This  Operation  Manual  is  intended  to  let  you  know  about  the  device,  safety  requirements,  operation  and 

maintenance  procedures  for  the  Control  unit  for  automatic  transfer  switch  PEF-321

АВР  ((hereinafter  in  the  text 

321ABP; device).  

 

1 DESIGNATION 

The  device  is  designed  to  operate  as  a  part  of  control  cabinets  for  automatically  turning  on  backup  power  in 

uninterruptible power supply systems. 

321ABP controls automatic transfer from the main three-phase power source to the backup one and vice versa 

in  case  of  unacceptable  voltage  deviations  in  phases,  asymmetry  or  phase  imbalance,  changing  the  phase 
sequence, breaking one or more phases in the "main" or "standby" networks. 

The device can be used in power supply networks as a part of devices: 
- automatic switching on a standby source (ABP); 
- automatic start of a three-phase electric generator. 
Device 321АВР controls voltage at two inputs of three-phase four-wire networks 230 / 400V with a grounded or 

insulated neutral wire. 

 

2 TECHNICAL SPECIFICATIONS 

The  general  data  of  321ABP  are  shown  in  Table  1.  The  main  technical  characteristics  of  321ABP  are  shown  in 
Table 2. Output contact specifications are shown in Table 3. 

 

Table 1 -

 General  

 

Description 

Value 

Designation of the device 

Control and distribution equipment 

Rated operating mode 

Long lasting 

Product protection 

IP20 

Electrical shock protection class 

II 

Climatic version 

NF 3.1 

Permissible pollution 

II 

Overvoltage category 

III 

Rated insulation voltage, V 

450 

Rated impulse withstand voltage, kV 

4.0 

Wire cross section for connecting to terminals, mm

2

 

0.5 

– 2 

Tightening torque of terminal screws, N * m 

0.4 

 

Table 2

 

– Main technical specifications 

 

Description 

Value 

Rated AC three-phase supply voltage, V 

380 

– 400 

Type of lines controlled 

Two three-phase 

four-wire inputs 

Mains frequency, Hz 

48 

– 62 

Voltage hysteresis, V 

Number of three-phase controlled inputs 

Voltage at which operability is maintained: 

-

 

phase voltage with supply from one phase and connected neutral wire, V, not less 

-

 

linear voltage with supply from three phases, V, not more 

 

100 
450 

Cutoff thresholds for 

Input 1

Input 2

, acc. to Umax, V 

Table 5 

Cutoff thresholds for 

Input 1

Input 2

, acc. to Umin, V 

Contactor sticking control 

yes 

Switching wear resistance, thousand times 

30 

Inputs: 
- analog inputs for measuring three-phase voltage at the inputs, pcs. 
- analog inputs for measuring three-phase voltage at the load, pcs. 
- analog input for connecting 12 V DC, pcs. 

 



Outputs: 
- discrete output for connecting the control winding of a three-phase load contactor, pcs. 
- discrete output of voltage state at the inputs, pcs. 
- discrete output of voltage presence  at least at one phase of any input, pcs. 
- discrete output for connecting indication of generator work, pcs. 
- discrete output of generator control, pcs. 
- digital input/output for connecting via  RS-485 protocol, pcs. 
- digital input/output for connecting via USB, pcs. 

 







Time delay for voltage distortion, s 

Table 5 

Time delay of response to phase sequence failure, s 

Table 5 

Time delay of response to phase failure alarm, s 

Table 5 

Содержание PEF-321ABP

Страница 1: ...m on the development and production complies with requirements ISO 9001 2015 Dear customer Company NOVATEK ELECTRO LTD thanks you for purchasing our products You will be able to use properly the produ...

Страница 2: ...AL ELEMENTS OF THE PRODUCT During operation and maintenance the regulatory document requirements must be met namely Regulations for Operation of Consumer Electrical Installations Safety Rules for Oper...

Страница 3: ...vervoltage category III Rated insulation voltage V 450 Rated impulse withstand voltage kV 4 0 Wire cross section for connecting to terminals mm2 0 5 2 Tightening torque of terminal screws N m 0 4 Tabl...

Страница 4: ...frame self extinguishing plastic No harmful substances in amount that exceeds permissible exposure limits Table 3 Characteristics of output contacts Used terminals Max current at U 250 V A Number of...

Страница 5: ...to power the device or connect the generator 7 8 9 10 11 not involved 31 the second phase of input 2 to power the device or connect the generator 12 13 the state of voltage at input 1 32 the third pha...

Страница 6: ...ECTIONS MUST BE PERFORMED WITH THE DEVICE BEING DEENERGIZED An error in installation work may result in damage of the device and instruments connected to it To ensure reliability of electrical connect...

Страница 7: ...f operation 321 supports 6 operating modes two equivalent three phase inputs two three phase inputs with priority input 1 two three phase inputs with priority input 2 three phase input 1 and a three p...

Страница 8: ...input 1 by contactor K1 and counts the transition time to the secondary input table 5 3 After completion of the 321 time countdown device 321 closes terminals 20 21 sends a signal to start the generat...

Страница 9: ...d configure other menu items In order to exit the menu press and hold the OK button for 3 s If no button is pressed within 30 s the menu will exit automatically Table 5 Menu Menu Value Name Descriptio...

Страница 10: ...SCII 1 RTU MODBUS modes 134 Parity check parity check is off even parity check odd parity check 135 Number of stop bits or 136 Transfer rate transfer rate 2400 baud transfer rate 4800 baud transfer ra...

Страница 11: ...d order dot is lighting 13 14 Phase voltage of phase 3 Low order dot is lighting 15 16 Linear voltage of phases 1 2 High order dot is flashing 17 18 Linear voltage of phases 2 3 Mid order dot is flash...

Страница 12: ...s not lighting no voltage 400 AC 16 17 Optotransistor Availability of the battery Is not lighting the battery is disconnected Is lighting the battery is connected 280 AC 400 DC 18 19 Optotransistor Th...

Страница 13: ...ite the value to 321 The coefficient of reduction to an integer value is determined by a number of decimal places 1 0 10 1 00 100 1 000 1000 Table 13 Error codes for the MODBUS protocol Error code Nam...

Страница 14: ...s Addresses of the slave devices are in the range from 1 to 247 Figure 10 shows the ASCII frame format 1 byte Address Function code Data CRC checksum CRLF 2 bytes 2 bytes 2 bytes Up to 504 bytes 2 byt...

Страница 15: ...tion 0x06 provides writing to one 321ABP register The master s request contains the address of the register and data for entering The answer of the device coincides with the request of the master unit...

Страница 16: ...ored at the temperature from minus 45 to 60 C and relative humidity of no more than 80 10 ACCEPTANCE CERTIFICATE PEF 321 has been manufactured and accepted in accordance with the requirements of valid...