RECOMMENDATIONS FOR THE INSTALLATION 
Installation, operation, and maintenance must only be carried out by 

qualified personnel and in accordance with the information provided 

in this manual. Any deviation from these instructions will be the sole 

responsibility of the client. 
Normal safety precautions should be taken to avoid the possibility of 

an accident occurring when operating under high pressure and/or 

high temperature conditions. 
Do not connect the power supply until the entire installation is 

complete. 

CALIBRATION 

The indicator leaves the factory calibrated and ready for use. 

Recalibration is a procedure that is not recommended for 

inexperienced operators. 
You should consider using the recovery feature of the last performed 

calibration (

rstr

). If no other calibration has been performed, the 

factory calibration is still available. 
If the calibration is actually required, you should proceed as follows: 
1.

 

Provide a power generator with accuracy  compatible with the 

measurement accuracy specification of the indicator. 

2.

 

Connect the generator to the indicator according to Figure 03

 

Figure 03 – Power generator 

3.

 

Set a current of 12 mA in the power generator. 

4.

 

Set a value for the 

inLL

 parameter (the value must be lower 

than the defined value set for 

nxL

). 

5.

 

Enter the correct password. 

6.

 

Change the 

Prot

 parameter to 

2

 and thus allow changes in all 

configuration parameters. 

7.

 

Change the 

(alib

  parameter to 

YES

  and thus enable the 

calibration and its parameters. 

8.

 

Access the 

INL(

 parameter. 

9.

 

Set a current of 4 mA in the power generator. 

10.

 

Set the value of parameter 

INL(

 so that it reads -1999. 

11.

 

Access the 

INx(

 parameter. 

12.

 

Set a current of 20 mA in the power generator. 

13.

 

Set the value of 

INx( 

parameter so that it indicates 9999. 

14.

 

Validate the calibration mode. 

MECHANICAL INSTALLATION 

Figure 04 provides information on the dimensions of the indicator: 

 

Figure 04 – Dimensions 

SPECIFICATIONS 

DIMENSIONS: ............................................................... See Figure 04 

Approximate Weight: ...............................................................54 g 

ENVIRONMENTAL CONDITIONS

Operating Temperature: ............................................  -40 to 85 °C 

POWER SUPPLY........................................... Loop current 4 to 20 mA 
MAXIMUM LOOP CURRENT .................................................... 60 mA 
INDICATION RANGE ........................... -1999 to 9999 / 9999 to -1999 
DISPLAY RESOLUTION ............... 11998 levels (from -1999 to 9999) 
ACCURACY OF THE INDICATED VALUE ..........................................  
 .......................................................... 0.1 % of span

 ± 

1 digit (@ 25°C) 

SAMPLING RATE ..................................................................... 100 ms 
THERMAL COEFFICIENT
 .................................. 0.005 % / °C of span 
VOLTAGE DROP AT THE INDICATOR:..............................................  

< 10 mA: ............................................................................. < 5.4 V 
10 to 12 mA: ....................................................................... < 3.9 V 
> 12 mA: ............................................................................. < 2.6 V

 

HOUSING .................................................. ABS (Polyurethane gasket) 
PROTECTION .............................................................. IP65, NEMA4X 
CERTIFICATION .............................................................................. CE 

IDENTIFICATION 

LoopView  

Basic version

 

WARRANTY 

Warranty conditions are available on our website 

www.novusautomation.com/warranty

 