
eco PDU PE Series User Manual
81
Administrator Login Failure
If you are unable to perform an Administrator login (because the Username and
Password information has become corrupted, or you have forgotten it, for
example), you can clear the login information with the following procedure:
1. Power off the eco PDU and remove its housing.
2. Short the jumper labeled J1 (PIN5 and PIN6).
3. Power on the eco PDU.
4. After the beep indicates successfully powered on, power off the switch.
5. Remove the jumper cap from J1.
6. Close the housing and start the eco PDU.
After you start, you can use the default Username and Password to log in.
J1
Содержание eco PDU PE series
Страница 21: ...Chapter 1 Introduction 12 PE8121kJ 1 2 3 4 PE8121kJ 1 5 5 5 1 ...
Страница 25: ...Chapter 1 Introduction 16 PE7328 1 2 3 4 1 PE7328 5 5 ...
Страница 27: ...Chapter 1 Introduction 18 PE9330 1 2 6 3 4 1 6 PE9330 5 ...
Страница 34: ...eco PDU PE Series User Manual 25 Installation Diagram 6 2 3 2 4 5 ...