N1500FT Flow Indicator 

NOVUS AUTOMATION 

6/9 

For screens that show totalizations, whether it is the total or the 

non-resettable value, when the reading cannot be shown in six 

digits it will be shown in two halves; that is, the lower six digits and 

the higher five digits (preceded by a 

k.

 to indicate it is the high half) 

will be displayed in turns every five seconds. 
In case no alarm is configured as “feeder”, a  “

------

“ will be 

displayed. 

Table 6

 shows the options for digital input and the 

 key. 

Off

 

No function. 

Rst.tot

 

Totalization reset. 

k

old.1n

 

Freezes display while the input is active or the 

key is pressed. 

Rst.MM

 

Resets minimum and maximum values. 

feeder

 

Start of 

Feeder

 function. Further details in the 

Feeder

 section. 

IGnore 

Suspends totalization, ignoring input signal, 

but keeps retransmission working. 

Table 6

 - Options for digital input and the 

 key 

INPUT SETUP CYCLE 

1N.TYPE 

In

put 

Type

 

Selection of flow input type. See 

Table 8

1N.4-20 

In

put 

4

 to 

20

 mA

 

Selection of 4-20 mA input as auxiliary input. 

Available only if flow input is different than 4-20 

mA.   

1n

 

LL 

In

put 

L

ow 

L

imit

 

Value for the beginning of the auxiliary input 

range. Available only if the 4-20 mA input is 

enabled. 

1n

 

xL 

In

put 

H

igh 

L

imit

 

Value for the end of the auxiliary input range. 

Available only if the 4-20 mA input is enabled. 

(Ut0ff 

Cut Off

 

Minimum flow rate for indication. Any flow rate 

below this value is shown as 0 and will not 

increment the totalizer. 

FLTR.1n 

F

i

lt

e

r

 

In

put

 

4-20 mA input filter. Available only if the 4-20 

mA input is enabled. 

Un1t

 

Unit

 

I

nstantaneous

 

Unit for indicating instantaneous flow rate. It 

also establishes the time base for this 

measurement  in Seconds, Minutes, Hour or 

Days (free alphanumeric description):  

-----

s

 / 

m

 / 

h

 / 

D

 (Seconds / Minutes / Hour 

/ Days) 

Un1t

 

Unit

 

t

otalizer

 

Unit for totalized flow rate indication: “

------

” 

(free alphanumeric description). 

k.1nst 

K

 

Inst

antaneous

 

K factor to be applied on the flow rate reading 

through the digital input. 
Available only if flow input is different than 4-

20 mA. 
Instantaneous  K  factor has its value set as 

“pulses per volume”. 

k.tot 

K

 

tot

alizer

 

K factor to be applied on total volume. 
When using pulse input, total K factor has its 

value set as “pulses per volume”. 

S.root 

S

quare 

root

 

Square root. Available only if the 4-20 mA 

input is enabled. The “

YES

” option applies 

quadratic function on the input signal within 

the limits programmed in “

inLL

” and “

inkL

”.

 

Table 7

 – Input setup cycle keys 

SELECTION OF FLOW INPUT TYPE 

SENSOR

 

DESCRIPTION 

4

 to 

20 

4-20 mA analog signal 

d.1.nPn 

NPN or tension type digital input 

D1.PnP 

NPN digital input 

Sw1tch 

Dry Contact (reed switch) digital input 

pickvp 

Coil signal input (from 30 mVpp) 

Table 8

 – Input sensor type 

Note

: For information about reading speed, check Specifications. 

OUTPUT SETUP CYCLE 

rtll 

R

e

t

ransmition 

L

ow 

L

imit 

Retransmission lower limit. It is the flow rate 

value that corresponds to the 4-20 mA output 

lower limit. When 

rtkl

  is equal to 

rtll

output is turned off. 

rtxl 

R

e

t

ransmition 

H

igh 

L

imit 

Retransmission higher limit. It is the flow rate 

value that corresponds to the 4-20 mA output 

higher limit. 
When

  rtll

  is equal to 

rtkl

, output is 

turned off. 

0UT.err 

Out

put 

Err

or

 

Value to be applied to 4-20 mA output in case 

of input failure. 

PULSe 

Pulse

 

Configuration of pulse output. Options are off, 

volumetric pulse and frequency. 

w.pulse 

V

olume 

Pulse

 

Volume to be accumulated to generate an 

output pulse. Available only when pulse output 

is set to volumetric pulse. 

Pulse.t 

Pulse T

ime

 

Time period during which pulse remains active 

after having reached intended volume. 

Available only when pulse output is set to 

volumetric pulse. 

freqdw 

Freq

uence 

D

i

v

ider 

Input frequency divider. Available only when 

pulse input is set to frequency. 

Table 9

 – Output setup cycle keys 

When pulse output is set as volumetric pulse, a pulse is generated 

every time the totalizer accumulates the value programmed on the 

w.pulse

  screen. For example, if 

u.pulse

  is programmed to 10, 

then a pulse will be generated for every 10 units of computed 

volume. 
When pulse output is set to frequency, the output signal will be an 

input signal divider. 

RELAY CONFIGURATION CYCLE 

Rl 1 

Relay 1

 

Relay 1 function selection: 

off

Al 1

,

 

al 

2

al 3

 e 

al 4

Rl 2 

Relay 2

 

Relay 2 function selection: 

off

Al 1

,

 

al 

2

al 3

 e 

al 4

Rl 3 

Relay 3

 

Relay 3 function selection: 

off

Al 1

,

 

al 

2

al 3

 e 

al 4

Rl 4 

Relay 4

 

Relay 4 function selection: 

off

Al 1

,

 

al 

2

al 3

 e 

al 4

Table 10

 – Relay configuration cycle screens 

If there is need for activating more than one output relay by the same 

alarm,  just assign the desired relays to the desired alarm.  Default 

configuration assigns one relay to its related (same index) alarm 

(relay 1 for alarm 1, relay 2 for alarm 2, and so on). 

Содержание 81500FT020

Страница 1: ...ization will continue even if the input rate is below the minimum rate required Instantaneous flow rate indication will be zero whenever there is a time lapse of 10 seconds without input variation In...

Страница 2: ...utput frequency has hardware limitation See Specifications Check the Specifications ALARMS The indicator s basic version has 2 alarm outputs with the option of up to 4 alarms Whenever an alarm is on a...

Страница 3: ...feeder alarm will be activated If the process was stopped all counters will keep their values and the process will remain stopped until it is activated either by the key or the digital input MANUAL OP...

Страница 4: ...value being modified Press while holding Available only for some parameters Change a parameter Press or to select the next option or in the case of a numerical value to increase or decrease the value...

Страница 5: ...Table 5 Key f Key Function Selection of key function See Table 6 d 1n F Digital Input Function Selection of digital input function See Table 6 reset Reset Resets totalizer Bat rst Feeder Batch Reset...

Страница 6: ...f the 4 20 mA input is enabled The YES option applies quadratic function on the input signal within the limits programmed in inLL and inkL Table 7 Input setup cycle keys SELECTION OF FLOW INPUT TYPE S...

Страница 7: ...nt close to 20 mA will be applied Measure current in mA and enter it on this screen rstr Restore Restores factory calibration Pa x Password Change Changes user password Prot Protection Protection leve...

Страница 8: ...control and sends a response to the master The indicator takes broadcast type commands addresses to all network instruments For this type of command the indicator does not send any reply or acknowledg...

Страница 9: ...Isolation 250 Vrms Pulse Maximum frequency 100 Hz Voltage 0 to 30 Vdc Maximum current 15 mA Isolation 250 Vrms OUTPUT RELAYS ALM1 and ALM2 SPDT 3 A 240 Vac 3 A 30 Vdc resisitive ALM3 and ALM4 SPST NA...