Novus N2020 Скачать руководство пользователя страница 2

N2020 Controller  

NOVUS AUTOMATION 

2/7 

OUT4

 - 

Analog output: 

 

 Electrical current, 0-20 mA or 4-20 mA 

 

 Electrical voltage pulse, 10 Vdc / 20 mA 

 

 Available at 29 and 30 terminals of controller 

CONTROL OUTPUT 

It is the output channel which effectively actuates on the process. 

Main exit. 

ALARM OUTPUT 

Output channels which actuates on the protection and signalization 

of process condition. 

RUN FUNCTION 

RUN parameter (

rvn

) works as a main key of output channels of 

controller. It enables channels defined as control output and channels 

defined as alarm output. With 

YES

 in this parameter, the control and 

alarm outputs are able to operate, turning on / off, according to the 

controller’s determinations. With 

NO

, all outputs remain off, regardless 

of the process requirements. In this condition, the controller’s display 

starts to show the 

STOP

  message, alternately with the measured 

temperature value (PV). 
This function can also be obtained by the 

F

 key when configured to 

operate in such mode. 

AUTOMATIC CONTROL MODE 

The controller may act in two different modes of operation: 

Automatic

 

mode or 

Manual

 mode. 

In automatic mode, the controller determines the control output 

behavior in order to lead the process up to the defined value in SP. It 

determines the duration the control output remains on and off, 

balancing the energy quantity applied to the process. In a technical 

language: it determines the MV value (Manipulated Variable). This is 

the normal mode of the controller operation. 
The parameter “

(trl

” defines the control mode to be adopted: 

 

Avto

   for automatic control. 

Man

   for manual control. 

This exchange functionality between automatic and manual mode 

can also be obtained by the   key, when configured to operate in 

such mode. 
The period (PWM cycle period) is defined in Cycle time parameter 

(

(t

). In it, a time interval (

seconds

), is defined and considered as a 

reference for the determination of MV. 
For instance: For a 10 seconds interval ((t = 10), 20 % MV means 

output on for 2 seconds and off for 8 seconds, balancing the energy 

quantity applied to the process. 

MANUAL CONTROL MODE  

In the manual mode, is the user who determines the control output 

behavior. It defines the MV value, this value will not be interfered by 

the controller. 
By exchanging the automatic mode to manual mode, the value 

adopted for MV will be the last value defined automatically by the 

controller.  It is known as “

bumpless

 transfer”. 

ON-OFF CONTROL / PID CONTROL 

In the automatic mode, it acts with ON-OFF adjustable hysteresis 

control and also with the PID control with the automatic tuning 

resource. 

ALARM OUTPUT 

The controller has two alarms which may be directed for any of the 

output channels. These alarms can be configured to operate the 

different functions described on 

Table 02

off

 

Alarms turned off. 

lo

 

Alarm of Absolute Minimum 

Value. Triggers when the 

value of measured 

PV

  is 

below

  the value defined for 

alarm Setpoint (SPA1 or 

SPA2). 

 

SPA1 

PV 

 

ki

 

Alarm of Valor Absolute 

Maximum Value. Triggers 

when the value of measured 

PV

  is 

above

  the value 

defined for alarm Setpoint. 

 

SPA1 

PV 

 

dif

 

Alarm of Differential Value. In this function the 

parameters 

SPA1

 and 

SPA2

 represent the deviation of 

PV in relation to the SP of CONTROL. 

 

SP 

PV 

SP + SPA1 

SP – SPA1 

 

 

SP 

PV 

SV – SPA1 

 

 

SV + SPA1 

 

 

SPA1 positive 

SPA1 negative 

difl

 

Alarm of Minimum Differential Value. It triggers when 

the value of PV is 

below

 the defined point by (using 

the Alarm 1 as example): 

 

SP 

PV 

SP – SPA1 

 

 

SP 

PV 

SP – SPA1 

 

SPA1 positive 

SPA1 negative 

difk

 

Alarm of Valor Maximum Differential Value. Triggers 

when the value of PV is 

above

 the defined point by 

(using Alarm 1 as example): 

 

SP 

PV 

SP + SPA1 

 

 

SP 

PV 

SP + SPA1 

 

SPA1 positive 

SPA1 negative 

ierr

 

Sensor Break Alarm. Activated when the input signal of 

PV is interrupted, out of the range limits or Pt100 in short-

circuit. 

Rs

 

Program  Segment Alarms. It acts when a certain 

segment of the ramps and soaks programs is 

reached. The respective segment is defined on the 

creation of ramps and soaks programs. 

Table 02

 – Alarme functions 

Note

: Alarm functions on 

Table 02

 are also valid for Alarm 2 (SPA2). 

INITIAL BLOCKING OF ALARM 

The 

initial blocking

 option inhibits the alarm from being recognized 

if an alarm condition is present when the controller is first energized 

(or after a transition from run YES or NO). The alarm will be enabled 

only after the occurrence of a non-alarm condition followed by a new 

occurrence for the alarm. 
The initial blocking is useful, for instance, when one of the alarms is 

configured as a minimum value alarm, causing the activation of the 

alarm  soon upon the process start-up, an occurrence that may be 

undesirable. 
The first lock out is not valid for 

ierr

 function (Open Sensor). 

PV AND SP ANALOGICAL RETRANSMISSION 

The analogical output, 

OUT4

when available

, may perform the 

retransmission of PV or SP values, with 0-20 mA or 4-20 mA signs. 

The analogical retransmission is scalable, i.e., it has minimum and 

maximum limits, which define the output range, defined in 

rtLL

 and 

rtkL

 parameters. 

To obtain a retransmission in voltage, the user should install one 

shunt resistor (500 

 max.) on the analogical output terminals. The 

value of this resistor depends on the voltage tension desired. 

Содержание N2020

Страница 1: ...r instrumentation It is strongly recommended to apply RC S FILTERS noise suppressor to contactor coils solenoids etc FEATURES INPUT TYPE SELECTION The input type to be used by the controller is defined in the equipment settings Table 01 shows the input options available for the user one of them must be selected during the controller setting TYPE CODE RANGE OF MEASUREMENT Thermocouple J Tc j Range ...

Страница 2: ... control and also with the PID control with the automatic tuning resource ALARM OUTPUT The controller has two alarms which may be directed for any of the output channels These alarms can be configured to operate the different functions described on Table 02 off Alarms turned off lo Alarm of Absolute Minimum Value Triggers when the value of measured PV is below the value defined for alarm Setpoint ...

Страница 3: ...This feature is disabed if the parameter is set to 0 zero PROGRAMS OF RAMP AND SOAK The controller allows the creation of one ramps and temperature soaks program This program is created from the values definition of SP and time intervals defining up to nine 9 program segments The figure below shows a program model with 9 segments Fig 04 Example of ramps and soaks program The program created is sto...

Страница 4: ...e the MV value may be changed by the user To differ this screen from SP screen the MV value blinks constantly E pr Enable Program Selects the ramp and soak profile program to be executed no the program is not executed yes the program is executed With enabled outputs RvN YES the program starts right after the program is selected rvn RUN Function Enables control outputs and alarms YES Outputs enable...

Страница 5: ... measured signal PV Adjustable between 0 and 20 In 0 zero it means filter turned off and 20 means maximum filter The higher the filter value the slower is the response of the measured value Dp po Decimal Point Determines the presentation of the decimal point vni t Unit Defines the temperature unit to be used Indication in Celsius f Indication in Fahrenheit 0ffs Offset Parameter that allows the use...

Страница 6: ...roller serial number is displayed by pressing for 5 seconds DETERMINATION OF PID PARAMETERS Automatic tuning allows the controller to obtain P I D parameters proportional band full rate derivative time During the process of determining automatically the PID parameters the system is controlled in ON OFF in the programmed Setpoint The auto tuning process may take several minutes to be completed depe...

Страница 7: ...ture sensor 15 minutes minimum time for terminal accommodations shall be observed SAFETY INFORMATION Any control system design should take into account that any part of the system has the potential to fail This product is not a protection or safety device and its alarms are not intended to protect against product failures Independent safety devices should be always provided if personnel or propert...

Отзывы: