N1540 Indicator 

NOVUS AUTOMATION 

4/5 

bla1

 

bla2

  

Blocking 

Alarm 

Alarms Initial Blocking. 

YES

  enables the initial blocking 

NO 

  inhibits the initial blocking 

xya1

 

xya2

  

Hysteresis of 

Alarm 

Alarm Hysteresis. It defines the difference between the 

value  of  PV  at which the  alarm  is triggered  and the 

value at which it is turned off. 

flsh 

Flash 

It allows signalization of an alarm conditions occurrence 

by flashing the  indication  of  PV  on the  indication 

display. 

YES 

Enables alarm signalization by flashing PV

NO 

Disables the flashing PV

INPUT CYCLE 

Type 

Type

 

Input  Type.  Selection of the  input  type, used by the 

indicator. Refer to Table 01

fltr 

Filter

 

Digital Input Filter – Used to improve the stability of the 

measured signal (PV). Adjustable between 0 and 20. 

At  0 (zero) it means  filter  turned off and  20  means 

maximum filter. The higher the filter value, the slower 

is the response of the measured value. 

Dp.po 

Decimal Point 

It determines the position of the decimal point on the 

display. 

vn

i

 t 

Unit

 

It defines the temperature unit to be used: 

Indication in Celsius. 

Indication in Fahrenheit. 

0ffs 

Offset

 

Parameter  that allows the  user  to make  fine 

adjustments to the indicated PV value. 

i

nll 

Input Low 

Limit

 

It defines the lower value of the indication range when 

the input types of 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V 

and 0-10 V are used. 

i

nxl 

input High 

Limit

 

It defines the upper value of the indication range when 

the input types of 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V 

and 0-10 V are used. 

bavd 

Baud Rate 

Baud Rate of the serial communication. In kbps. 
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 and 115.2  

prty 

Parity 

Parity of the serial communication. 

none

   

Without parity 

Even

   

Even parity  

0dd

   

Odd parity 

Addr 

Address 

Communication Address. A number that identifies the 

indicator in the serial communication network, between 

1 and 247. 

CALIBRATION CYCLE  
All types of  input  are  calibrated in the factory.  In  case a 

recalibration is required; it shall be carried out by a specialized 

professional. In case this cycle is accidentally accessed, do not 

perform alteration in its parameters. The factory calibration can 

be restored in the parameter 

rstr

pass 

Password.  Entering the  Access password.  This 

parameter  is  presented  before the protected  cycles. 

See item Protection of Configuration. 

(alib 

Calibration.  Enables the possibility for calibration  of 

the indicator. When the calibration is not enabled, the 

related parameters are hidden. 

inL( 

Input Low Calibration.  Indication of the low scale 

calibration signal applied to the input. 

ink( 

Input High Calibration.  Indication of the full scale 

calibration signal applied to the input. 

rstr 

Restore.  It restores  the factory calibrations of the 

input, disregarding any modifications carried out by the 

user. 

(j 

Cold Junction.  Temperature  of the indicator  cold 

junction. 

Pas.( 

Password Change.  It allows the definition of a new 

access password, always different from zero. 

Prot 

Protection. Sets up the Level of Protection. See Table 

03

Freq 

Frequency. Frequency of the local electrical network.  

Sn k 

First part of the indicator serial number. 

Sn l 

Second part of the indicator serial number. 

PROTECTION CONFIGURATION  

The  indicator provides means for protecting the parameters 

configurations, not allowing modifications to the parameters values, 

avoiding tampering or improper manipulation. The parameter 

Protection (

PROt

) in the Calibration level determines the protection 

strategy, limiting the access to particular levels, as shown in the table 

below. 

Protection Level  

Protected Levels 

Only the Calibration level is protected. 

Input and Calibration levels are protected. 

Alarms, Input and Calibration levels are 

protected. 

Table 03 – Levels of Protection of the Configuration 

ACCESS PASSWORD 
The protected levels, when accessed, request the user to provide the 

Access Password  for granting permission to change the 

configuration of the parameters on these levels. 
The prompt 

PASS

 precedes the parameters on the protected levels. 

If no password is entered, the parameters of the protected levels can 

only be visualized. 
The Access Password is defined by the user in the parameter 

Password Change  (

PAS.(

), present in the Calibration Level. The 

factory default for the password code is 1111
PROTECTION OF THE ACCESS PASSWORD 
The protection system built into the indicator blocks for 10 minutes 

the access to protected parameters after 5 consecutive frustrated 

attempts of guessing the correct password. 
MASTER PASSWORD  
The Master Password is intended for allowing the user to define a 

new password in the event of it being forgotten. The Master 

Password doesn’t grant access to all parameters, only to the 

Password Change  parameter (

PAS(

). After defining the new 

password, the protected parameters may be accessed (and 

modified) using this new password. 
The master password is made up by the last three digits of the serial 

number of the indicator added to the number 9000. 
As an example, for the equipment with serial number 07154321, the 

master password is 9 3 2 1. 
The  indicator  serial number can be obtained by pressing 

 

  for 5 

seconds. 
 
 
 
 