Programming the PRESET and ALL OFF buttons:
In order to program panels, a jumper block must be removed from the program jumper pins. This will allow data
to be stored in the eeprom memory. At this point the BUSY LED will start flashing, indicating that you are in
the program select mode.
IMPORTANT: After programming it is important to replace the programming jumper block so memory
will be protected. DO NOT press all three buttons down simultanously while the jumber is removed, this
will erase programming.
To program:
1.
Make sure that the 804CP or 808CP is in the program select mode as discussed. The BUSY LED should
be flashing.
2.
Set the zone levels as desired using the slide controls.
3.
Press the PRESET or ALL OFF button to store the new zone levels.
4.
Replace the programming jumper. Test the button operation.
Network ID number
Network ID number must be set to a uniqe number (IMPORTANT).
Since the Luma-net System is a digital network, all panels and devices attached (except dimmers) must have a
unique network ID number.
If two panels have the same network ID number, the entire network will stop functioning.
Panels need not be in program mode to change network ID number, since a dipwitch is used.
To set Network ID number:
1.
Locate dipswitch on rear of unit as illustrated below.
2.
Set the switches as per the chart on the following page.
Factory Default Setting:
The 804CP and 808CP are programmed at the factory for zone 1-4 (1-8) to be set for dimmer channel 1-4 (1-8)
respectively. PRESET is programmed for dimmers 1-4 (1-8) full on. ALL OFF is programmed for dimmers 1-4
(1-8) off. The fade rate and other parameters are also set to factory defaults. This may be acceptable for initial
testing. If it is necessary to return the panel to it’s factory default settings (except network ID), follow this procedure:
Caution: Special factory programming will be lost.
1.
Remove program jumper block and disconnect plug-in terminal block.
2.
Hold down all pushbuttons while connecting terminal block.
3.
Setting is complete when busy light begins to flash after several seconds.