N1500FT Indicator 

FLOW RATE INDICATOR – INSTRUCTIONS MANUAL – V1.2x E 

SAFETY ALERTS 

The symbols below are used on the equipment and throughout this 

document to draw the user’s attention to important operational and 

safety information. 

 

 

CAUTION: 

Read this manual carefully prior to 

installation and operation of the 

unit. 

CAUTION OR DANGER: 

Electric shock hazard 

All safety related instructions that appear in the manual must be 

observed to ensure personal safety and to prevent damage to either 

the instrument or the system.  If the device is used in a manner not 

specified in this manual, its safety features may be impaired. 

INTRODUCTION 

This flow rate indicator provides indication, totalization, 

retransmission, alarm and RS485 communication features (optional 

RTU Modbus slave).  It reads most flow signals available in the 

market, such as pulse, magnetic pickup and 4-20 mA.  The pulse 

input allows connecting sensors with outputs such as reed-switch, 

NPN, PNP and tension. Both for pulse input and 4-20 mA input, unit 

is selectable and a scale factor is set to turn the input signal into the 

unit of choice. It provides an isolated pulse output for totalized flow 

retransmission and a 4-20 mA output for immediate flow 

retransmission. Alarms are set off through 2 to 4 relays, depending 

on the equipment model.  
AC models provide a 24 Vdc / 50 mA output. 

INPUTS 

The flow rate indicator allows for two basic input types: 

 

Instantaneous flow input through a 4-20 mA signal. In this case, 

flow totalization is obtained by integrating instantaneous flow rate. 

 

Totalized flow input through a pulse signal. In this case, 

instantaneous flow rate is obtained by deriving totalized flow rate. 

Pulse signals may come from sensors/transmitters with NPN, PNP, dry 

contact (reed switch) and tension signal output, or even magnetic 

pickup outputs. 
When the input is set to 4-20 mA, you should establish on screens 

InLL

 and 

InKL

 which flow values are equivalent to 4-20 mA. 

When the 4-20 mA input is not used as flow input, it may be used 

alternatively as auxiliary input. This way it is possible to measure the 

pressure of a pipeline, for instance. 
The pulse flow input may be scaled, both for instantaneous and 

totalized flow rates (independently), through ‘K’ multiplication factors: 

k.1nst

 and 

k.tot

.

 

Both flow time base and unit must be defined on screen 

Un1t 1

To do so, there are six characters, the first five of which are used to 

set the unit and the last one (to the right) is used to set the time base 

on which the flow rate is measured. Available time bases are ‘s’ 

(seconds), ‘m’ (minutes), ‘h’ (hours) and ‘d’ (days). 

With pulse flow input, totalization will continue even if the input rate is 

below the minimum rate required. Instantaneous flow rate indication 

will be zero whenever there is a time lapse of 10 seconds without 

input variation. In this case, whenever there is a totalization increase 

(more input pulses), the instantaneous flow value will be shown for 

the nest 10 seconds. 

“K” FACTORS 

The instantaneous K factor (

k.1nst

) and the total K factor (

k.tot

allow the user to view the instantaneous and totalized flow in different 

units. 
The instantaneous K factor will be available only in case the selected 

flow input type is different from 4-20 mA. When the input type is 4-20 

mA, the configured range limits already provide the parameters for 

the indication. 
Instantaneous flow is directly related to the time base set in 

parameter 

Un1t1

In case user erroneously configures parameters 

k.1nSt

 and 

k.tot

 

with value “0” (zero), this will be assigned value “0.00001”. 
Example 1: 
Chosen  meter  gives us an information  of  (pulses per volume) 50 

pulses per liter. User wants to view the instantaneous flow in liters (l) 

and the totalized flow in cubic meters (m³). 
In order to do that, parameter 

k.1nst

 should be set a value of “50”, 

so indicating the instantaneous flow in liters. Parameter 

k.tot

 should 

be set a value of “50000”, so indicating the totalized flow in m³. 
Instantaneous flow will be viewed based on the selected time base in 

Un1t1

. In case the example meter output is 50 pulses per second, 

which means 1 liter/second,  and  the selected time  base  is  m 

(minute), the instantaneous flow indication will be 60 (liters/minute).

 

Example 2: 
Chosen sensor gives us an information in 4-20 mA that corresponds 

to a flow between 0 and 100 liters per minute. User wants to view the 

totalized flow in cubic meters (m³). 
On this case, parameter 

1N.TYPE

 

sholud  be  selected as  4-20 mA 

and  parameters 

InLL

 and 

InKL

 should be configured  as  “0”  and 

“100”. This way, we pass to the equipment the information that 4 mA 

relates to  0 liters per minute  and  20 mA relates to  100 liters per 

minute. In case sensor output is 12 mA, flow will be displayed as 50 

liters/minute. 
Parameter 

k.tot

 

should have a value of 0.001 (1 liter = 0.001 m³). 

This way, the totalized flow will be converted and displayed in m³ 

(cubic meters). 
When the instantaneous flow type is selected as 4-20 mA, the time 

base selected in 

Un1t1

 have no influence over the indicated values, 

having just unit display purposes.  The indication conversion from 

“liters per minute” to “liters per hour” should be adjusted directly on 

input limits 

InLL

 and 

InKL

In case user wanted instantaneous flow indicated in cubic meters per 

hour (m³/h) with the same meter, the values “0” and “6” should have 

been selected in input limits 

InLL

  and 

InKL

,  where the second 

value means 100 l/min converted to m³/h. 

k.tot

 

parameter should 

be changed to “1” because input is already in m³. 

Содержание 81500FT020

Страница 1: ...ization will continue even if the input rate is below the minimum rate required Instantaneous flow rate indication will be zero whenever there is a time lapse of 10 seconds without input variation In...

Страница 2: ...utput frequency has hardware limitation See Specifications Check the Specifications ALARMS The indicator s basic version has 2 alarm outputs with the option of up to 4 alarms Whenever an alarm is on a...

Страница 3: ...feeder alarm will be activated If the process was stopped all counters will keep their values and the process will remain stopped until it is activated either by the key or the digital input MANUAL OP...

Страница 4: ...value being modified Press while holding Available only for some parameters Change a parameter Press or to select the next option or in the case of a numerical value to increase or decrease the value...

Страница 5: ...Table 5 Key f Key Function Selection of key function See Table 6 d 1n F Digital Input Function Selection of digital input function See Table 6 reset Reset Resets totalizer Bat rst Feeder Batch Reset...

Страница 6: ...f the 4 20 mA input is enabled The YES option applies quadratic function on the input signal within the limits programmed in inLL and inkL Table 7 Input setup cycle keys SELECTION OF FLOW INPUT TYPE S...

Страница 7: ...nt close to 20 mA will be applied Measure current in mA and enter it on this screen rstr Restore Restores factory calibration Pa x Password Change Changes user password Prot Protection Protection leve...

Страница 8: ...control and sends a response to the master The indicator takes broadcast type commands addresses to all network instruments For this type of command the indicator does not send any reply or acknowledg...

Страница 9: ...Isolation 250 Vrms Pulse Maximum frequency 100 Hz Voltage 0 to 30 Vdc Maximum current 15 mA Isolation 250 Vrms OUTPUT RELAYS ALM1 and ALM2 SPDT 3 A 240 Vac 3 A 30 Vdc resisitive ALM3 and ALM4 SPST NA...