Copyright Harmsco
®
Inc.
All rights reserved.
1243-HP, MANUAL - HUR FL
Page 6 of 25
HARMSCO
®
Hurricane
®
Swing Bolt Water Filters
SPECIFICATIONS
Specification
Model
HUR 1X170FL
HUR 3X170FL
HUR 5X170FL
HUR 8X170FL
Cartridge Quantity
1
1
3
5
8
Recommended Flow Rate, gal/min
105
315
525
840
Max. Flow Rate, gal/min
150
450
750
1200
Pressure Rating, P.S.I.G. Max. *
150 *
150 *
150 *
150 *
Height, inches
48"
64"
74"
84"
Service Height, inches
77"
98-1/2"
98-1/2"
104-1/2"
Housing Diameter
11"
20"
30"
35-3/8"
Inlet/Outlet
2
2" Flange
3" Flange
4" Flange
6" Flange
Height of Inlet, inches
23-5/8"
35-1/4"
38"
44-1/4"
Height of Outlet, inches
9 3/4
12"
14-1/8"
20-1/2"
Drain (Qty 2, Female)
3/4" NPT
1-1/2" NPT
1-1/2" NPT
1-1/2" NPT
Weight, Dry
150 lbs.
420 lbs.
1,100 lbs.
1,600 lbs.
Weight, Wet
284 lbs.
929 lbs.
2,284 lbs.
3,535 lbs.
Floor Contact Area
.188 ft²
.292 ft²
.776 ft²
1.164 ft²
Floor Load (approx.)
2,3
1,515 lbs/ft²
3,200 lbs/ft²
3,000 lbs/ft²
3,100 lbs/ft²
Floor Space
4
1.6 ft²
4.5 ft²
8.5 ft²
14.0 ft²
Bonding:
Housing shall be bonded in accordance with all applicable codes.
A grounding lug is provided on the leg.
Housing Material:
Stainless Steel Construction.
All wetted metallic components are ASTM A-240
Finish:
Electro-polish
O-ring Material:
EPDM is standard. Buna-N & Viton are available
Temperature Rating:
Up to 140°F, Note: Higher temperatures are possible,
check cartridge specifications and contact a Harmsco
®
sales engineer.
* Models with -HP suffix 200 P.S.I.G. Max.
Notes:
1. Utilizes Genuine Harmsco
®
Hurricane
®
HC/170 cartridges.
- HC/170 cartridge filters are available in many micron ratings and styles.
- Activated carbon and several high temperature cartridges are also available.
- The use of cartridges other than Genuine Harmsco
®
Hurricane
®
HC/170 filter cartridges will void
certifications by NSF International.
2. Piping shall conform to all applicable codes and be independently supported.
3. If floor strength is suspect, use appropriate measures to adequately distribute load.
4. Does not include Cover/Davit swing position for models HUR 3X170FL, HUR 5X170FL & HUR 8X170FL.