Novus N2020 Скачать руководство пользователя страница 3

N2020 Controller  

NOVUS AUTOMATION 

3/7 

LBD – LOOP BREAK DETECTION 

The parameter defines a time interval, in minutes, within which the 

PV is expect to react to a control output signal. If the PV does not 

react properly within the time interval configured in 

lbd.t

, the 

controller interprets this as a control loop break and signals this 

occurrence in the display. 

LBD

 event may be sent to any output channel. Simply configure 

the 

LBD

 function to the desired output channel (OUT1 or OUT2): the 

selected output will be activated when a 

LBD

 condition is detected. 

When the 

Lbd.t

 parameter is programmed with 0 (zero), the 

LBD

 

function is disabled. 
The LBD is useful in detecting system failures, such us defective 

sensors or actuators, loads and power supply, among others. 

SAFE OUTPUT VALUE WITH SENSOR FAILURE 

This function defines an output value (user defined) to be assigned to 

the control output in the event of a sensor failure. 
When the input sensor is identified as broken, the controller switches 

the control mode to MANUAL while forcing MV to assume the user 

configured value in the 

1E.ov

 parameter. This function requires that 

one of the alarms be configured as 

1Err

 and the 

1E.ov

 parameter 

(control output percentage) programmed with a value other then 0 

(zero). 
Once this function is triggered, the controller remains in SAFE mode 

(MANUAL control output) even after the sensor failure appears to be 

fixed. The operator intervention is required for switching back to 

AUTO mode. 

1E.ov

 values are only 0 and 100 % when in ON/OFF control mode. 

For PID control mode any value in the range from 0 to 100 % is 

accepted. 

OFFSET 

Allows fine adjustments to the PV reading for compensation of 

sensor error. 

SOFT START 

 

The soft-start feature avoids abrupt variations in the power delivered 

to the load regardless of the system power demand.  

This is accomplished by defining a limiting ramp for the control 

output. The output is allowed to reach maximum value (100 %) only 

after the time programmed (in seconds) in the soft-start parameter 

has elapsed.  

The Soft-start function is generally used in processes that require 

slow start-up, where the instantaneous application of 100 % of the 

available power to the load may cause damages to parts of the 

system.  

In order to disable this function, the soft-start parameter must be 

configured with 0 (zero).  

Note: 

 

1- This feature is available only with PID (Proportional Band greater 

than zero).  

2- This feature is disabed if the parameter is set to 0 (zero). 

PROGRAMS OF RAMP AND SOAK 

The controller allows the creation of 

one

  ramps and temperature 

soaks program. This program is created from the values definition of 

SP and time intervals, defining up to nine (9) 

program segments

The figure below shows a program model with 9 segments: 

 

Fig. 04

 - Example of ramps and soaks program 

The program created is storage permanently on the controller’s ram. 

It may be always changed, executed and repeated whenever 

necessary. 
For the program’s execution: 

1- Turn off the outputs (

rvn

NO

); 

2- Enable the parameter execution 

E.Pr

yes

3- Start-up the outputs: (

rvn

yes

). 

Once the program execution is started, the controller starts to create 

automatically the SP values defined for each program segment. The 

SP adjustment on the indication screen is blocked. 

Program Toleration Function - 

PtoL

 

The program toleration function “

PtoL

” defines the maximum error 

limit between PV and SP values during the program execution. If this 

limit is exceeded, the time counting of the segment (Pt1...Pt9) is 

stopped until the error is within the established tolerance. With a 

value >0 the user indicates in its program that priority must be given 

to PV in relation to the indeterminate value times. 
If 0 is programmed in the tolerance (

Ptol

= 0), the controller 

executes the program defined without considering eventual errors 

between PV and SP. Thus, the user defines that the priority has to be 

given for the execution time of the program. 

Programs with few Segments 

For the execution of programs with few segments, it is enough to 

program 0 (zero) for the time interval of the segment, which 

succeeds the last segment of the desired program. 

 

SP 

Time 

T1 

T2 

T3 

SP0 

SP1 

SP2 

SP3 

T4=0 

 

Fig. 05

 - Program example with three segments 

Successive Repetitions of a Program 

The program created may be repeated for several times, always 

restarting immediately after the end of each execution. 
The parameter 

rPt.p

  (

r

e

P

eat 

P

rogram) in the Programs cycle 

configures the number of times the program must be 

REPEATED

. It 

determines the number of executions besides the first execution. 
With 0, the program is executed once. It won’t repeat. 
Important: After the last execution of the program, all controller 

outputs will be turned off and the 

RUN

 parameter is 

OFF

OPERATION 

The controller’s front panel, with its parts, can be seen in the 

Fig. 06

 

Fig. 06

 - Identification of the parts referring to the front panel 

Display

: It shows the variable measured, configuration parameters 

symbols and its respective values/conditions. 

TUNE indicator

: Stays ON while the controller is in tuning process. 

Содержание N2020

Страница 1: ...r instrumentation It is strongly recommended to apply RC S FILTERS noise suppressor to contactor coils solenoids etc FEATURES INPUT TYPE SELECTION The input type to be used by the controller is defined in the equipment settings Table 01 shows the input options available for the user one of them must be selected during the controller setting TYPE CODE RANGE OF MEASUREMENT Thermocouple J Tc j Range ...

Страница 2: ... control and also with the PID control with the automatic tuning resource ALARM OUTPUT The controller has two alarms which may be directed for any of the output channels These alarms can be configured to operate the different functions described on Table 02 off Alarms turned off lo Alarm of Absolute Minimum Value Triggers when the value of measured PV is below the value defined for alarm Setpoint ...

Страница 3: ...This feature is disabed if the parameter is set to 0 zero PROGRAMS OF RAMP AND SOAK The controller allows the creation of one ramps and temperature soaks program This program is created from the values definition of SP and time intervals defining up to nine 9 program segments The figure below shows a program model with 9 segments Fig 04 Example of ramps and soaks program The program created is sto...

Страница 4: ...e the MV value may be changed by the user To differ this screen from SP screen the MV value blinks constantly E pr Enable Program Selects the ramp and soak profile program to be executed no the program is not executed yes the program is executed With enabled outputs RvN YES the program starts right after the program is selected rvn RUN Function Enables control outputs and alarms YES Outputs enable...

Страница 5: ... measured signal PV Adjustable between 0 and 20 In 0 zero it means filter turned off and 20 means maximum filter The higher the filter value the slower is the response of the measured value Dp po Decimal Point Determines the presentation of the decimal point vni t Unit Defines the temperature unit to be used Indication in Celsius f Indication in Fahrenheit 0ffs Offset Parameter that allows the use...

Страница 6: ...roller serial number is displayed by pressing for 5 seconds DETERMINATION OF PID PARAMETERS Automatic tuning allows the controller to obtain P I D parameters proportional band full rate derivative time During the process of determining automatically the PID parameters the system is controlled in ON OFF in the programmed Setpoint The auto tuning process may take several minutes to be completed depe...

Страница 7: ...ture sensor 15 minutes minimum time for terminal accommodations shall be observed SAFETY INFORMATION Any control system design should take into account that any part of the system has the potential to fail This product is not a protection or safety device and its alarms are not intended to protect against product failures Independent safety devices should be always provided if personnel or propert...

Отзывы: