background image

TxBlock-USB 

NOVUS AUTOMATION 

2/5 

Pt1000 3-wire / Pt100 3-wire and 4-wire: For appropriate cable 

resistance compensation they should be equal for all legs. Maximum 

wire resistance is 25 

  per wire leg. Usage of a 3 or 4 wire with 

conductors of equal length and gauge is recommended. 

NTC 2-WIRE 

 

Fig. 5 – Transmitter electrical connections (NTC 2-wire) 

THERMOCOUPLES 

 

Fig. 6 – Transmitter electrical connections (Thermocouple) 

VOLTAGE (0-50 mV) 

 

Fig. 7 – Transmitter electrical connections (0-50 mV)

 

CONFIGURATION 

When the trasmitter is used with the factory setting, no further action 

is required and the transmitter is ready to be installed.  
Changes to the configuration are possible through the TxConfig  II 

software or the TxConfig application, provided free of charge.  
The TxBlock-USB Setup Kit consisting of the TxConfig II software and 

USB cable can be purchased from the manufacturer or any authorized 

distributor.  
The software is continuously updated and new versions can be 

downloaded at no charge from the manufacturer’s website. To install, 

execute the 

TxConfigIISetup.exe

 file and follow the instructions. 

The setup application is only available for Android smartphones and 

also can be downloaded for free in the Google Play Store. To configure 

the device through the application, an 

On The Go

  (OTG) adapter is 

required. The procedure for using this adapter will be explained 

throughout this manual. 

 

Fig. 8 – USB cable connection 

During the setup, the transmitter is powered by the USB, not 

requiring an external power supply. 
The transmitter setup can also be made by connecting it to the loop, 

using the 

loop

 power supply. There is no electrical insulation between 

the transmitter and the communication port (interface), therefore it is 

not recommended to configure it with the sensor inlet connected to the 

process. See Fig. 9

 

Fig. 9 – USB cable connections – 

Loop

 powered

 

After these connections, the user must run the TxConfig II software 

and, if necessary, consult the 

Help

 topic to help using the software. 

For more information on how to connect the TxBlock-USB  to the 

smartphone itself and to configure the device, see chapter 

SMARTPHONE CONNECTIONS

 

The USB communication port (interface) of the 

TxBlock-USB is not electrically insulated from the 

transmitter’s input. 

Содержание TxBlock-USB

Страница 1: ...l 0 8 Nm RECOMMENDATIONS FOR INSTALLATION Sensor signals conductors must go through the plant system separate from power leads loop if possible in grounded conduits The instruments must be powered from the instrumentation power supply circuit In control and monitoring applications is essential to consider what can happen when any part of the system fails It is recommended the use of suppressors in...

Страница 2: ...install execute the TxConfigIISetup exe file and follow the instructions The setup application is only available for Android smartphones and also can be downloaded for free in the Google Play Store To configure the device through the application an On The Go OTG adapter is required The procedure for using this adapter will be explained throughout this manual Fig 8 USB cable connection During the s...

Страница 3: ...le typically used for refrigeration Maximum Output current goes to 22 0 mA up scale typically used for heating 5 Zero Correction It corrects small deviations presented in the transmitter output for example when the sensor is replaced 6 Send Configuration It applies the new setup Once sent the setup will be immediately adopted by the transmitter 7 Read Configuration Reads the current setup in the t...

Страница 4: ...ed sensors are listed in Table 1 along with their maximum ranges Thermocouples Types J K R S T N E and B accoding to IEC 60584 ITS 90 Impedance 1 MΩ Pt100 Type 3 wire Excitation 0 8 mA α 0 00385 according IEC 60751 ITS 90 For 2 wire sensors tie terminals 3 and 4 together Pt1000 Type 3 wire Excitation 0 65 mA α 0 00385 according IEC 60751 ITS 90 For 2 wire sensors tie terminals 3 and 4 together NTC...

Страница 5: ...device and its alarms are not intended to protect against device failures Independent safety devices should be always provided if personnel or property are at risk Device performance and specifications may be affected by its environment and installation It s user s responsibility to assure proper grounding shielding cable routing and electrical noise filtering in accordance with local regulations ...

Отзывы: