performance and sound level of the axial 
flow fan that the air flow is unimpeded and 
free of eddies.

4.5 Duct connection

Novax ACG Smoke axial flow fans are 
equipped with an outlet guide vane 
assembly with core. This improves fan 
efficiency and allows duct connection.

The duct on the outlet side of the fan must 
be designed to ensure a smooth flow of air 
without turbulence. Avoid, for instance, 
sharp bends or flexible connectors in the 
ducting immediately behind the fan.

ACP and ACG Smoke fans are prepared for 
circular duct connections on the outlet side.

Flanges supplied as standard comply with 
EUROVENT 1/2.

Systems with higher vibration levels or 
more exacting performance requirements 
must be provided with expansion joints 
between the fan and duct, and the duct 
must not be supported by the fan.

It is important to provide sufficient free 
space for assembling and dismantling the 
system and to facilitate cleaning and 
maintenance.

4.6 Wiring 

Important:

Do not mount a frequency 

converter on a fan intended 
for smoke exhaust. The 
electric installation must be 
designed to bypass the 
frequency converter and run 
the fan at nominal speed in 
the event of fire.

Electrical connections must be made by an 
authorised electrician in accordance with 
current legislation. Power is connected via 
the motor terminal box as shown in the 
wiring diagrams in the terminal box cover.

Three-phase motors are connected as 
shown in the wiring diagrams in the 
terminal box cover.

For the connection of single-phase motors, 
see wiring diagrams for single-phase 
variable motors.

Having wired the motor terminal box, 
check that the direction of rotation of the 
impeller complies with the arrow plate 
fitted on the outside of the fan.

For reversible fans (alternating direction of 
rotation) a time delay must be provided to 
ensure that the impeller is stationary before 
restarting.

5. Start-up

5.1 Before start-up

Before start-up, check that the fan and duct 
connections are clean and free of tools and 
other foreign matter.

Also ensure that the electrical connections 
fulfil applicable requirements, that any 
protective grilles on the fan inlet or outlet 
sides are correctly fitted, and that the 
direction of rotation of the impeller 
complies with the arrow plate (check by 
briefly starting the fan).

See fig. 7 pos. 01 and 02.

5.2 Motors with Y/

Δ

 start

The relay must be set to the calculated time.

5.3 Start-up procedure

• Start the fan.
• Check that no abnormal sound occurs.
• Check that the vibration level is 

normal. At operating speed, fan 
vibration must not exceed 7 mm/s 
rms* measured radially at two points 
with 90° offset and at the free shaft end 
of the motor. Otherwise, the fan must 
be rebalanced.

When fixed in position, the fan must not be 
operated if vibration levels exceed 11 mm/
s rms*.
When freely suspended or mounted on 
vibration dampers, the fan must not be 
operated if vibration levels exceed 18 mm/
s rms*. 

* ISO 2954: Mechanical vibration of rotating 
and reciprocating machinery – 
Requirements for instruments for 
measuring vibration severity.

After thirty minutes of operation, check 
that the fan operates normally.

Important:

The fan is designed for 

continuous operation. The 
following kinds of operation 
may cause fatigue break in 
the impeller and endanger 
people.
- Operation with pulsating 
counter pressure - called 
pump mode
- Operation with repeated 
starting and stopping
If in doubt Novenco should 
be contacted to assess the 
suitability of the fan.

6. Maintenance

6.1 Safeguards prior to 

inspection and maintenance

Before inspecting or servicing the fan, it 
must be switched off and disconnected 
from the electrical system. Also ensure that 
the fan cannot be restarted unintentionally. 

6.2 Fan housing

As standard, the fan housing requires no 
maintenance other than cleaning.

If the housing is painted, the surface should 
be checked regularly and repaired where 
necessary.

6.3 Impeller

The impeller (rotor unit) is supplied with 
the blades factory adjusted to the pitch 
corresponding to the desired operating 
point (pressure and air flow) at the fan 
speed in question. To ensure vibration-free 
operation the impeller has been carefully 
balanced in this position.

Vibration occurring during operation is 
usually the result of dust or dirt 
accumulating on the hub and blades, and 

Fig. 7. Novax ACG Smoke

Fig. 8. Dismantling/assembling types ACG and ACP Smoke

1. Motor
2. Motor flange
3. Wire guard
4. Motor shell
5. S-washer
6. Set screw
7. Impeller
8. Centre disc
9. Centre screw
10. Set screw
11. Washer
12. Hub
13. Outlet guide vanes
14. Nut

Содержание ACP Series

Страница 1: ... ACP ACG Smoke ACP ACG SMOKE INSTALLATION AND MAINTENANCE 918816 0 English ...

Страница 2: ...rnumber Thenameplatealso states maximum temperature and operating time If the fan has an approval number the nameplate states class category and the applicable test standard EN 12101 3 Finally the nameplate states Fan size Motor size 90 100 112 132 160 180 200 225 250 280 Hub diameter 160 230 280 330 and 380 400 46 56 500 60 70 78 93 560 72 82 90 105 182 630 77 87 95 110 187 219 710 85 95 103 118 ...

Страница 3: ... Fansmustalwaysbeinstalledinsuchaway as to prevent contact with rotating parts Free inlets and outlets must be guarded by protective grilles If ducts are connected these must be provided with protective grilles on the side of the building The fan is provided with an arrow plate denoting the direction of air flow through thefanhousing Duringinstallation ensure that the fan is oriented so as to prov...

Страница 4: ...rrectly fitted and that the direction of rotation of the impeller complies with the arrow plate check by briefly starting the fan See fig 7 pos 01 and 02 5 2 Motors with Y Δ start The relay must be set to the calculated time 5 3 Start up procedure Start the fan Check that no abnormal sound occurs Check that the vibration level is normal At operating speed fan vibration must not exceed 7 mm s rms m...

Страница 5: ...re describing the blade pitch tool and its use is available on request 6 8 Fault finding Possible operating faults are described in the following Insufficient output Blocked air supply on the inlet side Damper closed Duct blocked Supply fan if any stopped Motor defective Motor cut out Incorrect direction of impeller rotation Noise vibration Bearings in electric motor defective Impeller out of bala...

Страница 6: ... WWW NOVENCO BUILDING COM ACP ACG Smoke ...

Отзывы: