4.6 Wiring

Connection to the mains is effected direct in 
the motor terminal box.

Connect 3-phase motors as shown on the 
diagrams in the terminal box lid.

Regarding 1-phase motors see diagrams 
for 1-phase adjustable motors.

Having wired the motor terminal box, 
check that the direction of rotation of the 
impeller complies with the arrow-plate 
fitted on the outside of the fan.

For reversible fans (alternating directions 
of rotation) a time delay arrangement must 
be provided to ensure that the impeller is 
stationary before restarting.

Important:

Only fans with steel hubs 
may be run in reverse. 
Reversible operation 
increases risk of fan 
stalling. If the fan stalls, the 
service life is shortened.

5. Start of operation

5.1 Prior to start of operation

Prior to start of operation check that the fan 
and duct connections are clean and free 
from tools and foreign substances.

Also ensure that the electric connections 
meet the prescribed requirements, that any 
wire guard fitted on the fan inlet or outlet 
side is correctly mounted and that the 
direction of rotation of the fan complies 
with the arrow-plate (check by short-time 
operation).

See fig. 7 items 01 and 02.

5.2 Motors with Y/

Δ

 starting

The relay must be set to the calculated time.

5.3 Starting procedure

• Start the fan.
• Check that no abnormal noises occur.
• See that the vibration level is normal. 

The vibration level at the fan 

operating speed must not exceed 7 
mm/s, rms*, measured radially at 
two points, 90° offset and at the free 
shaft end of the motor. Otherwise, the 
fan must be balanced.

Operation at a vibration level exceeding 11 
mm/s, rms*, is not allowed in case of fixed 
fan position.

Operation at a vibration level exceeding 18 
mm/s, rms*, is not allowed in case of 
position on feet or anti-vibration 
mountings.
* ISO 2954, Requirements for instruments 
for measuring vibration severity.

After thirty minutes of operation check that 
the fan operates normally.

Important:

The fan is designed for 
continuous operation. The 
following kinds of 
operation may cause 
fatigue break in the 
impeller and endanger 
people.
- Operation in stall area
- Operation with pulsating 
counter pressure - called 
pump mode
- Operation with repeated 
starting and stopping
If in doubt Novenco should 
be contacted to assess the 
suitability of the fan.

6. Maintenance

6.1 Protection prior to 

inspection and maintenance

When the fan is out of operation for reasons 
of inspection or repair/maintenance, the 
electric system must be switched off and 
protected so that the fan is not cut in 
unintentionally.

6.2 Fan casing

The fan casing requires as standard no 

maintenance other than ordinary cleaning.

If the fan casing is painted, the painted 
surface should be checked regularly and 
repaired where necessary.

6.3 Impeller

The impeller (rotor unit) is supplied from 
the factory with the blades adjusted to the 
pitch corresponding to the desired 
operating point (pressure and air flow) at 
the fan speed in question. To ensure 
vibration-free operation the impeller has 
been carefully balanced in this position.

Vibrations occurring during operation will 
normally be due to accumulations of dust 
or dirt on hub and blades, and will 
disappear after cleaning. Should this not be 
the case, expert assistance should be called 
in immediately, as continued vibrations 
will shorten the life of the blades and the 
motor bearings.

6.4 Motor

The motor normally only requires 
maintenance of the bearings as indicated in 
the maintenance instructions for electric 
motors.

6.5 Dismounting of motor

Prior to commencing the work, switch off 
the current and disconnect the motor cable. 
Next, dismount any ducts and 
downstream guide vane arrangement (fig. 
8 items 13, 10, 11, and 14) on the fan outlet 
side.

Remove the impeller centre screw (item 09) 
and centre disc (item 08).

Dismount the impeller by means of a puller 
fastened in the two threaded holes of the 
hub boss (item 12).

Detach the motor by loosening the screws 
in the motor shell (items 05 and 06). Now 
the motor (item 01) and motor flange (item 
02) can be removed.

Fig. 7. Novax Type ACG

Fig. 8. Dismounting/mounting of types ACG and ACP

1. Motor
2. Motor flange
3. Wire guard
4. Motor shell
5. S-washer
6. Set screw
7. Impeller
8. Centre disc
9. Centre screw
10. Set screw
11. Washer
12. Hub
13. Outlet guide vanes
14. Nut

Содержание Novax ACP Series

Страница 1: ... Axial flow fans types ACP and ACG are supplied on pallets or bearers to allow fork lift transport Fig 2 Total weight for type ACG fans incl of motor Fan size Motor size 71 80 90 100 112 132 160 180 200 225 250 280 Hub diameters 160 230 280 330 and 380 ACG 250 19 3 22 8 ACG 315 22 3 25 8 31 8 ACG 400 32 5 38 42 49 5 ACG 500 39 5 50 56 63 5 67 88 ACG 560 47 5 62 68 75 5 79 100 139 ACG 630 52 5 67 7...

Страница 2: ...unt the fan casing in the two flange holesofthemountingplatesandmountthe distance bush fig 5 item 07 by means of joining elements items 08 and 09 between inlet cone and mounting plate item 06 The fan houses for ACP and ACG sizes 1250 1600 have circular fan casings Therefore the fan casing is mounted with fittings for mounting foot fig 6 item 07A and joining elements fig 6 items 08A and 09A Mount t...

Страница 3: ...gue break in the impeller and endanger people Operation in stall area Operation with pulsating counter pressure called pump mode Operation with repeated starting and stopping If in doubt Novenco should be contacted to assess the suitability of the fan 6 Maintenance 6 1 Protection prior to inspection and maintenance Whenthefanis outof operationforreasons of inspection or repair maintenance the elec...

Страница 4: ... adjustment of the blade pitch Novenco can supply special tools for blade pitch adjustment and instructions for impeller balancing The brochure Blade angle tool is available on request 6 8 Fault localization These are likely causes of breakdowns failures Deficiency in performance Blocked air supply to the fan inlet side Damper closed Duct choked Supply fan if any stopped Motor defective Motor cut ...

Отзывы: