Novus N480 Скачать руководство пользователя страница 7

N480

7

HIGH

differenti

al

3

SPA1

Negati

ve

SP + SPA1

SP

Alarm ON

TEMPERATURE

SPA1

Positi

ve

SP + SPA1

SP

Alarm

ON

TEMPERATURE

differenti

al or

deviation

4

SPA1

Negati

ve

SP + SPA1

SP - SPA1

SP

Alarm ON

TEMPERATURE

SPA1

Positi

ve

SP + SPA1

SP - SPA1

SP

Alarm

ON

Alarm

ON

TEMPERATURE

Input

sensor

error or

heater

break

detection

5

Alarm is ON whenever:

  Temperature is below/above selected range;

  Termocouple or Pt100 is broken;

  Pt100 is shorted;

  Pt100 is badly connected or wire impedance is too high;

  The heater resistence is broken

 

End of

Program

 

6

 

Activated when the programmed soak time is run out. Refer to item 4 of this manual.

 

7

 

Low limit alarm disabled at power-up

 

8

 

High limit alarm disabled at power-up

 

9

 

Differential low limit alarm disabled at power-up

 

10

 

Differential high limit alarm disabled at power-up

 

Alarm

Function

s

 

With

alarm

inhibition

at power-

up

 

11

 

Differential alarm disabled at power-up

Table 2 - Alarm functions and their identification codes

6.1  ALARM INITIAL BLOCKING

The initial blocking option inhibits the alarm from being recognized if an alarm condition is present when the controller is
first energized. The alarm will actuate only after the occurrence of a non alarm condition followed by a new occurrence for
the alarm.

7.  PID AUTO TUNE

During auto tune the temperature is controlled in ON/OFF mode at the programmed Set Point (SV). Depending on the
process characteristics large oscillations above and below SV may occur and auto tuning may take several minutes to be
concluded.
The recommended procedure is as follows:

  Program a new SP close to the desired final temperature other than the present measured temperature.

  Enable the auto tune at the “

Atvn

Atvn

Atvn

Atvn

” prompt by selecting 

1

.

 Set 

1

 at the

 

rvn

rvn

rvn

rvn

” prompt.

During auto tune large oscillations will be induced around the setpoint. Make sure the process can accept these
oscillations.
If auto tuning results are not satisfactory refer to table 3 for manual fine tuning procedure.

PARAMETER

RESPONSE

SOLUTION

Proportional

Slow Response

Decrease

Band

Large Oscillation

Increase

Integral

Slow Response

Increase

Rate

Large Oscillation

Decrease

Derivative

Slow Response or Instability

Decrease

Time

Large Oscillation

Increase

Table 3 - Suggestions for manual tuning of PID parameters

Содержание N480

Страница 1: ...N480 OUT OPERATING MANUAL ...

Страница 2: ...put 3 2 5 alarm outputs 4 3 configuration and operation 4 3 1 parameters flow chart 4 3 2 operation level 4 3 3 tuning and alarms level 4 3 4 configuration level 5 3 5 calibration level 5 4 ramp to soak function characteristics 6 5 problems with the controller 6 5 1 electronic serial number visualization 6 6 alarm functions 6 6 1 alarm initial blocking 7 7 pid auto tune 7 ...

Страница 3: ...c Operation 0 to 55 C humidity 20 to 85 2 2 TEMPERATURE SENSOR INPUT Pt100 3 wire connection Excitation current 170µA Thermocouple input impedance 10MΩ A D converter resolution 15000 steps Sampling rate 10 measurements per second Auto zero and auto range Accuracy 0 2 of full scale for Pt100 and 0 25 of full scale 1 C for T C Thermocouples are connected to terminals 8 and 9 with positive in termina...

Страница 4: ...is reached the controller returns to operation level and the display will indicate the measured temperature The display will also go back to the measured temperature whenever the display is inactive for 20 seconds or more When a parameter value is changed via keyboard the controller will only accept the new value after the user presses the INDEX key to go to next prompt or if the keyboard is left ...

Страница 5: ...s OUT A 1 1 1 1 Sets control output to terminals OUT B As control output is defined to terminals OUT A alarm output is automatically set to OUT B If control output is defined to OUT B alarm 1 will then be automatically set to OUT A spll SP Low Limit SET POINT LOW LIMIT sets the lower range for SV spKl SP High Limit SET POINT HIGH LIMIT Sets the upper range for SV A1fv Alarm 1 Function FUNCTION OF ...

Страница 6: ...to identify possible problems Process temperature is below the selected sensor range Process temperature is above the selected sensor range Controller or sensor error Example Broken thermocouple or Pt100 Pt100 badly connected short circuited or high cable resistance 5 1 ELECTRONIC SERIAL NUMBER VISUALIZATION To read the 8 digit serial number go to the Operation Level and press the key for 3 second...

Страница 7: ...rom being recognized if an alarm condition is present when the controller is first energized The alarm will actuate only after the occurrence of a non alarm condition followed by a new occurrence for the alarm 7 PID AUTO TUNE During auto tune the temperature is controlled in ON OFF mode at the programmed Set Point SV Depending on the process characteristics large oscillations above and below SV ma...

Страница 8: ...323 3600 FAX 51 33233644 E Mail info novus com br FILIAL São Paulo Rua José Augusto Penteado 107 V Madalena TEL 11 3675 0366 FAX 11 3675 0377 E Mail sp novus com br FILIAL Curitiba Rua Vereador Toaldo Túlio 2235 sala 4 TEL FAX 41 372 8476 Cel 41 99964524 E Mail pr novus com br ...

Отзывы: