In dismounting and disassembling the fan 
be careful not to expose the individual 
parts to shocks etc. likely to damage the 
motor bearings or other fan components.

6.6 Mounting of motor

After servicing remount the motor; see that 
the motor flange (fig.8, item 02) is correctly 
located and that the motor shaft is 
concentrically placed in the fan casing 
before tightening the bolts (item 06).

Mount the impeller (item 07) on the motor 
shaft by means of a tool fastened in the 
threaded hole of the motor shaft. Fix the 
impeller hub to rest against the motor shaft 
collar. Check that the blade clearan-

ce is the same throughout the 
circumference of the casing. If this is not the 
case, adjust the motor location in the 
suspension arrangement.

Now mount the centre screw (item 09) and 
centre disc (item 08). Replace lock washers 
and lock nuts during fan assembly. Finally, 
connect the motor cable in the terminal box 
(item 01) and any ducts and downstream 
guide vane arrangement (item 13). 

To start the fan follow the procedure 
described in section 5 (Start of operation).

6.7 Blade pitch adjustment

The blade pitch has been adjusted in the 
factory with a special tool (fixture) to 
deliver the performance required by the 
customer/order on delivery.

If the fan performance is required to be 
changed it is possible to change the blade 
pitch. It requires knowledge of the motor 
load and the max. permissible blade pitch 
on the graph as related to the motor rating 
(in case of blade pitch increase).

Contact Novenco before any such 
adjustment of the blade pitch.

Novenco can supply special tools for blade 
pitch adjustment and instructions for 
impeller balancing.

The brochure "Blade-angle tool" is 
available on request.

6.8 Fault localization

These are likely causes of breakdowns/
failures:

Deficiency in performance:

Blocked air supply to the fan inlet side:
–  Damper closed
–  Duct choked
–  Supply fan, if any, stopped

–   Motor  defective
–   Motor  cut  out
–  Wrong direction of rotation of impeller.

Noise/vibrations:
–  Bearings in electric motor defective
–  Impeller out of balance
–  Impeller worn/damaged
–  Bolts/components loose
–  Impeller blades have different pitch 

angles

–  Fan operates in the stalling area. May 

result in break-down - repair failures, 
see "Deficiency in performance".

7. Sound

The sound generation of the fans depends 
on installation and operating conditions, 
which means that no general data of the 
sound generation can be given.

Reference is made to our catalogues or 
computer programs for calculation of the 
specific sound generation.

8. Attestation of 

conformity

EU - Attestation of Conformity

Novenco A/S
Industrivej 22
DK-4700 Naestved

Hereby declares that axial flow fans types 
ACP 250-1600 and ACG 250-1600 have 
been manufactured in conformity with the 
Council's directive 2006/42/EC regarding 
mutual approximation of the machinery 
laws (the Machinery Directive) of the 
member states.

Directives
– EC Machinery Directive 2006/42/EC
– EMC Directive 2004/108/EC
– Low Voltage Directive 2006/42/EC

Applied standards

EN ISO 12100-1:Safety of machinery part 1
EN ISO 12100-2:Safety of machinery part 2
EN ISO 13857: Safety of machinery -

Safety distances

EN 60204-1: Safety of machinery -

Electrical equipment of
machines Part 1 : 
General Requirements

It is a condition that Novenco's instructions 
for installation have been followed.

Naestved, 1. 11. 2010

Steen Hansen
R&D manager
Novenco A/S

Содержание Novax ACP Series

Страница 1: ... Axial flow fans types ACP and ACG are supplied on pallets or bearers to allow fork lift transport Fig 2 Total weight for type ACG fans incl of motor Fan size Motor size 71 80 90 100 112 132 160 180 200 225 250 280 Hub diameters 160 230 280 330 and 380 ACG 250 19 3 22 8 ACG 315 22 3 25 8 31 8 ACG 400 32 5 38 42 49 5 ACG 500 39 5 50 56 63 5 67 88 ACG 560 47 5 62 68 75 5 79 100 139 ACG 630 52 5 67 7...

Страница 2: ...unt the fan casing in the two flange holesofthemountingplatesandmountthe distance bush fig 5 item 07 by means of joining elements items 08 and 09 between inlet cone and mounting plate item 06 The fan houses for ACP and ACG sizes 1250 1600 have circular fan casings Therefore the fan casing is mounted with fittings for mounting foot fig 6 item 07A and joining elements fig 6 items 08A and 09A Mount t...

Страница 3: ...gue break in the impeller and endanger people Operation in stall area Operation with pulsating counter pressure called pump mode Operation with repeated starting and stopping If in doubt Novenco should be contacted to assess the suitability of the fan 6 Maintenance 6 1 Protection prior to inspection and maintenance Whenthefanis outof operationforreasons of inspection or repair maintenance the elec...

Страница 4: ... adjustment of the blade pitch Novenco can supply special tools for blade pitch adjustment and instructions for impeller balancing The brochure Blade angle tool is available on request 6 8 Fault localization These are likely causes of breakdowns failures Deficiency in performance Blocked air supply to the fan inlet side Damper closed Duct choked Supply fan if any stopped Motor defective Motor cut ...

Отзывы: