background image

TxBlock-USB 

NOVUS AUTOMATION 

3/5 

SOFTWARE AND APPLICATION CONFIGURATION:

 

 

Fig. 10 – TxConfig II software main screen 

 

Fig. 11 – TxConfig application main screen 

The fields in the screen mean: 
1.

 

General Information: This field shows information that identifying 

the transmitter. This information should be sent to the 

manufacturer in an eventual request for technical assistance. 

2.

 

Sensor: Select the type of sensor to be used. See Table 1

3.

 

Measuring Range:  Sets de measurement range of the 

transmitter. 
Lower Range Limit: equivalent temperature for a current of 4 mA. 
Upper Range Limit: equivalent temperature for a current of 20 mA. 

Sensor Range 
The values chosen cannot exceed the range of sensor shown in 

this field. See Table 1 of this manual. 
Minimum Range 
Do not set a lower band (span) that the Minimum Range 

indicated below in this same field. See Table 1 of this manual. 

4.

 

Sensor  Failure:  It establishes the output behavior, when the 

transmitter indicates a failure: 
Minimum:  Output  current goes to <  3.6  mA (down-scale), 

typically used for refrigeration. 
Maximum: Output current goes to > 22.0 mA (up-scale), typically 

used for heating. 

5.

 

Zero  Correction:  It corrects small deviations presented in the 

transmitter output, for example, when the sensor is replaced. 

6.

 

Send  Configuration:  It applies the new setup. Once sent, the 

setup will be immediately adopted by the transmitter. 

7.

 

Read Configuration: Reads the current setup in the transmitter 

connected. The screen now presents the current setup that may 

be changed by the user. 

FACTORY SETTING: 

 

Sensor: Pt100 3-wire, range 0 to 100 °C 

 

Sensor failure: upscale (maximum). 

 

0 °C zero correction. 

 

Unit: °C;  

 

Output: 4-20 mA. 

Upon purchase order, the user can define a specific setup. 

SMARTPHONE CONNECTIONS 

With the help of a specific cable, which allows smartphones to 

recognize and configure TxBlock-USB when running the TxConfig 

application, Android smartphones with On the Go (OTG) technology 

can be directly connected to the device via the Micro-USB. 
To do this, it is necessary to observe the connection mode of the 

cable On the Go in the device, as can be seen in Fig. 12

 

Fig. 12 – On the Go connection cable 

 

Incorrectly positioning the cable end may cause 

the device to be unrecognized by the application. 

Содержание TxBlock-USB

Страница 1: ...l 0 8 Nm RECOMMENDATIONS FOR INSTALLATION Sensor signals conductors must go through the plant system separate from power leads loop if possible in grounded conduits The instruments must be powered from the instrumentation power supply circuit In control and monitoring applications is essential to consider what can happen when any part of the system fails It is recommended the use of suppressors in...

Страница 2: ...install execute the TxConfigIISetup exe file and follow the instructions The setup application is only available for Android smartphones and also can be downloaded for free in the Google Play Store To configure the device through the application an On The Go OTG adapter is required The procedure for using this adapter will be explained throughout this manual Fig 8 USB cable connection During the s...

Страница 3: ...le typically used for refrigeration Maximum Output current goes to 22 0 mA up scale typically used for heating 5 Zero Correction It corrects small deviations presented in the transmitter output for example when the sensor is replaced 6 Send Configuration It applies the new setup Once sent the setup will be immediately adopted by the transmitter 7 Read Configuration Reads the current setup in the t...

Страница 4: ...ed sensors are listed in Table 1 along with their maximum ranges Thermocouples Types J K R S T N E and B accoding to IEC 60584 ITS 90 Impedance 1 MΩ Pt100 Type 3 wire Excitation 0 8 mA α 0 00385 according IEC 60751 ITS 90 For 2 wire sensors tie terminals 3 and 4 together Pt1000 Type 3 wire Excitation 0 65 mA α 0 00385 according IEC 60751 ITS 90 For 2 wire sensors tie terminals 3 and 4 together NTC...

Страница 5: ...device and its alarms are not intended to protect against device failures Independent safety devices should be always provided if personnel or property are at risk Device performance and specifications may be affected by its environment and installation It s user s responsibility to assure proper grounding shielding cable routing and electrical noise filtering in accordance with local regulations ...

Отзывы: