N1500FT Flow Indicator 

NOVUS AUTOMATION 

9/9 

SPECIFICATIONS 

DIMENSIONS

: ............................................ 48 x 96 x 92 mm (1/8 DIN) 

 ............................................................ Approximate Weight: 242 g 

PANEL CUTOUT

: .................................. 45.5 x 93 mm (+0.5 -0.0 mm) 

POWER SUPPLY

: ..................... 100 to 240 Vac/dc (±10 %), 50/60 Hz 

Optional 24 V: ...................  12 to 24 Vdc / 24 Vac (-10 % / +20 %) 

 Maximum Consumption: ....................................................  7.5 VA 

ENVIRONMENTAL CONDITIONS

Operation Temperature: ...............................................  5 to 50 

°

Relative Humidity: ...................................... 80 % max. up to 30 ºC 

For temperatures above 30 °C, reduce 3% by °C 

Internal use; Category of installation II, Degree of pollution 2; 

altitude < 2000 m 

INPUTS 
  4-20 mA

: ........................................ Accuracy: ± 0.2 % of full scale 

  Dry Contact

: ........................................... Frequency: 0.1 to 10 Hz 

  Pulse (Tension, NPN or PNP)

: ........ Frequency: 0.1 to 50000 Hz 

   ........................................................... Amplitude: from 4 V to 24 V 

   ........................................................ Accuracy: ± 30 ppm @ 25 °C 

  Magnetic Pickup

: ........... Frequency: 0.1 to 8000 Hz @ 30 mVpp 

   ........................................................ 0.1 to 50000 Hz @ 250 mVpp 

   ................................................ Amplitude: from 30 mVpp to 5 Vpp 

   ........................................................... Accuracy: ± 0.1 % @ 25 °C 

Input impedance

: .....................4-20 mA: 150 

Ω

 (+4.5 Vdc @ 20 mA) 

OUTPUTS

  4-20 mA

: ..............................................  550 

Ω max.

, 10000 levels 

   .........................................................................Isolation: 250 Vrms 

  Pulse

: .............................................. Maximum frequency: 100 Hz 

   ....................................................................... Voltage: 0 to 30 Vdc 

   ............................................................... Maximum current: 15 mA 

   .........................................................................Isolation: 250 Vrms 

OUTPUT RELAYS

  ALM1 and ALM2

: ..........................................................................  

 

 ................................ SPDT: 3 A / 240 Vac (3 A / 30 Vdc resisitive) 

  ALM3 and ALM4

: ..........................................................................  

 

 ....................... SPST-NA: 1.5 A / 250 Vac (3 A / 30 Vdc resisitive) 

ELECTROMAGNETIC COMPATIBILITY

: ...........................................  

 ........................................ EN 61326-1:1997 and EN 61326-1/A1:1998 

SAFETY

: .......................... EN61010-1:1993 and EN61010-1/A2:1995 

  Connections suitable for fork-type terminals 6.3 mm. 
  FRONTAL PANEL

:  ............................. IP65, polycarbonate UL94 V-2

 

  CASE

:  ........................................................... IP20, ABS+PC UL94 V-0

 

  Operation is started

: three seconds after connection to power 

supply.

 

IDENTIFICATION 

N1500FT - 

4R - 

485 - 

24V 

A

:  Indicator model: 

N1500FT

 

B

:  Output relays: 

Nothing shown

  (basic version with two SPDT relays); 

4R

        (version with two additional SPST relays); 

C

:  Digital Communication: 

Nothing shown 

(basic version with no serial communication); 

485

       (version with RS485 serial, Modbus protocol) 

D

:  Power Supply: 

Nothing shown 

(basic version, power supply of 100 to 240 Vac);

 

  24V

       (version with power supply of 12 to 24 Vdc /  

24 Vac). 

WARRANTY 

Warranty conditions are available on our website 

www.novusautomation.com/warranty

Содержание 81500FT020

Страница 1: ...ization will continue even if the input rate is below the minimum rate required Instantaneous flow rate indication will be zero whenever there is a time lapse of 10 seconds without input variation In...

Страница 2: ...utput frequency has hardware limitation See Specifications Check the Specifications ALARMS The indicator s basic version has 2 alarm outputs with the option of up to 4 alarms Whenever an alarm is on a...

Страница 3: ...feeder alarm will be activated If the process was stopped all counters will keep their values and the process will remain stopped until it is activated either by the key or the digital input MANUAL OP...

Страница 4: ...value being modified Press while holding Available only for some parameters Change a parameter Press or to select the next option or in the case of a numerical value to increase or decrease the value...

Страница 5: ...Table 5 Key f Key Function Selection of key function See Table 6 d 1n F Digital Input Function Selection of digital input function See Table 6 reset Reset Resets totalizer Bat rst Feeder Batch Reset...

Страница 6: ...f the 4 20 mA input is enabled The YES option applies quadratic function on the input signal within the limits programmed in inLL and inkL Table 7 Input setup cycle keys SELECTION OF FLOW INPUT TYPE S...

Страница 7: ...nt close to 20 mA will be applied Measure current in mA and enter it on this screen rstr Restore Restores factory calibration Pa x Password Change Changes user password Prot Protection Protection leve...

Страница 8: ...control and sends a response to the master The indicator takes broadcast type commands addresses to all network instruments For this type of command the indicator does not send any reply or acknowledg...

Страница 9: ...Isolation 250 Vrms Pulse Maximum frequency 100 Hz Voltage 0 to 30 Vdc Maximum current 15 mA Isolation 250 Vrms OUTPUT RELAYS ALM1 and ALM2 SPDT 3 A 240 Vac 3 A 30 Vdc resisitive ALM3 and ALM4 SPST NA...

Отзывы: