Novus N480 Скачать руководство пользователя страница 4

N480

4

Both outputs are available in the basic model and the desired main control output is user selected via keyboard (refer to “

Cntr

Cntr

Cntr

Cntr

 

“ prompt). The remaining output can then be used as an alarm output.

In case of sensor break or failure an error 

"

Erro

Erro

Erro

Erro

"

 message is displayed and the control output is turned off.

2.5 ALARM 

OUTPUTS

  Alarm Output 1:

SPST relay 3A/250Vac or 5Vdc/20mA pulse

  Alarm Output 2:

SPST relay 3A/250Vca (optional)

3. CONFIGURATION 

AND 

OPERATION

Prior to first operation the controller should be fully configured. The user must set basic parameters as temperature type
(“

TYPE

TYPE

TYPE

TYPE

”), the desired control set point (“ 

SP

SP

SP

SP

 “), the alarms set points (“

SPA1

SPA1

SPA1

SPA1

” and “

SPA2

SPA2

SPA2

SPA2

”), etc.

3.1  PARAMETERS FLOW CHART

The programming parameters are organized in 4 different sets or levels:

 Operation 

level

  Alarms and tuning level

 Configuration 

level

 Calibration 

level

At power up the controller displays a prompt at the Operation Level and remains in this level while under normal operation.
The other levels are only accessed when a change of parameters is necessary (except for Set Point change). To reach
these other parameters the user must keep the INDEX Key ( 

 ) pressed for about three seconds. After this time the

controller will show the first parameter of the next level. By keeping the INDEX key pressed for another 3 seconds the next
level will be accessed.
Release the  

 key when the desired level is reached. Press once the 

 to go to the next prompt in the same level.

When a parameter is shown the display will alternate its name and value. The value can then be changed by pressing the

 or 

 key.

After the last parameter in one level is reached the controller returns to operation level and the display will indicate the
measured temperature.
The display will also go back to the measured temperature whenever the display is inactive for 20 seconds or more.
When a parameter value is changed via keyboard the controller will only accept the new value after the user presses the
INDEX key to go to next prompt or if the keyboard is left inactive for 20 seconds.

 

For disabling the keyboard, move the internal strap to the position KEY DISABLE. All parameters will be protected, accept
the 

SP parameter

.

 

KEY
DISABLE

 

KEY
DISABLE

Figure 2 – Strap in normal operating

position (enabled)

 

Figura 3 – Strap position for inhibiting the

keyboard

3.2 OPERATION 

LEVEL

 

TEMPERATURE

 

INDICATION

 

END

 

SP

 

S

et 

P

oint

 

TEMPERATURE

 measured by the sensor.

 

At power up, the upper display shows the process temperature value. It also shows the messages
described in chapter 5 of this manual.
The lower displays shows the set point value which is the temperature value desired for the process.

 

rAte

 

rAtE

TEMPERATURE RATE OF RISE

: The user defines the rate of temperature rise from the starting

temperature to the value set in “ 

SP

SP

SP

SP

 ”.

Rate is defined in 

°C / minute

.

 

T Sp

 

t

ime for

soak

TIME FOR SOAK

: Time in minutes which the temperature will remain at the selected “ 

SP

SP

SP

SP

 “.  Refer to

item 4.

 

Rvn

 

run

RUN

: At this prompt  the user sets the control output and alarms to active or to inactive.

0

0

0

0

 - inactive outputs;

1

1

1

1

 - active outputs;

3.3  TUNING AND ALARMS LEVEL

 

Atvn

 

A

uto 

tun

e

AUTO-TUNE

: Activates the auto-tuning of PID parameters.

0

0

0

0

 - Auto-tune is off;

1

1

1

1

 - Auto-tune is on;

 

Pb

 

P

roportional

b

and

PROPORTIONAL BAND

: percentage of maximum input span.

When set ot zero (

0

), control action is 

ON/OFF

.

 

Ir

 

i

ntegral 

r

ate

INTEGRAL RATE

: Integral time constant in repetitions per minute (Reset). This constant is not used

when controller is set to ON/OFF action (

Pb

=

0

).

Содержание N480

Страница 1: ...N480 OUT OPERATING MANUAL ...

Страница 2: ...put 3 2 5 alarm outputs 4 3 configuration and operation 4 3 1 parameters flow chart 4 3 2 operation level 4 3 3 tuning and alarms level 4 3 4 configuration level 5 3 5 calibration level 5 4 ramp to soak function characteristics 6 5 problems with the controller 6 5 1 electronic serial number visualization 6 6 alarm functions 6 6 1 alarm initial blocking 7 7 pid auto tune 7 ...

Страница 3: ...c Operation 0 to 55 C humidity 20 to 85 2 2 TEMPERATURE SENSOR INPUT Pt100 3 wire connection Excitation current 170µA Thermocouple input impedance 10MΩ A D converter resolution 15000 steps Sampling rate 10 measurements per second Auto zero and auto range Accuracy 0 2 of full scale for Pt100 and 0 25 of full scale 1 C for T C Thermocouples are connected to terminals 8 and 9 with positive in termina...

Страница 4: ...is reached the controller returns to operation level and the display will indicate the measured temperature The display will also go back to the measured temperature whenever the display is inactive for 20 seconds or more When a parameter value is changed via keyboard the controller will only accept the new value after the user presses the INDEX key to go to next prompt or if the keyboard is left ...

Страница 5: ...s OUT A 1 1 1 1 Sets control output to terminals OUT B As control output is defined to terminals OUT A alarm output is automatically set to OUT B If control output is defined to OUT B alarm 1 will then be automatically set to OUT A spll SP Low Limit SET POINT LOW LIMIT sets the lower range for SV spKl SP High Limit SET POINT HIGH LIMIT Sets the upper range for SV A1fv Alarm 1 Function FUNCTION OF ...

Страница 6: ...to identify possible problems Process temperature is below the selected sensor range Process temperature is above the selected sensor range Controller or sensor error Example Broken thermocouple or Pt100 Pt100 badly connected short circuited or high cable resistance 5 1 ELECTRONIC SERIAL NUMBER VISUALIZATION To read the 8 digit serial number go to the Operation Level and press the key for 3 second...

Страница 7: ...rom being recognized if an alarm condition is present when the controller is first energized The alarm will actuate only after the occurrence of a non alarm condition followed by a new occurrence for the alarm 7 PID AUTO TUNE During auto tune the temperature is controlled in ON OFF mode at the programmed Set Point SV Depending on the process characteristics large oscillations above and below SV ma...