motion is sensed 5 Wire Terminal Block For connection of ENVIROMUX and po...

Страница 6: ...ld be static stable Away from a window no direct sunlight Away from a heat or cold source temperature should not be changing significantly 2 Mount E IMD LCV2 P using installation bracket provided 3 Re...

Страница 7: ...NTI INFRARED MOTION DETECTOR 4...

Страница 8: ...ll be a 10 second delay before the sensor will react to any additional motion and send another alert The sensor will send an alert every 10 seconds if it continues to sense motion All motion sensed be...

Страница 9: ...12VDC Operating temperature 10 to 50 C Operating humidity 0 95 RH non condensing Mounting mode wall mounted Mounting height 2 2m Detecting distance 12m Detecting angle 110 degree Alarm output NO NC op...

Страница 10: ...wo 2 years from the date of purchase Please contact Network Technologies Inc at 800 742 8324 800 RGB TECH or 330 562 7070 or visit our website at http www networktechinc com for information regarding...

Отзывы: