NOVUS AUTOMATION
20/25
8.3.3.1
RETRANSMISSION OUTPUT CONFIGURATION
Figure 16 –
Output
The
Measurement
parameter allows you to read the differential pressure magnitude.
The analog output
Mode
allows you to select the electrical standard to be used for transmission: 0-10 V or 4-20 mA. The electrical signal of the
output will be proportional to the selected magnitude, respecting the values configured in the
Lower Limit
and
Upper Limit
parameters.
In case of a sensor failure, the quantity to be transmitted by the analog output will enter the
Error Mode
. For the error condition, you must select
the
High
,
Low
or
Low-High
status (see
Table 04
).
8.3.3.2
ALARM OUTPUT CONFIGURATION
To select the alarm output to be configured, you must click on the
button and enable it by sliding it to the right.
Figure 17 –
Alarm
The alarm output may be timed by the
Time On
and
Time Off
parameters.
If the device is configured in the
Value Lower than SPLo
,
Value Higher than SPHi
,
Inside the Range
or
Outside the Range
modes, the
Error
Condition
parameter allows you to configure a safe status of the alarm output in case of sensor failure. Thus, the output will be on or off depending
on the value set in this parameter.
Upper Limit
and
Lower Limit
are the differential pressure values that act as alarm activation conditions that, together with the
Hysteresis
, define
the barrier to be exceeded so that the channel exits the alarm situation. For more information about the alarm configuration, see
section.