N1500FT Flow Indicator 

NOVUS AUTOMATION 

6/8 

CUSTOMIZED LINEARIZATION CYCLE 

Lin.enbl 

Linearization 

Enabl

Enables linearization. Applicable only when 

flow input is 4-20 mA. 

1np.01 

Input 01 

First input point for linearization. 

0vT.01 

Output 01 

First output point for linearization. 

1np.02 

Input 02 

Second input point for linearization. 

0vT.02 

Output 02 

Second output point for linearization. 

 

27 input and output points for linearization. 

1np.30 

Input 30 

Last input point for linearization. 

0vT.30 

Output 30 

Last output point for linearization. 

Table 10 – Customized linearization cycle keys 

HARDWARE CYCLE (MANUAL MODE) 

manual

 

Manual mode

 

Enables manual mode of operation. 

(ur.0ut

 

Current Out

 

Current output status in manual mode. 

PUl.0ut

 

Pulse Out

 

Pulse output status in manual mode. 

Rl1.0ut

 

Relay 1 Out

 

Relay 1 output status in manual mode. 

Rl2.0ut

 

Relay 2 Out

 

Relay 2 output status in manual mode. 

Rl3.0ut

 

Relay 3 Out

 

Relay 3 output status in manual mode. Visible 

only for the 4 relays model. 

Rl4.0ut

 

Relay 4 Out

 

Relay 4 output status in manual mode. Visible 

only for the 4 relays model. 

Table 11 – Hardware cycle keys 

CALIBRATION CYCLE 
All input and output types are factory calibrated. If recalibration is 

required, it must be performed by a specialist. If this cycle is 

accidentally accessed, go through all parameters without changing 

values. 

PASS 

Password

 

Access Password entry. 
This parameter is shown before protected 

cycles. See item Configuration Protection. 

(alib 

Calibration 

Enables calibration. 

inL( 

Input Low 

Calibration 

Entry of value close to the beginning of scale 

in 4-20 mA input, within scale specified in 

InLL

 and 

InKL

inx( 

Input High 

Calibration 

Entry of value close to the end of scale in 4-20 

mA input, within scale specified in 

InLL

 and 

InKL

ovL( 

Output Low 

Calibration 

On this screen, whenever you press 

 or 

, a standard current close to 4 mA will 

be applied. Measure current, in mA, and enter 

it on this screen. 

ovx( 

Output High 

Calibration 

On this screen, whenever you press 

 or 

, a standard current close to 20 mA will 

be applied. Measure current, in mA, and enter 

it on this screen. 

rstr 

Restor

Restores factory calibration. 

Pa.(x 

Password 

Change 

Changes user password. 

Prot 

Protection 

Protection level. 

Table 12 – Calibration cycle keys 

CONFIGURATION PROTECTION 

The indicator allows configuration protection as determined by user, 

preventing unauthorized changes. The Protection (

PROt

) parameter, 

in the Calibration cycle, determines the protection level to be 

adopted, limiting Access to cycles, as shown in the table below. 

PROTECTION 

LEVEL 

PROTECTED CYCLE 

Calibration 

Calib Hardware 

Calib Ha Linearization 

Calib Ha Lineari Output 

Config. 

Calib Ha Lineari Output 

Config. + Input Config. 

Calib Ha Lineari Output 

Config. + Input Config. + Functions 

Calib Ha Lineari Output 

Config. + Input Config. + Fun Alarm 

Calib Ha Lineari Output 

Config. + Input Config. + Fun Alarm + 

Main 

Table 13 – Configuration Protection Levels 

Access Password 
To access the protected cycles, it is necessary to enter an Access 

Password  that allows altering the configuration of parameters in 

these cycles. 
The access password is entered in the 

Pass

  parameter, which is 

shown in the first of protected cycles. 
Without  a protection password, parameters of the protected cycles 

can be only viewed. 
The Access Password is defined by user in the Password Change 

(

PA.(k

) parameter, shown in the Calibration cycle. 

New indicators come from factory with access password “1111”. 
MASTER PASSWORD 
If you forget the access password, it is possible to use the Master 

Password feature. When this password is entered, users gain access 

to the Password Change (

PA.(k

) parameter and are allowed to 

specify a new access password to the indicator. 
The Master Password consists of the last three digits of the indicator 

serial number added to the number 9000. 
For example, for a device with serial number “12154321”, master 

password is “9 3 2 1”. 

MAINTENANCE 

PROBLEMS WITH INDICATOR 
Connection errors and inadequate programming are the main 

problems when using the indicator. A final review should prevent 

losses and wasting time. 

Содержание N1500FT

Страница 1: ...ays With pulse flow input totalization will continue even if the input rate is below the minimum rate required Instantaneous flow rate indication will be zero whenever there is a time lapse of 10 seco...

Страница 2: ...maximum values of instantaneous flow rate These values can be viewed on the first screen of the main cycle by pushing and respectively The key can be set to zero maximum and minimum values FEEDER The...

Страница 3: ...this key for more than 10 seconds inside the main cycle the 8 digit serial number will be shown on both displays FUNCTION OPERATION METHOD Go to the next cycle Press for more than 3 seconds Go to nex...

Страница 4: ...t from off and 1 Error BLA3 Block Alarm 3 A3t1 Alarm 3 Timer 1 Visible only if Fva3 is different from off A3t2 Alarm 3 Timer 2 Fva4 Function Alarm 4 Selection of Function Alarm 4 off 1 Error Lo x1 and...

Страница 5: ...ion applies quadratic function on the input signal within the limits programmed in inLL and inkL Table 7 Input setup cycle keys 1 Special application of alarm outputs When an alarm is set as Feeder an...

Страница 6: ...dard current close to 20 mA will be applied Measure current in mA and enter it on this screen rstr Restore Restores factory calibration Pa x Password Change Changes user password Prot Protection Prote...

Страница 7: ...ster The indicator takes broadcast type commands addresses to all network instruments For this type of command the indicator does not send any reply or acknowledgement FEATURES Signals compatible with...

Страница 8: ...Communication Nothing shown basic version with no serial communication 485 version with RS485 serial Modbus protocol D Power Supply Nothing shown basic version power supply of 100 to 240 Vac 24V vers...

Отзывы: