N1540 Indicator 

NOVUS AUTOMATION 

3/5 

 

 

 

 

Figure 03 – Current (mA) and Voltage (V) signal connection 

This indicator offers an auxiliary 24 Vdc power supply which is 

tipically applied to power up two wire 4-20 mA field transmitters. The 

Figure 04 presents the wiring for this application. 

 

 

 

Figure 04 – Auxiliary 24 Vdc usage example 

RECOMMENDATIONS FOR THE INSTALLATION 

 

To minimize the pick-up of electrical noise, the low voltage DC 

connections and the sensor input wiring should be routed away 

from high-current power conductors. If this is impractical, use 

shielded cables. In general, keep cable lengths to a minimum. 

 

The input signals conductors shall be positioned throughout the 

factory separate from the output and the power supply 

conductors, in grounded conduits if possible. 

 

The power supply of the electronic instruments shall come from a 

proper source for the instrumentation network. 

 

It is recommended to use RC FILTERS (0,1 uF in series with 100 

ohms) to suppress the noise generated by contactors coils, 

solenoids, etc. 

OVER-TEMPERATURE PROTECTION  
When designing any control system it is essential to consider what 

will happen if any part of the system should fail. In temperature 

control applications the primary danger is one in which the heating 

remains constantly on. In any application where physical injury or 

destruction of equipment might occur, it is recommend to install an 

independent protection equipment, with a separate temperature 

sensor, to disable the heating circuit in case of overheating. Please 

note that the alarm relays within the indicator will not give protection 

under all failure conditions. 

OPERATION 

The indicator front panel, together with its elements, can be seen on 

Figure 02

 

Figure 02 - Identification of the front panel parts 

Display:  Shows the process  variable  PV, the configuration 

parameters prompts and their respective values/conditions. 
Indicators  A1  and  A2:  signalize the occurrence of an alarm 

condition. 
Key P:   used to walk through the parameters in the menu cycles.  
F1 / 

 

 key and F2 / 

 

 key: Used to change parameter values. 

Key 

 

: go back to the previous displayed parameter. 

START UP 
When the indicator is powered up, its firmware version is displayed 

for 3 seconds, after which the N1540 starts normal operation, when 

the value of PV is displayed and the outputs are enabled. 
Before the indicator is ready to be used in a given process, it requires 

some basic configuration, consisting of assigning values to the 

parameters according to the desired behavior.  The  user  shall 

understand the importance of each parameter and determine a valid 

condition or a valid value for each one of them. 
The configuration parameters are grouped in levels according to their 

affinity. The 4 parameters levels are: 

1 – Operation 

2 – Alarms 

3 – Input 

4 – Calibration 

The “P” key provides the access to the levels and to the parameters 

of these levels. 
Keeping the P key pressed, at every 2 seconds, the indicator jumps 

from one  level  to another,  presenting the first  parameter  of each 

level: 

PV  >>  

fva1

  >>  

type

  >>  

pass

  >>  PV  … 

To enter into a particular level, simply release the P key when the 

first parameter in that level is displayed. 
To walk through the parameters in a level, press the P key with short 

strokes. To go back to the previous parameters, use the 

 

 Key. 

The display alternates the presentation of the parameter prompt and 

its value. The parameter value is displayed with a light blinking to 

differentiate it from the parameter prompt.  
Depending on the level of parameter protection adopted, the 

parameter PASS precedes the first parameter in the level where the 

protection is active. See section PROTECTION CONFIGURATION. 

DESCRIPTION OF THE PARAMETERS 

OPERATION CYCLE 

PV 

Indication Display of PV. The value of the measured 

variable (PV) is shown on the upper display (red). 

Sp.a1

  

Sp.a2  

Alarm SP: Value that defines the alarm activation point.  
For the  alarms  set up  with the  functions  of the type 

Differential,  these  parameters  define the maximum 

differences accepted between  PV  and  a reference 

value defined in the parameter 

ALrF

For the  alarm  function 

ierr,

  this  parameter  is not 

used. 

Parameters  shown in this level only  when  enabled in 

the parameters 

sp1.E

 and 

sp2.E

ALARMS CYCLE 

Fva1

 

Fva2

  

Alarm Functions. It defines the functions of the alarms 

among the options in Table 02

al.rf

 

Reference value  used by the  alarms  with differential 

function, minimum differential or maximum differential. 

Sp.a1

  

Sp.a2 

Alarm SP: Value that defines the point of activation of 

the alarm outputs. For the alarms programmed with the 

functions  of the type  Differential,  these  parameters 

represent the deviations. 
For the 

ierr

  alarm function, this  parameter  has no 

meaning. 

Sp1.e 
sp2.e 

SP Enable

 

It allows the parameters SPA1 and SPA2 to be displays 

also in the indicator operation cycle. 

YES

  shows the  parameters SPA1/SPA2 in the 

operation cycle  

NO 

  Does not show the parameters SPA1/SPA2 in 

the operation cycle 