If you use the encoder simulation you can configure it at the external position sensor system
section. As resolution you may configure a multiple of 0.1um, recommended values are
2um
5um 10um, which should be a good selection for most applications.
If the resolution value is too small, the maximal speed in operation may be
reduced! For secure operation, the maximal velocity/resolution should not be
greater than 2MHz. E.g. 4m/s/2um = 2MHz, which means 4m/s is the maximal
save operation speed for 2um sensor simulation resolution.
When the motor wizard is finished all the needed parameters are set accordingly. The system
is now ready for operation. Switch on the motor supply.