will disappear after cleaning. Should this 
not be the case, technical assistance should 
be called in immediately as continued 
vibration will shorten the service life of the 
blades and motor bearings.

6.4 Motor

Normally, only the motor bearings require 
maintenance. This should be performed as 
described in the maintenance instructions 
for electric motors.

6.5 Detaching the motor

Before detaching the motor, disconnect the 
power supply and motor cable. Next, 
detach any ducts and outlet guide vane (fig. 
8 pos. 13, 10, 11, and 14) on the fan outlet 
side.

Remove the impeller centre screw (pos. 09) 
and centre disc (pos. 08).

Detach the impeller using a puller secured 
in the two threaded puller holes in the hub 
boss (pos. 12). 

Loosen the screws in the motor shell (pos. 
05 and 06). The motor (pos. 01) and motor 
flange (pos. 02) can then be detached.

When dismantling the fan, be careful not to 
expose individual parts to impacts or other 
forces that might damage the motor 
bearings or fan parts.

6.6 Fitting the motor

After servicing is complete the motor must 
be refitted. Check that the motor flange (fig. 
8 pos. 02) is correctly positioned and that 
the motor shaft is concentrically positioned 
in the fan housing before tightening the 
bolts (pos. 06).

Refit the impeller (pos. 07) on the motor 
shaft by means of a puller secured in the 
threaded hole on the motor shaft. Tighten 
the impeller hub against the motor shaft 
collar. Check that blade clearance is equal 
around the entire circumference of the 
housing. If this is not the case, adjust the 
motor position in the suspension system.

Now fit the centre screw (pos. 09) and centre 
disc (pos. 08). It is recommended that lock 
washers and lock nuts be replaced when 
reassembling the fan. Finally, connect the 
motor cable in the terminal box (pos. 01) 
and any ducts and outlet guide vane (pos. 
13). 

To restart the fan, follow the procedure 
described in section 5: Start-up.

6.7 Blade pitch adjustment

The blade pitch is factory adjusted using a 
special tool (fixture) to provide the output 
required by the customer/order on 
delivery.

If a different output is required, it is possible 
to alter blade pitch. This requires 

knowledge of the motor load and the max. 
permissible blade pitch in relation to the 
motor rating (in case of blade pitch 
increase).

Please contact Novenco before any such 
adjustment of blade pitch. Special tools for 
blade pitch adjustment and instructions for 
impeller balancing are available from 
Novenco.

A brochure describing the blade pitch tool 
and its use is available on request.

6.8 Fault finding

Possible operating faults are described in 
the following.

Insufficient output:

Blocked air supply on the inlet side:

• Damper closed
• Duct  blocked
• Supply fan, if any, stopped
• Motor  defective
• Motor cut out
• Incorrect direction of impeller rotation 

Noise/vibration:

• Bearings in electric motor defective
• Impeller out of balance
• Impeller worn/damaged
• Bolts/components loose
• Impeller blades have different pitch
• Fan operating in "stall" mode – this 

may damage the system and should be 
remedied immediately, see 
"Insufficient output".

7. Testing functionality 

and operational 
readiness

To maintain their fire approval, ACP and 
ACG Smoke fans must be tested every three 
months with respect to functionality and 
operational readiness.

If ACP and ACG Smoke fans are also used 
for ventilation purposes, such tests need 
only be performed at six-month intervals 
provided the fan is started at least once a 
day by means of a time switch or carbon 
monoxide sensor. 

7.1 Periodic inspection

Novax fume fans must always be 
maintained in proper operating condition. 
To ensure satisfactory operation and long 
service life, the fans should be inspected 
every six months. 

Such inspection should include the 
following: 

• Measurement of power consumption
• Measurement of fan housing vibration
• Control of fixation bolt torque and, if 

necessary, readjustment

• Visual inspection of impeller, housing 

and wiring

• Cleaning:

– Use compressed air to clean the 

inside

– Use water to clean the outside

It is recommended that a log be kept of all 
values and observations. 

8. Sound

The sound generated by the fans depends 
on installation and operating conditions, 
and general data on sound generation is 
therefore unavailable.

For further details, please refer to our 
catalogue material or computer programs 
designed to calculate specific sound 
emissions.

9. EU declaration of 

conformity

Novenco A/S
Industrivej 22
DK-4700 Naestved

hereby declares that ACP Smoke 400-1600 
and ACG Smoke 400-1600 axial flow fans 
have been manufactured in conformity 
with Council Directive 2006/42/EC on the 
approximation of the laws of the member 
states relating to machinery (the Machinery 
Directive).

Directives
– EC Machinery Directive 2006/42/EC
– EMC Directive 2004/108/EC)
– Low Voltage Directive 2006/95/EC

Applied standards
EN ISO 12100-1: Safety of machinery -

Part 1

EN 12100-2:

Safety of machinery -
Part 2

EN 13857:

Safety of machinery -
Safety distances

EN 12101-3:

Smoke and heat control
systems - Part 3, class 1

EN 60204-1:

Safety of machinery -
Electrical equipment of
machines - Part 1:
General Requirements

It is a condition that Novenco installation 
instructions have been followed.

Naestved, 1.11.2010

Steen Hansen
R&D manager
Novenco A/S

Содержание ACP Series

Страница 1: ... ACP ACG Smoke ACP ACG SMOKE INSTALLATION AND MAINTENANCE 918816 0 English ...

Страница 2: ...rnumber Thenameplatealso states maximum temperature and operating time If the fan has an approval number the nameplate states class category and the applicable test standard EN 12101 3 Finally the nameplate states Fan size Motor size 90 100 112 132 160 180 200 225 250 280 Hub diameter 160 230 280 330 and 380 400 46 56 500 60 70 78 93 560 72 82 90 105 182 630 77 87 95 110 187 219 710 85 95 103 118 ...

Страница 3: ... Fansmustalwaysbeinstalledinsuchaway as to prevent contact with rotating parts Free inlets and outlets must be guarded by protective grilles If ducts are connected these must be provided with protective grilles on the side of the building The fan is provided with an arrow plate denoting the direction of air flow through thefanhousing Duringinstallation ensure that the fan is oriented so as to prov...

Страница 4: ...rrectly fitted and that the direction of rotation of the impeller complies with the arrow plate check by briefly starting the fan See fig 7 pos 01 and 02 5 2 Motors with Y Δ start The relay must be set to the calculated time 5 3 Start up procedure Start the fan Check that no abnormal sound occurs Check that the vibration level is normal At operating speed fan vibration must not exceed 7 mm s rms m...

Страница 5: ...re describing the blade pitch tool and its use is available on request 6 8 Fault finding Possible operating faults are described in the following Insufficient output Blocked air supply on the inlet side Damper closed Duct blocked Supply fan if any stopped Motor defective Motor cut out Incorrect direction of impeller rotation Noise vibration Bearings in electric motor defective Impeller out of bala...

Страница 6: ... WWW NOVENCO BUILDING COM ACP ACG Smoke ...

Отзывы: