Alert Threshold
The alert threshold screen allows the user to adjust the tolerance from the
reference voltage which, if exceeded in either direction, the output channel will
report a fault status. The default threshold value is set at ±25% percent from the
current state of the amplifier, and is user programmable in 5% increments, from
±10% to ±60%.
The output channel has a reference voltage which can be set by latching the
channel
’s current value in the latch channel average screen. The output
reference voltage can be set individually by writing the value serially with the
$SET command. After saving the current configuration on a channel, any
subsequent deviation on that channel which exceeds the alert threshold
percentage will trigger an alert.
Steps to ensure correct alert configuration:
1. Connect distribution cabling to the 10MHz output.
2. Set alert threshold to desired range.
3. Save current channel voltage with the latch channel values screen.
4. Save current settings on the save configuration screen.