NRG Product Manual
LOGR-S Data Logger
NRG_LOGR-S_Manual
Rev. 1.0
[email protected] | Page 35
5 November 2021
Hukseflux SR30 Heater Control
This file can be placed on the FTP
server to control the heater of
the Hukseflux SR30 pyranometer.
As a default, the sensor fan is
always on. The ambient
temperature used for thee SR30
heater control must be a single
ended analog temperature
sensor (such as the NRG 110S or
NRG T60) and
must be wired to
Channel 14
. The SR30 controller
will turn the heater on/off based
on the value of the temperature
sensor and the control
temperature settings in the
command file.
This only values in this file that
should be
edited are the “on
temperature” which is the
temperature (in degrees C)
below which the SR30 heater
should turn on and “hysteresis”
which is the amount of
temperature lag (in degrees C)
for heater control. The other
parameters are registers and
values specific to the SR30 sensor
and should not be altered.
[command]
instruction = serial
sensor control
[control params]
heater coil = 1
fan coil = 3
temperature reg = 6
temperature reg count = 1
on temperature = 50
hysteresis = 5
*These command options are actionable via the webserver.