EM-481 

 

                                                                                                                                                

NOVATEK-ELECTRO

 

described  in  Table  5.2).  For  example,  the  message  "r3h873  EXC.2  ILLEGAL  DATA  ADDRESS"  means  that  for 
device 3 register with address 873 is not readable (or absent). 
 

Table 5.2

 

– The standard Modbus exception codes 

 

Code 

Exception 

Description 

ILLEGAL FUNCTION 

The received function code cannot be processed 

ILLEGAL DATA ADDRESS 

The data address specified in the query is not available 

ILLEGAL DATA VALUE 

The value contained in the query data field is invalid value 

DEVICE FAILURE 

Unrecoverable  error  has  occurred  when  the  addressee  has  tried  to 
perform the requested action 

ACKNOWLEDGE 

The addressee accepted the request and processed it, but it takes a long time 

DEVICE BUSY 

The addressee is busy processing the command. The client can retry the 
message later 

MEMORY PARITY ERROR 

The  parity  error  was  detected  when  the  addressee  has  tried  to  read  the 
extended memory 

10 

GATEWAY PATHS NOT 

AVAILABLE 

The gateway cannot redirect the query, since there is no path (connection) 
to the addressee 

11 

TARGET DEVICE FAILED TO 

RESPOND TO GATEWAY 

The gateway did not receive a response to the forwarded query, because 
the addressee did not respond on time  

 

5.2.2.5.

 Data collection and event tracking 

When  action  logic  program  is  loaded  into  the  internal  memory,  the  device  reads  the  specified  registers 

(connected devices or EM-481) at a specified interval, then performs the specified conversions and evaluates the 
received  data.  As  a  result,  the  following  actions  can  be  performed:  SMS  sending,  writing  to  the  specified  register 
(connected  device  or  EM-481).  The  program  is  loaded  into  the  internal  memory  from  the  memory  card.  The 
procedure for preparing and downloading the program into the device is described in Appendix C. 

 

5.3. Configuration 
5.3.1.

 General 

The  connection  settings  of  EM-481  is  made  via 

HTTP

  protocol  or  via 

Modbus  TCP

  protocol  and  serves  for 

specifying the main parameters needed for the device operation: types of connected sensors, exchange parameters 
via RS

-

485, parameters of address in Ethernet network (if Ethernet is used) and server address to which EM-481 is 

connected automatically

.  

The adjustable parameters are described in items 5.3.2. The parameters remain saved after the power cut off. 
EM-481 setting can be made by two methods: 

  Via WEB-interface (it.

 

5.3.3); 

  Via Modbus-interface

 

(it. 5.3.4). 

ATTENTION! WHEN CHANGING EM-481PARAMETERS, THE VALUES MAY BE SET THAT INTERFERE OR 

BLOCK  THE  CONNECTIONS  TO  IT  IN  THE  NETWORKS.  IN  THIS  CASE,  THE  PARAMETERS  SHOULD  BE 
RESETTED TO THE FACTORY VALUES. 

Safely  remove  of  the  memory  card,  restarting  the  device  or  reset  of  settings  to  factory  values  is  executed  by 

means of the 

“R” 

button available through a hole on a front panel. The button is pressed by a thin subject

The reset of the device to factory settings:

 

  press  and  hold  the  reset  button 

“R”

  for  not  less  than  8  seconds  (after  2  seconds  of  holding  the  indicator 

“AL”

 will light on); after 8 seconds of holding the device will restart, the indicators will blink one time; 

  then release the button 

“R”

To restart the device with saving of the user’s settings: 

 

– press and hold the reset button 

“R”

 during time from 2 to 8 seconds; 

 

– when

 

“AL”

 

indicator lights on, release the button

 

“R”

To display information about connections or safely remove of the memory card:

 

  press  and  release  the  reset  button 

"R"

,  the  display  shows  information  about  connections,  the  indicator 

"Memory SD" will go out. Remove the memory card, if necessary.

 

 

5.3.2.

 EM-481 parameters 

The  sets  of  parameters  available  via  MODBUS  protocol  are  provided in  Table 5.3.  The  internal  structure  of  all 

sets of parameters is similar to the structure of a set provided in Table 5.8, for exception of the initial address. 

The format of parameters presentation in MODBUS registers is described in Table 5.4. 
Parameters describing the device are given in Table 5.5.

 

The parameters of the device current mode are available for reading and writing and are provided in Table 5.6

The parameters of current state are available only for reading and are described in Table 5.7. 
The setting parameters are available only in the setting mode and are listed in Table 5.8. 
 

Table 5.3

 

– The sets of parameters available via Modbus protocol 

 

Set 

Description 

Access 

Address 

Содержание EM-481

Страница 1: ...development and production complies with the requirements of ISO 9001 2015 Dear Customer NOVATEK ELECTRO Ltd Company thanks you for purchasing our products You will be able to use properly the device...

Страница 2: ...d via RS 485 9 5 2 2 3 Access to MODBUS network using MODBUS TCP 9 5 2 2 4 Access to MODBUS network using SMS 9 5 2 2 5 Data collection and event tracking 10 5 3 Configuration 10 5 3 1 General 10 5 3...

Страница 3: ...THE HOUSING IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE DEVICE During operation and maintenance the regulatory document requirements must be met namely Regulations fo...

Страница 4: ...ing and transferring data IP protocol is routable protocol for transferring data by Ethernet It is a part of TCP IP and used for Internet IP address is a node address which is unique within a single n...

Страница 5: ...showing of warnings about detected faults 4 GSM LED is blinking every 3 sec when there is connection via GSM network or UMTS it is blinking 3 times per second while data exchanging via GPRS or HSPA 5...

Страница 6: ...ort circuit output voltage of driver RS 485 maximum mA 250 Resistance of in built terminator Ohm 1000 The recommended number of connected devices in Modbus network when the input current of receivers...

Страница 7: ...vice operation Check the device for damage after transportation in case of such damages detection contact the supplier or the manufacturer Carefully study the Operating Manual pay special attention to...

Страница 8: ...in the SIM slot and connect the GSM antenna to the ANT connector SMA F connector 5 2 Using the device 5 2 1 General After power is turned on all indicators except LAN and GSM light up and EM 481 perf...

Страница 9: ...addresses identifiers If the query could not be redirected for example in the RS 485 slave mode if the connection to the remote MODBUS TCP server was terminated the EM 481 can generate and send the MO...

Страница 10: ...ters of address in Ethernet network if Ethernet is used and server address to which EM 481 is connected automatically The adjustable parameters are described in items 5 3 2 The parameters remain saved...

Страница 11: ...ess MAC 48 from left to right 6 Table 5 5 Parameters describing the device Parameter Description Address Device type The code that defines the MODBUS product by the manufacturer 23 EM 481 0 Firmware v...

Страница 12: ...d access tabs 0 no permission 1 there is permission Bit 6 It is always as 1 Bit 7 Permission for the connected client to configure EM 481 the same as register 121 0 no permission 1 there is permission...

Страница 13: ...on to remote server Modbus TCP 0 connection to the remote server is set 1 connecting to the remote server 2 65534 the number of seconds before reconnecting 65535 Connection to the Modbus TCP server is...

Страница 14: ...parameters Parameter Range of values Factory setting Description Address Ethernet network Static IP address IP address 192 168 0 111 If the dynamic addressing is switched off or not available IP addre...

Страница 15: ...vice provider up to 24 characters 392 415 APN address of host Character string Provided by the GSM service provider up to 34 characters there cannot be spaces in a string 416 449 MODBUS TCP clients Co...

Страница 16: ...tart bit 7 data bits 2 stop bits or parity bit and stop bit total is 10 bits The non standard byte formats register 461 values 4 and 5 are not available in this case format 3 2 stop bits is used inste...

Страница 17: ...ssword This string should not have any spaces 540 549 The specified password for recording per mission via MODBUS TCP in devices using RS 485 Character string It is used to access devices connected to...

Страница 18: ...Gateway Path Unavailable response is not returned to the client 1 255 if there is no connection to the query addressee this exception code is returned to the client 636 Enable RS 485 slave mode 0 1 0...

Страница 19: ...aylight saving time 1 10 10 It is used if you selected the automatic transition to daylight saving time on the specified days Week of the month when the clock will be set one hour ahead 1 5 week of th...

Страница 20: ...f clock for synchroniza tion s 1 180 2 It is used if you have enabled synchronization of clocks with the server clock The synchronization is performed after receiving the server time if the difference...

Страница 21: ...ears once again 5 3 4 EM 481 configuring via MODBUS interface Setting via Modbus interface shall be provided if the device is connected using the Modbus client which is supporting the Modbus TCP proto...

Страница 22: ...return and transfer it to the warranty post warranty service please indicate detailed reason for the return in the field of the claims data 8 TRANSPORTATION AND STORAGE The device in the original pack...

Страница 23: ...in the GSM network is displayed alternately with the IP address in the local Ethernet network The operation speed with remote Modbus TCP server is improved The speed of GSM operation is increased 30...

Страница 24: ...481 Parameter Value Addressing using DHCP Yes IP address 192 168 0 111 Subnet mask 255 255 255 0 Gateway 192 168 0 1 With the factory settings of the EM 481 two ways are possible for communicating wi...

Страница 25: ...ter closing the windows answer yes 3 Connection to Internet via Ethernet ATTENTION THE USER IS STRONGLY RECOMMENDED TO CONNECT THE UNIT TO INTERNET UNDER THE SUPERVISION OF THE LAN SYSTEM ADMINISTRATO...

Страница 26: ...om the client over the long period the access returns to locked mode ATTENTION DURING ANY CONNECTIONS EXCEPT FOR TRANSMITTING VIA GSM AND COMMUNICATION WITH SERVER VIA SPECIAL PROTOCOL EM 481 THE PASS...

Страница 27: ...age in order to delete the device from Overvis system That guarantees that the EM 481 device will be used only by the authorized users Using the instruction on the site of Overvis system connect to EM...

Страница 28: ...again the internal memory to re read the program Files can have arbitrary names and extensions and placed in subfolders of the folder TASKS Files placed directly in the folder TASKS allow you to use...

Страница 29: ...s The file can contain comment lines that begin with and are ignored when reading the file Correct example Incorrect example This is a comment VARS number of seconds per minute 0 VAL 60 1 VAL 1 This i...

Страница 30: ...eters in the task file which are accessed through RS 485 and GSM interfaces By default if no modifier is specified it is 0 PARAMACTUAL ushort Frequency of reading the parameters in seconds It allows o...

Страница 31: ...in a single query WRHMULTIPLE uchar uchar Device can write only using function 16 in the storage registers The first argument specifies how many registers can be read in one query the second one deter...

Страница 32: ...point 100 F32BLEEP3R 32 bit with reverse order of bytes and floating point 1000 F32WLEEP0R 32 bit with reverse order of words and floating point F32WLEEP1R 32 bit with reverse order of words and floa...

Страница 33: ...all variables in the specified range VARSMINIDX var ref var ref The number of the minimum variable in the specified range VARSMAX var ref var ref Maximum of all variables in the specified range VARSMA...

Страница 34: ...ref Copy of the condition CONDIS int Set to the specified value The condition is met if the value is not 0 It can be used for adjustment or for unconditional actions for each update cycle NOT cond ref...

Страница 35: ...has the following format index action type argument 1 argument 2 Index the sequential number of the line The types of the arguments int 32 bit signed integer alarm reason is the number of reason of t...

Страница 36: ...n the text 3 MODBUS ID of the device is OM 310 240 is the register address which is monitored for the fault enabling relay 1 depending on bit 0 of register 240 of device 3 META 8th version of Protocol...

Страница 37: ...hieving the temperature respectively the lower or upper limits These registers are read only To change them you should be in configuration mode see it 5 3 4 then write the desired values to addresses...

Страница 38: ...VARGEVAR V2 V1 in other cases do not change the hysteresis current value 2 CONDIS 1 VARS the desired hysteresis is selected from V3 V5 according to the conditions of C0 C2 6 VARSSELBYC V3 C0 CONDS is...

Страница 39: ...ting select the file of updating The procedure for file selection is given in Table D 2 To cancel the updating cut off the power supply of EM 481 or wait until automatic completion of updating mode Ta...

Страница 40: ...Similar to No 2 but the file with an error has less priority The error is automatically corrected with available files of updating 4 The files of updating are not available Escape from the mode of upd...

Отзывы: