background image

 Chapter 1. Introduction

4

Features

Power Distribution

Š

Space saving 0U rack mount design with rear mounting

Š

Various IEC outlet models

Š

2 digit 7-segment front panel LED shows PDU/Phase / Bank / Outlet ID

Š

3 digit 7-segment front panel LED shows Current / Voltage / Power 
Dissipation, IP address, and readings from up to 4 environment sensors

Š

Safe shutdown support

Š

Separate power for the unit's own power and its power outlets – the user 
interface is still accessible even when an overload condition trips the 
devices' circuit breaker

Š

Dedicated 8/14-outlet bank for critical load devices (PE9 models only: 
PE9216/PE9324 8 outlets; PE9330 14 outlets) – always powered on

Š

Proactive overload protection (POP) (PE8 / PE9 models only) – 
automatically powers off the last outlet that caused the current overload 
(see 

Proactive Overload Protection (POP)

, page 6)

Remote Access

Š

Remote power control via TCP/IP and a built in 10/100 Ethernet port

Š

Network Protocols: TCP/IP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP, 
NTP, DNS, auto sense, Ping

Š

Remote users can monitor outlet status via web pages on their browsers

Š

eco PDU Power Management software – eco Sensors

Š

Supports SNMP Manager V3

Operation

Š

Local and Remote power outlet control (On, Off, Power Cycle) by 
individual outlets (PE8 / PE9 models)

Š

Supports multiple power control methods – Wake on LAN, System after 
AC Back, Kill the Power

Š

Power-on sequencing – set the power on sequence and delay time for each 
outlet to allow equipment to be powered on in the correct order

Š

Easy setup and operation via a browser-based user interface

Š

Multibrowser support (IE, Mozilla, Firefox, Chrome, Safari, Opera, 
Netscape)

Содержание eco PDU PE series

Страница 1: ...eco PDU PE Series PE7216 PE7324 PE8121kJ PE8216 PE8324 PE9216 PE9324 PE7328 PE9330 Power Distribution Unit User Manual www aten com ...

Страница 2: ...ated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own ex...

Страница 3: ...any radio and or TV interference caused by unauthorized modifications to this device It is the responsibility of the user to correct such interference The manufacturer is not responsible for any damage incurred in the operation of this system if the correct operational voltage setting was not selected prior to operation PLEASE VERIFY THAT THE VOLTAGE SETTING IS CORRECT BEFORE USE PE Device Safety ...

Страница 4: ...ping contact your dealer Read this manual thoroughly and follow the installation and operation procedures carefully to prevent any damage to the switch or to any other devices on the eco PDU installation Features may have been added to the eco PDU since this manual was published Please visit our website to download the most up to date version Copyright 2013 ATEN International Co Ltd Manual Date 20...

Страница 5: ...s 4 Power Distribution 4 Remote Access 4 Operation 4 Management 5 Security 5 eco Sensors Energy Management Software 6 Proactive Overload Protection POP 6 Requirements 7 Optional Accessories 8 Environment Sensors 8 Door Sensor 8 Cable Holders 9 Components 10 PE7216 PE8216 PE9216 10 PE8121kJ 12 PE7324 PE8324 PE9324 14 PE7328 16 PE9330 18 Port and LED Panel All models 20 Chapter 2 Hardware Setup Befo...

Страница 6: ...ogin 31 Moving On 31 Chapter 4 Logging In Logging In 32 The eco PDU Main Page 33 Page Components 34 Chapter 5 Energy Energy 35 Connections 35 Configuration 39 Chapter 6 User Management Overview 42 Administrator Information 42 User Information 43 Chapter 7 Log Log 44 The System Log Event List 45 Chapter 8 Setup Device Management 46 Device Configuration 46 Date Time 53 Security 55 Login Failures 55 ...

Страница 7: ...al 67 Rack Mounting 69 The eco PDU s Main Power Cord 69 Securing the Power Cables 69 Technical Support 70 International 70 North America 70 IP Address Determination 71 Specifications 73 Basic Comparison 73 PE7216B PE8216B PE9216B 74 PE7216G PE8216G PE9216G 75 PE8121kJ 76 PE7324B J PE8324B J PE9324B J 77 PE7324G PE8324G PE9324G 78 PE7328B J PE7328G 79 PE9330B J PE9330G 80 Administrator Login Failur...

Страница 8: ...If keys need to be chorded they appear together in the same bracket with a plus sign between them Ctrl Alt 1 Numbered lists represent procedures with sequential steps Bullet lists provide information but do not involve sequential steps Indicates selecting the option on a menu or dialog box for example that comes next For example Start Run means to open the Start menu and then select Run Indicates ...

Страница 9: ...all NRGence products and how they can help you save money in the data center visit NRGence on the Web or contact an ATEN Authorized Reseller Visit ATEN on the Web for a list of locations and telephone numbers International http www aten com North America http www aten usa com ...

Страница 10: ... combined with real time power measurement allowing you to control and monitor the power status of devices attached to the PDUs either at the PDU device bank or outlet level depending on the model from practically any location via a TCP IP connection The power status of each outlet can be set individually allowing users to switch each device On Off The eco PDU also offers comprehensive power analy...

Страница 11: ...ors are optional accessories A sensor enabled installation is required to generate a more complete energy efficient data and chart Higher sensor installation density is helpful to generate more accurate data See Optional Accessories page 8 for further information 2 eco PDUs are primarily designed for access via Intranet extra network security protection is suggested for Internet access usage 3 Not...

Страница 12: ...s 8 16 PE7216G IEC 60320 C20 No PE8216G Yes 16 16 PE9216G Yes 8 16 PE8121kJ NEMA L6 15P 21 21 x IEC 320 C13 with lock PDU 1 x Bank Outlet Yes 21 21 PE7324B J NEMA L6 30P 24 21 x IEC 320 C13 3 x IEC 320 C19 PDU 2 x Bank Outlet No PE8324B J Yes 24 24 PE9324B J Yes 16 24 PE7324G IEC 60309 32A No PE8324G Yes 24 24 PE9324G Yes 16 24 PE7328B J NEMA L6 30P 28 24 x IEC 60320 C13 4 x IEC 60320 C19 PDU 2 x ...

Страница 13: ... models only automatically powers off the last outlet that caused the current overload see Proactive Overload Protection POP page 6 Remote Access Remote power control via TCP IP and a built in 10 100 Ethernet port Network Protocols TCP IP UDP HTTP HTTPS SSL SMTP DHCP NTP DNS auto sense Ping Remote users can monitor outlet status via web pages on their browsers eco PDU Power Management software eco...

Страница 14: ...via blinking LEDs locally SMTP SNMP trap notification Supports Management Information Base MIB files for SNMP Environment monitoring supports external temperature humidity differential pressure sensors for rack environment monitoring Door Sensor support allows the monitoring of rackmount enclosure door access to notify users when a door has been opened Current and voltage threshold setting Naming ...

Страница 15: ... PDUs and is bundled with all PE series packages Proactive Overload Protection POP The PE8121kJ PE8216 PE9216 PE8324 PE9324 and PE9330 models feature NRGence s exclusive Proactive Overload Protection POP technology Effective on all non critical outlets this added safety feature automatically powers off the last outlet that caused the current overload POP mode is engaged when the current exceeds th...

Страница 16: ...booting of attached computers the computer s BIOS must support Wake on LAN or System after AC Back For Safe Shutdown The computer must be running Windows Windows 2000 or higher or Linux The Safe Shutdown program available by download from our website or on the software CD included must be installed and running on the computer ...

Страница 17: ...8xxx PE9xxx range feature a 4 pin dry contact port for door sensors that supports the monitoring of rackmount enclosure door access to notify users when a door has been opened See the table below for information about the two available door sensors Please contact your ATEN dealer for purchasing information Sensor Management Sensors can be managed via the eco PDU s built in graphical user interface...

Страница 18: ...he cables from your attached devices in place on the eco PDU unit Use only the ATEN Lok U Plug cable holders that have been specifically designed to work with the eco PDU Using any other kind of cable securing device could be highly dangerous Part Number Description 2X EA07 Lok U Plug Cable Holder 10 pcs 2X EA08 Lok U Plug Installation Tool 4 pcs ...

Страница 19: ...nts PE7216 PE8216 PE9216 Note The PE7216 PE8216 PE9216 unit components are identical except for the outlet LEDs the PE7216 has none the PE8216 has 16 and the PE9216 has 8 as shown by number 9 above 1 2 5 3 4 1 5 5 PE7216 PE8216 PE9216 ...

Страница 20: ...ensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 16 3 Circuit Breaker Pushbutton As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation 4 Power Inlet The power cord that connects the unit to an AC power source plugs into this socket B models...

Страница 21: ...Chapter 1 Introduction 12 PE8121kJ 1 2 3 4 PE8121kJ 1 5 5 5 1 ...

Страница 22: ...rt Reset Switch Full details of this section are provided on page 16 3 Circuit Breaker Pushbutton As a safety measure if there is an over current situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation 4 Power Inlet The power cord that connects the unit to an AC power NEMA L6 15P source plugs into this socket 5 Outlet Status LEDs These 21 ...

Страница 23: ...4 PE8324 PE9324 Note The PE7324 PE8324 PE9324 unit components are identical except for the outlet LEDs the PE7324 has none the PE8324 has 24 and the PE9324 has 16 as shown by number 5 above 1 2 5 3 4 PE7324 PE8324 PE9324 1 1 5 5 5 5 ...

Страница 24: ...el contains Readout Section and LEDs Sensor Ports LAN Port Door Sensor Port Reset Switch Full details of this section are provided on page 16 3 Circuit Breakers As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation 4 Power Cord Plug the cord into an AC power source B models connect to a NEMA...

Страница 25: ...Chapter 1 Introduction 16 PE7328 1 2 3 4 1 PE7328 5 5 ...

Страница 26: ...witch Full details of this section are provided on page 16 3 Circuit Breaker Pushbutton As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation 4 Power Inlet The power cord that connects the unit to an AC power source plugs into this socket B models connect to a NEMA L6 30P source G models con...

Страница 27: ...Chapter 1 Introduction 18 PE9330 1 2 6 3 4 1 6 PE9330 5 ...

Страница 28: ...vided on page 16 3 Circuit Breaker Pushbutton As a safety measure if there is an overcurrent situation regarding the device s power the circuit breakers will trip Press the button to recover normal operation 4 Power Inlet The power cord that connects the unit to an AC power source plugs into this socket B models connect to a NEMA L6 30P source G models connect to an IEC 60309 32A source 5 Output P...

Страница 29: ...hrough the outlets 01 02 03 01 Outlet1 Outlet2 Outlet3 Outlet1 2 Readout Section When PDU Phase Bank Outlet is selected readouts for Current Voltage Power and IP address appear in the display window Press the button next to the LED display window to cycle the selection between the items the LEDs next to the items indicate which one the display relates to When a sensor is selected the display shows...

Страница 30: ... the end of a paper clip Press and release to reboot the device Press and hold for more that three seconds to reset the eco PDU to its factory default settings 6 LAN Port The cable that connects the unit to the Internet LAN or WAN plugs in here 7 Door Sensor This 4 pin dry contact port is for a door sensor support allows the monitoring of rack mount enclosure door access to notify users when a doo...

Страница 31: ...e mounted either near the top and bottom of the back panel or the top and bottom ends of the device as shown in the diagram below 1 Important safety information regarding the placement of this device is provided on page 67 Please review it before proceeding 2 Make sure that power to all the devices you will be connecting have been turned off You must unplug the power cords of any computers that ha...

Страница 32: ...not be installed with the power sockets facing directly up or down and thus should only be installed with the power sockets facing out from a vertical position as shown below Note The eco PDU models shown in the diagrams are for rack mount reference purposes only Right Wrong Floor Floor ...

Страница 33: ...at connects the eco PDU to the LAN into the eco PDU s LAN port 4 Optional If you are using environmental sensors in your eco PDU installation connect up to four to the RJ 11 sensor ports on the unit s front panel Note Sensors are optional Please see Optional Accessories page 8 and the installation diagrams later in this chapter for further information 5 Optional If you are using a door sensor in y...

Страница 34: ...eco PDU PE Series User Manual 25 Installation Diagram 6 2 3 2 4 5 ...

Страница 35: ...DU unit Secure the cable holders using the specially designed holes around the individual power outlets as shown below Note 1 Cable holders are an optional accessory See Cable Holders page 9 2 Use only the ATEN Lok U Plug cable holders that have been specifically designed to work with the eco PDU Using any other kind of cable securing device could be highly dangerous ...

Страница 36: ...e a tie wrap to secure the sensor tighten the tie wrap over the recessed channel on the sensor as shown in the following diagram Note 1 The sensors shown in the above diagram are for reference purposes only The sensors for the eco PDU may look slightly different 2 Depending on the model and type of sensor sensor mounts tie wraps and adhesive cable tie holders may or may not be provided in the pack...

Страница 37: ...orm See First Time Setup page 29 and the following sections in this chapter for full details eco Sensors All eco PDUs support eco Sensors eco PDU Manager Software NRGence eco Sensors provides you with an easy method for managing multiple devices offering an intuitive and user friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment conne...

Страница 38: ...owser Note 1 Since this is the first time you are logging in use the default Username administrator and the default Password password For security purposes we recommend changing them to something unique see Changing the Administrator Login page 31 2 For remote methods of getting logged in to the network see IP Address Determination page 71 After you successfully log in the eco PDU Energy Connectio...

Страница 39: ...k Configuration To set up the network do the following 1 Click the Setup tab 2 This opens on the Device Configuration page A screen similar to the one below appears 3 Fill in the fields according to the information provided under Device Configuration page 46 ...

Страница 40: ...nformation section at the top reset the name and password fields to something unique then click Save at the bottom of the page Note If you forget the Administrator s name or password short the mainboard jumper to restore the default Administrator account See see Administrator Login Failure page 81 in the Appendix for full details Moving On After setting up the network and changing the default Admi...

Страница 41: ... access in the browser s URL location bar Note You can get the IP address from the eco PDU administrator or see IP Address Determination page 71 for information about setting it up yourself 2 If a Security Alert dialog box appears accept the certificate it can be trusted The Login page appears 3 Provide a valid Username and Password set by the eco PDU administrator 4 Select your preferred Language...

Страница 42: ...e After you have successfully logged in the eco PDU Main Page comes up with the Energy Connections page displayed Note The screen depicts an Administrator s page Depending on a user s type and permissions and your PE model not all of these elements appear ...

Страница 43: ...e menu bar contains operational sub categories that pertain to the item selected in the tab bar The items that appear in the menu bar are determined by the user s type and the authorization options that were selected when the user s account was created 3 Sidebar The Sidebar provides a tree view listing of outlets that relate to the various tab bar and menu bar selections 4 Help Connects to on line...

Страница 44: ...face opens with its default selection of the Energy tab and the Connections menu The contents of the PDU Status Bank Status and Outlet Status sections are displayed in the main panel Note Only enabled eco PDU models will display the Bank Status and or Outlet Status submenu section ...

Страница 45: ...ency is displayed here in Hz On Off Reboot You can manually turn the device On and Off from this page by clicking the radio buttons To Reboot the device enable the Reboot checkbox and click on Save located at the bottom of the page Door Sensor This section allows you to select the type of door sensor that is being used in the installation See Door Sensor page 8 for further information Sensor 1 4 I...

Страница 46: ...er management configuration for the individual banks Threshold Settings These fields are used to set the maximum minimum and fluctuation threshold settings for Aggregate Current Voltage Power and Power Dissipation If a range falls below the minimum setting or exceeds the maximum setting an alarm is triggered Breaker status ON OFF displays here ...

Страница 47: ...d to set the maximum minimum and fluctuation threshold settings for Aggregate Current Voltage Power and Power Dissipation If a range falls below the minimum setting or exceeds the maximum setting an alarm is triggered On Off Reboot You can manually turn the outlet On and Off from this page by clicking the radio buttons To Reboot the outlet enable the Reboot checkbox and click on Save located at th...

Страница 48: ...tlets this added safety feature automatically powers off the last outlet that caused the current overload Enable POP Mode by clicking the radio button Make your selection for the POP Threshold options are Same as Bank Maximum Current or User Defined Enter a value in the field Note This feature is available on the PE8121kJ PE8216 PE9216 PE9324 and PE9330 models only See Proactive Overload Protectio...

Страница 49: ...lect one of the choices below Wake on LAN This is a Safe Shutdown and Restart option If this is selected when an Outlet is turned Off the eco PDU first sends a message to the computer telling it to prepare for a shutdown it then waits for the amount time set in the Power Off Delay field to give the OS time to close down before the computer is powered down to standby mode Likewise when the Outlet i...

Страница 50: ...ion is selected the eco PFDU waits for the amount time set in the Power Off Delay field and then turns the Outlet s power Off Turning the power off performs a cold non safe shutdown MAC Address In order to use either of the Safe Shutdown and Restart methods the MAC address of the computer connected to the outlet must be filled in here Heading Meaning ...

Страница 51: ...strator account It can be used to set up the device and to begin creating users and groups The Username for this account is administrator the password is password For security purposes we strongly recommend changing these to something unique Administrator Information This section is used to set the Administrator name and password Only Administrators can view this section For details see Changing t...

Страница 52: ... options are explained in more detail in the following table Field Description Management The Management field allows you to Enable or Disable a user s account Enable stores the user account Disable disables the user account Name From 1 to 16 characters are allowed Password From 1 to 16 characters are allowed Outlet This field allows you to set the outlet by outlet permissions of the user Click on...

Страница 53: ...44 Chapter 7 Log Log The eco PDU keeps a record of transactions that take place on its installation and stores up to 128 events at one time ...

Страница 54: ...f your choice The top right of the main panel shows the total number of pages in the log file and what page you are currently viewing The buttons on the bottom row function as follows Clear click to erase the contents of the log event list First Page click to go to the first page of the log event list Previous Page click to move to the previous page of the log event list Next Page click to move to...

Страница 55: ...DU Name This field lets you give the device a unique name Simply delete whatever is in the text box and key in the name of your choice Click Save located at the bottom of the page to save the new name MAC Address This item displays the eco PDU s MAC address Firmware Version This item displays the current firmware version number You can reference it to see if there are newer versions available on t...

Страница 56: ...l not be found Select whether to allow only secure browser logins as show below An explanation of the fields is given in the table below Note 1 Valid entries for all of the Service Ports are from 1 65535 2 The service ports cannot have the same value You must set a different value for each one 3 If there is no firewall on an Intranet for example it doesn t matter what these numbers are set to sinc...

Страница 57: ... Server address automatically radio button To specify the DNS Server address manually select the Set DNS server address manually radio button and fill in the addresses for the Preferred and Alternate DNS servers with values appropriate for your network Note 1 If you choose Obtain IP address automatically when the device starts up it waits to get its IP address from the DHCP server If it hasn t obt...

Страница 58: ...e Obtain DNS Server address automatically radio button To specify the DNS Server address manually select the Set DNS server address manually radio button and fill in the addresses for the Preferred and Alternate DNS servers with values appropriate for your network Note 1 If you choose Obtain IP address automatically when the device starts up it waits to get its IP address from the DHCP server If i...

Страница 59: ... IP address of your SMTP server 2 If your server requires authentication put a check in the My server requires authentication checkbox 3 Key in the appropriate account information in the Account Name Password and From fields Note Only one email address is allowed in the From fields and it cannot exceed 64 characters 4 Key in the email address addresses of where you want the event reports sent to i...

Страница 60: ...to use 3 Key in the IP address es and the service port number s of the computer s to be notified of SNMP trap events The valid port range is 1 65535 The default port number is 162 Note Make sure that the port number you specify here matches the port number used by the SNMP receiver computer 4 Key in the community value s if required for the SNMP version 5 Key in the auth privacy password s that co...

Страница 61: ...nts that take place on eco PDU devices and write them to the eco PDU Syslog server do the following 1 Check Enable Syslog Server 2 Key in the IP address and the port number of the Syslog server The valid port range is 1 65535 The default port number is 514 ...

Страница 62: ...meters according to the information described below Time Zone To establish the time zone that the eco PDU is located in drop down the Time Zone list and choose the city that most closely corresponds to where it is at If your country or region employs Daylight Saving Time Summer Time check the corresponding checkbox ...

Страница 63: ... time settings from the locally connected PC Network Time To have the time automatically synchronized to a network time server do the following 1 Check the Enable auto adjustment checkbox 2 Drop down the time server list to select your preferred time server or Check the Preferred custom server IP checkbox and key in the IP address of the time server of your choice 3 If you want to configure an alt...

Страница 64: ...cutive failed login attempts that are permitted from a remote user Timeout sets the amount of time a remote user must wait before attempting to login again after exceeding the number of allowed failures Working Mode If ICMP is enabled the eco PDU device can be pinged If it is not enabled the device cannot be pinged The default is Enabled ...

Страница 65: ...Password Length Sets the minimum number of characters required for a password Acceptable values are from 1 16 Password Must Contain At Least Checking any of these items requires users to include at least one of the specified items in their password Note This policy does not affect existing user accounts Only new user accounts created after this policy has been enabled and users required to change ...

Страница 66: ...168 0 126 abcdefg The following characters are allowed 0 9 a z A Z _ The following characters are not allowed Space Compound characters É Ç ñ etc Note 1 There must be a forward slash between the IP address and the string 2 If no login string is specified here anyone will be able to access the eco PDU device login page using the IP address alone This makes your installation less secure For security...

Страница 67: ... mark in the IP Filter Enable and or MAC Filter Enable checkbox If the include button is checked all the addresses within the filter range are allowed access all other addresses are denied access If the exclude button is checked all the addresses within the filter range are denied access all other addresses are allowed access Adding Filters To add an IP filter do the following 1 Click Add A dialog...

Страница 68: ...resses you want to filter IP Filter MAC Filter Conflict If there is a conflict between an IP filter and a MAC filter for example where a computer s IP address is allowed by the IP filter but its MAC address is excluded by the MAC filter then that computer s access is blocked In other words if either filter blocks a computer then the computer is blocked no matter what the other filter is set to Mod...

Страница 69: ...Chapter 8 Setup 60 Authentication Authorization The Authentication Authorization page is used to set up login authentication and authorization management from external sources ...

Страница 70: ... the time in seconds that the eco PDU device waits for a RADIUS server reply before it times out 4 In the Retries field set the number of allowed retries for attempting to connect to the RADIUS server 5 In the Shared Secret field key in the character string that you want to use for authentication between the eco PDU device and the RADIUS Server 6 On the RADIUS server set the entry for each user as...

Страница 71: ...eatest security we recommend using a third party certificate authority CA signed certificate To obtain a third party signed certificate go to a CA Certificate Authority website to apply for an SSL certificate After the CA sends you the certificate and private encryption key save them to a convenient location on your computer Importing the Private Certificate To import the private certificate do th...

Страница 72: ...is used to upgrade the eco PDU s firmware and to backup and restore the device s configuration settings Firmware File When you click the PDU tab the display opens with the Upgrade Main Firmware menu page which looks similar to the one below ...

Страница 73: ... appears to inform you of the situation and stops the upgrade procedure Name Lists all of the eco PDU devices Click to put a check in the checkbox of the device s whose firmware you want to upgrade F W Version Displays the eco PDU s current firmware version Filename As new versions of the firmware become available they are posted on our website and can be downloaded to a convenient location on you...

Страница 74: ...form you of the situation and stops the upgrade procedure If you didn t enable Check Main Firmware Version the upgrade file is installed without checking what its level is Once the upgrade completes successfully the switch resets itself 4 Log in again and check the firmware version to be sure it is the new one Firmware Upgrade Recovery Should the eco PDU s firmware upgrade procedure fail and the d...

Страница 75: ...nvenient location Restore To restore a previous backup do the following 1 Click Browse navigate to the file and select it Note If you renamed the file you can leave the new name There is no need to return it to its original name 2 In the Password field key in the same password that you used to save the file Note If you did not set a password when you created the backup file you can omit this step ...

Страница 76: ...vided Never spill liquid of any kind on the device Unplug the device from the wall outlet before cleaning Do not use liquid or aerosol cleaners Use a damp cloth for cleaning The device should be operated from the type of power source indicated on the marking label If you are not sure of the type of power available consult your dealer or local power company To prevent damage to your installation it...

Страница 77: ...s or short out parts resulting in a risk of fire or electrical shock Do not attempt to service the device yourself Refer all servicing to qualified service personnel If the following conditions occur unplug the device from the wall outlet and bring it to qualified service personnel for repair The power cord or plug has become damaged or frayed Liquid has been spilled into the device The device has...

Страница 78: ... total rack load should not exceed 80 percent of the branch circuit rating Make sure that all equipment used on the rack including power strips and other electrical connectors is properly grounded Ensure that proper airflow is provided to devices in the rack Ensure that the operating ambient temperature of the rack environment does not exceed the maximum ambient temperature specified for the equip...

Страница 79: ...hand Product model number serial number and date of purchase Your computer configuration including operating system revision level expansion cards and software Any error messages displayed at the time the error occurred The sequence of operations that led up to the error Any other information you feel may be of help Email Support support aten usa com Online Technical Support Troubleshooting Docume...

Страница 80: ... network address See Device Management page 49 Method 1 For computers running Windows an IP address can be determined and or assigned with the IP Installer utility The utility can be obtained from the Download area of our web site or from the software CD Look under Driver SW and the model of your device After downloading the utility to your computer do the following 1 Unzip the contents of IPInsta...

Страница 81: ...od 2 1 Set your computer s IP address to 192 168 0 XXX Where XXX represents any number or numbers except 60 192 168 0 60 is the default address of the eco PDU 2 Specify the device s default IP address 192 168 0 60 in your browser and you will be able to connect 3 Assign a fixed IP address for the device see IPv4 Configuration page 51 that is suitable for the network segment that it resides on 4 Af...

Страница 82: ...s Metering Level Outlet Switching PE7216B NEMA 6 20P 16 14 x IEC 320 C13 2 x IEC 320 C19 PDU 1 x Bank Outlet No PE8216B Yes 16 16 PE9216B Yes 8 16 PE7216G IEC 60320 C20 No PE8216G Yes 16 16 PE9216G Yes 8 16 PE8121kJ NEMA L6 15P 21 21 x IEC 320 C13 with lock PDU 1 x Bank Outlet Yes 21 21 PE7324B J NEMA L6 30P 24 21 x IEC 320 C13 3 x IEC 320 C19 PDU 2 x Bank Outlet No PE8324B J Yes 24 24 PE9324B J Y...

Страница 83: ... P D Sensor1 Sensor4 FW Upgrade 3 digit 7 segment Orange Current Volt P D IP Sensor1 Sensor4 7 Green Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 1 x 16A Branch Breaker Nominal Input Power 100 240V 50 60Hz 16A UL 20A Max Power Capacity 4 16kW Nominal Output Power Per Port IEC 320 C1...

Страница 84: ...t 3 Green Current Volt P D Sensor1 Sensor4 FW Upgrade 3 digit 7 segment Orange Current Volt P D IP Sensor1 Sensor4 7 Green Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 1 x Non fuse Breaker Nominal Input Power 100 240V 50 60Hz 16A Power Capacity 4 60kW Nominal Output Power Per Port I...

Страница 85: ...grade 3 digit 7 segment Orange Current Volt P D IP Sensor1 Sensor4 7 Green Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 1 x 16A Pushbutton Breaker Nominal Input Power 100 240V 50 60Hz 15A Max Nominal Input Output Voltage 200 VAC Power Capacity 3kW Nominal Output Power Per Port IEC 3...

Страница 86: ... Current Volt P D Sensor1 Sensor4 FW Upgrade 3 digit 7 segment Orange Current Volt P D IP Sensor1 Sensor4 7 Green Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 2 x Branch Breaker Nominal Input Power 100 240V 50 60Hz 24A UL 30A Max Nominal Input Output Voltage 200 240 VAC Power Capaci...

Страница 87: ...t Volt P D Sensor1 Sensor4 FW Upgrade 3 digit 7 segment Orange Current Volt P D IP Sensor1 Sensor4 7 Green Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 2 x Non fuse Breaker Nominal Input Power 100 240V 50 60Hz 32A Nominal Input Output Voltage 200 240 VAC Power Capacity 7 36kW Nomina...

Страница 88: ...r1 Sensor4 7 Green Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 2 x Branch Breaker Nominal Input Power 100 240V 50 60Hz 24A UL 30A Max 100 240V 50 60Hz 30A TUV 32A Max Nominal Input Output Voltage 100 240 VAC Power Capacity 7 40kW Nominal Output Power Per Port IEC 320 C19 100 240V 5...

Страница 89: ... P D IP Sensor1 Sensor4 7 Green Door Open 1 Red IP 1 Green Power 1 Blue Switches LED Display Select 1 x Pushbutton PDU Bank Outlet Select 2 x Pushbutton Reset 1 x Semi recessed Pushbutton Power 2 x Branch Breaker Nominal Input Power 100 240V 50 60Hz 24A UL 30A Max 100 240V 50 60Hz 30A TUV 32A Max Nominal Input Output Voltage 100 240 VAC Power Capacity 7 40kW Nominal Output Power Per Port IEC 320 C...

Страница 90: ...r example you can clear the login information with the following procedure 1 Power off the eco PDU and remove its housing 2 Short the jumper labeled J1 PIN5 and PIN6 3 Power on the eco PDU 4 After the beep indicates successfully powered on power off the switch 5 Remove the jumper cap from J1 6 Close the housing and start the eco PDU After you start you can use the default Username and Password to ...

Страница 91: ...o improper equipment or attempted repair by anyone other than ATEN This warranty does not cover products sold AS IS or WITH FAULTS IN NO EVENT SHALL ATEN S LIABILITY EXCEED THE PRICE PAID FOR THE PRODUCT FURTHER ATEN SHALL NOT BE RESPONSIBLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE USE OF THE PRODUCT ITS ACCOMPANYING SOFTWARE OR ITS DOCUMENTATION ATEN SHAL...

Отзывы: