Delay 1, 2 and 3

 - Delay time to start control. Upon power-on, control OUTPUT 

1 is kept 

off

 until the time programmed in 

dl1

 is elapsed.  Its usage is intended 

to prevent multiple compressors to start simultaneously after the turn-on of a 

system with several controllers.  Value in seconds, 0 to 250 s. 

of1 

Of2 

Of3 

Off time 1, 2 and 3

 - Defines the minimum 

off

 time for control OUTPUT. 

Once OUTPUT 1 is turned off, it remains so for at least the time programmed 

in 

of1

. For thermocouple inputs this parameter is not available. This 

parameter is intended for refrigeration systems where longer compressor life 

is desired. For heating systems, program

 of1

 to zero. Value in seconds, 0 

to 999 s. 

On1 

On2 

On3 

On time 1, 2 and 3

 - Defines the minimum 

on

 time for control OUTPUT 1. 

Once turned on, OUTPUT 1 remains so for at least the time programmed in 

on1

. For thermocouple inputs this parameter is not available. This 

parameter is intended for refrigeration systems where increased compressor 

life is desired. For heating systems, program

 

on1

 to zero. Value in seconds, 

0 to 999 s. 

2t1 
3t1 

Timer T1 

Time interval 

T1

  for alarm temporization. Defines the temporization mode 

and interval, as shown in Table 4. Adjustable from 0 to 1999 seconds. 

Available only when outputs 2 or 3 are configured as alarms. 

2t2 
3t2 

Timer T2

 

Time interval 

T2

  for alarm temporization. Defines the temporization mode 

and interval, as shown in Table 4. Adjustable from 0 to 1999 seconds. 

Available only when outputs 2 or 3 are configured as alarms. 

Add

 

Address

 - Controllers with the optional RS485 Modbus RTU communication 

interface have the 

Add

  parameter at the Configuration  level. Set a unique 

Modbus address for each equipment connected to the network. Address range 

is from 1 to 247. 

Level 3 – Calibration Level 

The  controller  is factory calibrated. The following parameters should be accessed only by 
experienced personnel. To enter this cycle, the 

 key must be kept pressed for 4 seconds. 

Don’t press the 

 

and

 

 

keys if you are not sure of the calibration procedures. 

Just press the 

 key a few times until the temperature measurement level is reached 

again. 

pas 

Password

 - Enter the correct password to unlock write operations for the 

parameters in the following levels. 

[Al 

Calibration low

  -  Offset value of the input. It adjusts the lower 

measurement range of the sensor. 

[Ak 

 

Calibration High

  -  Gain calibration. It adjusts the upper measurement 

range of the sensor. 

[JL 

 

Cold Junction Offset  calibration

  -  This parameter is available only for 

thermocouple. 

FA( 

Factory Calibration 

- Restores factory calibration parameters. Change from 

0

 to 

1

 to restore the calibration parameters with factory values.

 

Prt 

Protection

  - Defines the levels of parameters that will be password 

protected. See "Configuration Protection" for details.

 

Pa( 

Password Change

 - Allows changing the current password to a new one. 

Values from 1 to 999 are allowed.

 

Sn2 

Serial number

 - First part of the controller electronic serial number.  

sn1 

Serial number

 - Second part of the controller electronic serial number.  

sn0 

Serial number

 - Third part of the controller electronic serial number. 

WORKING WITH THE CONTROLLER 

Multiple output controllers are suited for controlling multiple stage systems.  

Other applications require OUTPUT 1 to be the control output and OUTPUT 2 to be the alarm.  
In a multiple stage application, 

SP1,

 

SP2

  and 

SP3

  are configured to operate at different 

temperatures, creating a progressive sequence for turning on the outputs (compressors) in 

response to a system demand.  
The output delays for turning on the compressors (

dL1

dl2

  and

 

dL3

) cause the 

compressors to be turned on one by one, minimizing energy demand. 
Another usage for multiple output controllers is in systems that require automatic selection 

between cool and heat action. In these applications, one output is configured as reverse 

action (heating) and the other as direct action (refrigeration).  

Alarm Functions 

There are eight distinct alarm functions implemented in OUTPUT 2 and 3, selected by the 

parameter 

Ac2

 and 

ac3

, described below: 

2

 -  Low temperature alarm – OUTPUT is turned on when the measured temperature falls 

below 

the respective set point value. 

3

 -  High temperature alarm –  OUTPUT is turned on when the measured temperature 

exceeds the respective set point value. 

4

 -  Inside range alarm – OUTPUT 2 is turned on when the measured temperature is within 

the range defined by: 

(

SP1

 – 

SP2

and

 (

SP1

 + 

SP2

or

 (

SP1

 – 

SP3

and

 (

SP1

 + 

SP3

)

 

5

 -  Outside range alarm: OUTPUT 2 is turned on when the temperature falls outside the 

range defined by: 

(

SP1

 – 

SP2

and

 (

SP1

 + 

SP2

or

 (

SP1

 – 

SP3

and

 (

SP1

 + 

SP3

)

 

Functions 

6

7

8

 e 

9

 are identical to the above ones except that they incorporate the Initial 

Blocking feature, which inhibits the output if an alarm condition is present at start-up. The 

alarm will be unblocked after the process reaches a non-alarm condition for the first time. 

Alarm Timer 

Alarms can be configured for timed operation. Three operation modes can be programmed: 

alarm delay, alarm timed pulse or alarm oscillator. Alarm temporization is available only for 

outputs 2 and 3 and is configured through parameters: “

2t1

”, “

3t1

”, “

2t2

” and “

3t2

”. 

Table 4 shows these advanced functions. Times T1 and T2 can be programmed from 0 to 

1999 seconds. Programming 0 (zero) in the timer parameters T1 and T2 disables the timer 

function. 
The output status led P2 and P3 in the controller panel, signals when the control output is on. 

Advanced 

Function 

T1 

T2 

ACTION 

Normal Operation 

Alarm Event

Alarm

Output

 

Delayed 

1 to 1999 s 

Alarm Event

Alarm

Output

T2

 

Pulse 

1 to 1999 s 

Alarm Event

Alarm

Output

T1

 

Oscillator 

1 to 1999 s  1 to 1999 s 

Alarm Event

Alarm

Output

T1

T2

T1

 

Table 4

 – Timer Alarm Functions 1 and 2

 

 

 
 

 

 

CONFIGURATION PROTECTION 

A protection system to avoid unwanted changes to the controller parameters is implemented. 

The level of protection can be selected from partial to full. The following parameters are part 

of the protection system: 

Pas

  When this parameter is presented, the correct password should be entered to allow 

changes of parameters in the following levels. 

Prt

  Defines the level of parameters that will be password protected: 

1 -  Only calibration level is protected (factory configuration); 

2 -  Calibration and Configuration levels are protected; 

3 -  All levels are protected - calibration, Configuration and setpoints. 

PA(

  Parameter for definition of a new password. Since it is located in the calibration level, 

can only be changed by a user that knows the current password. Valid passwords are 

in the range 1 to 999. 

CONFIGURATION PROTECTION USAGE 

PAS

 parameter  is displayed before entering a protected level. If the correct password is 

entered, parameters in all following levels can be changed. If wrong or no password is 

entered, parameters in the following levels will be read only.  

Important notes

1- After 

five

 consecutive attempts to enter a wrong password, new tentative will be blocked 

for the next 10 minutes. If the current valid password is unknown, the 

master password

 

can be used only to define a new password for the controller. 

2 - The password for a brand new device is 

111

ERROR MESSAGES 

Sensor measurement errors force the controller outputs to be turned off.  The cause for these 

errors may have origin in a bad connection, sensor defect (cable or element) or system 

temperature outside the sensor working range. The display signs related to measurement 

errors are shown below: 

 

Measured temperature exceeded maximum allowed range for the 

sensor. Broken Pt100, Pt1000 or T/C. Short circuited NTC sensor. 

 

Measured temperature is below minimum measurement range of the 

sensor. Short circuited Pt100, Pt1000 or T/C. Broken NTC. 

PRODUCT IDENTIFICATION 

The label attached to the controller case identifies the model and the optional present in the 

product, as described below: 

MODEL: 

N323 - A - B - C

, where: 

A

: Input Sensor:  

 

NTC

 or 

Pt100

 or 

Pt1000

 or 

J/K/T

 (Thermocouples) 

B

: Digital communication: 

blank 

or

 485

 (RS485, Modbus protocol) 

C

. Voltage rating:     

blank

 (100-240 Vac/dc) or 

24V

 (24 Vac/dc); 

TECHNICAL ASSISTANCE 

If you encounter a problem with your controller, review the configuration with regard to inputs, 

outputs, alarms, etc. If the problem persists, contact your supplier or Novus at 

[email protected]