~ 5 ~
PEF-
321АВР
NOVATEK-ELECTRO
The controls
and indication
:
1
– green LED «
L1
» lights if normal voltage is in phase
1 at
input 1
;
2
– green LED «
L2
» lights if normal voltage is in phase
2 at
input 1
;
3
– green LED «
L3
» lights if normal voltage is in phase
3 at
input 1
;
4
– blue LED «
I
» lights if the load has power supply
from
input 1
;
5
– red LED «
» lights if there is at least one failure at
input 1
;
6
– red LED «
» lights if there is at least one failure at
input 2
;
7
– blue LED «
II
» lights if the load has power supply
from
input 2
;
8
– green LED «
L1
» lights if normal voltage is in phase
1 at
input 2
;
9
– green LED «
L2
» lights if normal voltage is in
phase 2 at
input 2
;
10
– green LED «
L3
» lights if the normal voltage is in
phase 3 at
input 2
;
11
– connector for USB communication;
12
– blue LED «
» blinks when transmitting data via
USB or RS-485, it does not light up if data transfer
is not used;
13
–
input 2
displays phase and line voltage values,
input 2
network frequency and menu values;
14
– button « »;
15
– button «OK»;
16
– button « »;
17
– display of
input 1
displays phase and line voltage
values,
input 1
network frequency and menu.
18
– green LED «
» lights if the generator is
connected to the load; blinks if time is running. It is
off when operating from the mains.
Functions of 321ABP terminals
:
1
–
input 1
control (normally open contact);
25
– RS-485-G;
2
–
input 1
control (common contact);
26
– the first phase of
input 1
to power the device;
3
–
input
1 control 1 (normally closed contact);
27
– the second phase of
input 1
to power the device;
4
–
input 2
control (normally open contact);
28
– the third phase of
input 1
to power the device;
5
–
input 2
control (common contact);
6
–
input 2
control (normally closed contact);
29
– neutral wire of
input 1
to power the product;
30
– the first phase of
input 2
to power the device or connect the
generator;
7,8,9,10,11
– not involved;
31
– the second phase of
input 2
to power the device or connect
the generator;
12,13
– the state of voltage at input 1;
32
– the third phase of
input 2
to power the device or connect
the generator;
14,15
– the state of voltage at input 2;
33
– neutral wire of
input 2
to power the device or connect the
generator;
16,17
– the state of voltage on both inputs;
34
– the first phase of voltage measurement at the load;
18,19
– the state of generator operation;
35
– the second phase of voltage measurement at the load;
20
– generator control (normally open contact);
36
– the third phase of voltage measurement at the load;
21
– generator control (common contact);
37
– not involved;
22
– generator control (normally closed contact);
38
– external button to turn on the device from the battery;
23
– RS-485-A;
39
– “+” of power supply from the 12-V battery;
24
– RS-485-B;
40
– “-” of power supply from the 12-V battery.
4 OPERATION CONDITIONS
The product is designed for operation in the following conditions:
–
Ambient temperature: from minus 35 to
+55°C;
–
Atmospheric pressure: from 84 to 106.7 kPa;
–
Relative air humidity
(at temperature of +25°C): 30 … 80%.
If the temperature of the device after transportation or storage differs from the ambient temperature at which it
is supposed to be operated, then before connecting to the mains keep the device under the operating conditions
within two hours (because of condensation may be on the device elements).
ATTENTION! The product is not intended for operation in the following conditions
:
–
Significant vibration and shocks;
–
High humidity;
–
Aggressive environment with content in the air of acids, alkalis, etc., as well as severe
contaminations (grease, oil, dust, etc.).
5 CONTENTS OF DELIVERY
The contents of delivery is shown in Table 4.
Table 4
- The contents of product delivery
Description
Quantity, pcs
321АВР
1
Coupling cable to connect a PC via USB
1
Operation Manual
1
Packing
1